8.3 Electrical components
Electrical components and safety equipment
Pressure switch cooling cycle HP and LP
There is a high pressure switch (HP) in the hot gas
line within the cooling circuit to for switching off the
chiller in the event of insufficient heat dissipation. A
low pressure switch (LP) in the suction pipe or in
the compressor switches off the chiller if the fill
level for the refrigerant is too low.
Flow switch
The flow switch monitors the medium flow rate and
switches the unit off if the flow rate drops below the
minimum medium flow rate. This component is
therefore largely responsible for the protection of
the unit and so its function must not be changed in
any way.
Condenser fan thermal contacts
The condenser fan's thermal contacts prevent
overheating of the motors.
Compressor thermal contact
The thermal contact is located within the com-
pressor and limits its hot gas end temperature.
Phase sequence relay
The phase sequence relay controls the direction of
rotation for the power supply. The controller will not
be enabled if the direction of rotation is wrong.
Probe medium inlet
The probe is located at the unit's medium inlet
(system return flow). It serves to detect the current
temperature to regulate the setpoint.
Probe medium outlet
The probe is located at the unit's medium outlet
(system inlet). It serves to detect the current tem-
perature and check the anti-freeze protection tem-
perature.
9
Leak testing
The leak test is carried out after the connection
has been made.
1.
Flush the system twice with tap water.
2.
Clean the sieve insert on the dirt trap.
3.
Fill the system with water again and bleed
the unit at the manual bleed valves.
4.
Adjust the test pressure to at least 200 kPa
(2.0 bar).
5.
Check the connections after a period of at
least 24 hours for leaking water. If water is
visible, the connection has not been estab-
lished properly. Tighten the connection or
establish a new connection.
6.
After a successful leak test, remove the
excess pressure from the medium piping if a
water-glycol mixture is used or adjust the
non-circulating pressure to the required
system pressure.