Unit data KWE 800-1150 Eco
Series
KWE
800 Eco
KWE
970 Eco
KWE
1060 Eco
KWE
1150 Eco
Operating mode
Air-cooled chiller for external installation in high-effi-
ciency design for cooling
Nominal cooling output
1)
kW
79.3
97.2
106.4
115.9
SEER
4.8
5.4
5.5
4.8
Annual room cooling efficiency
ŋ
S,C
%
182
208
212
184
Adjustment range - return temperature
cooling
°C
+5 to +18
Operating range, cooling
°C
+5 to +48 / -15 to +48
3)
Cooling circuits, number
1
2
Refrigerant
R452B
GWP value
676
Refrigerant filling quantity
kg
10.0
12.5
13.0
CO
2
equivalent
t
6.8
8.5
8.8
Compressor, number
2
4
Nominal flow rate
m
3
/h
19,500
28,000
39,000
Number of fans
1
2
Sound pressure level
2)
dB (A)
55.2
52.6
57.3
57.2
Sound power level
dB (A)
86.8
84.4
89.1
Power supply
V/Ph/Hz
400/3~N / 50
Enclosure class
IP
X4
Electrical current consumption, max.
A
80.3
110.3
116.3
126.3
Electrical rated power consumption,
cooling
kW
26.3
28.6
33.4
37.0
Electrical rated current consumption,
cooling
A
47.5
51.6
60.3
66.8
Operating medium
Water; max. 35% ethylene glycol, max. 35% propy-
lene glycol
Operating pressure, medium, max.
kPa
800
Nominal flow rate, cooling
m
3
/h
13.8
16.2
17.7
20.0
Minimum flow volume, medium
m
3
/h
8.3
9.7
10.6
12.0
Maximum flow volume, medium
m
3
/h
22.0
25.9
28.3
31.9
Pressure loss, indoor
kPa
54.1
56.2
67.3
49.4