8 - PARAMETER QUICK REFERENCE GUIDE
49'1329 e
GV3000/SE
8 - 3
GV3000/SE Regulator, General Parameters (P.xxx)
(continued)
* =
Parameter tuneable at drive stopped or running; all others adjust with drive stopped.
N/A
= not available
Para-
meter
Description
Selection / Adjustment Range
EUr-Init.
Setting
Actual
Setting
*P.034
Preset Speed 4
Value of P.003 to P.004 in Hz
(on type V/Hz)
Value of P.003 to P.004 in RPM
(on type Vector)
5.0 Hz
150RPM
*P.035
Preset Speed 5
Value of P.003 to P.004 in Hz
(on type V/Hz)
Value of P.003 to P.004 in RPM
(on type Vector)
5.0 Hz
150RPM
*P.036
Preset Speed 6
Value of P.003 to P.004 in Hz
(on type V/Hz)
Value of P.003 to P.004 in RPM
(on type Vector)
5.0 Hz
150RPM
*P.037
Preset Speed 7
Value of P.003 to P.004 in Hz
(on type V/Hz)
Value of P.003 to P.004 in RPM
(on type Vector)
5.0 Hz
150RPM
*P.038
Preset Speed 8
Value of P.003 to P.004 in Hz
(on type V/Hz)
Value of P.003 to P.004 in RPM
(on type Vector)
5.0 Hz
150RPM
*P.039
Encoder Loss Enable
OFF = Disable encoder loss
diagnostic.
ON = Enable encoder loss diagnostic.
OFF
P.040
Motor Thermal Overload
Enable
OFF = Disable Electronic Motor Thermal Overload function
ON = Enable Electronic Motor Thermal Overload function
ON
P.041
Motor Thermal Overload Type
nC = Standard motor without cooling
FC = Forced cooled motor
FC
P.042
Line Dip Ride Through Time
0.1 - 999.9 sec
(on type V/Hz)
500ms
(on type Vector)
5s
500ms
P.043
Fault Auto Reset, Attempts
1 -10 Attempts
0
P.044
Fault Auto Reset, Time Interval 1 -60 sec
8s
P.045
Output Phase Loss Enable
OFF = Disable output phase loss
diagnostic
ON = Enable output phase loss diagnostic
ON
P.047
(1)
Carrier Frequency,
influences Power Unit Output
Amps (P.095)
2 = 2 kHz Carrier frequency
Defaults are power module-
4 = 4 kHz Carrier frequency
depend.: up to 43A: 8 kHz
8 = 8 kHz Carrier frequency
58A and above: 2 kHz
8 or 2
P.M.
depend.
P.048
V/Hz or Vector Mode
Regulation
UEC = Vector Control
U-H = V/Hz Control
U-H
P.049
Country Defaults
USA = North American defaults
EUr = European defaults
JPn = Japanese defaults
EUr
P.050
Restore Defaults
(to selection P.049)
OFF = No action
ON = Restore Default Settings for (P.xxx only) to selected
Default Type (P.049)
OFF
*P.051
Programming Disable
For password refer to Chapter 3, 'Program Mode'
0
*P.052
AUTO/MAN Key Disable
OFF = Enable the AUTO/MAN key regardless of control s.
ON = Disable the AUTO/MAN key except from the selected
control source
OFF
*P.053
Manual Reference Preset
Enable
OFF = Do not preset the manual reference
ON = preset the manual reference with the auto reference at
the transition from AUTO to MANUAL.
OFF
P.054
Level Sense Start Enable
OFF = Start input is edge-sensitive
ON = Start input is level-sensitive
OFF
*P.055
STOP/RESET Key Disable
OFF = Enable the STOP/RESET key regardless of control
source.
ON = Disable the STOP/RESET key except from the
selected control source
OFF
P.060
Network Drop Number
Network-dependent
1
P.061
Network Connection Type
Network-dependent
1
*P.062
Option Port:
Communication Loss
Response
Network-dependent
0
Note:
(1) P.047, P.005 and H.000 must be set before activating at V/Hz mode the Identification Request (H.020)
Содержание GV3000SE
Страница 2: ......
Страница 4: ......
Страница 5: ...GV3000 SE Power Units Instruction Manual User Manual 49 1327e 11...
Страница 6: ......
Страница 8: ......
Страница 14: ...2 DESCRIPTION 2 4 GV3000 SE 49 1327 e PE Figure 2 2b Typical System Block Diagram Type GV3000 SE AC024 and 030...
Страница 77: ......
Страница 80: ......
Страница 86: ...2 2 GV3000 SE 49 1329 e...
Страница 94: ...3 8 GV3000 SE 49 1329 e...
Страница 134: ...4 40 GV3000 SE 49 1329 e...
Страница 188: ...7 10 GV3000 SE 49 1329 e...
Страница 196: ...8 8 GV3000 SE 49 1329 e...
Страница 197: ......