![Reliance electric GV3000SE Скачать руководство пользователя страница 189](http://html1.mh-extra.com/html/reliance-electric/gv3000se/gv3000se_instruction-manual_1436345189.webp)
8 - PARAMETER QUICK REFERENCE GUIDE
49'1329 e
GV3000/SE
8 - 1
GV3000/SE Regulator, General Parameters (P.xxx)
* =
Parameter tuneable at drive stopped or running; all others adjust with drive stopped.
Para-
meter
Description
Selection / Adjustment Range
EUr-Init.
Setting
Actual
Setting
P.000
Control Source
(Selection ‘OP’ only available
with optional-Card installed)
LOCL - Local keypad/display
rE
- Terminal strip remote inputs
OP
- Option Port (InterBus, Profibus, DeviceNet, AMX)
SErL
- Serial port (CS3000 or OIM*)
LOCL
*P.001
Acceleration Time, Ramp 1
1.0 - 999.9 s
(on type V/Hz)
20.0s
0.1 - 999.9 s
(on type Vector)
*P.002
Deceleration Time, Ramp 1
1.0 - 999.9 s
(on type V/Hz)
20.0s
0.1 - 999.9 s
(on type Vector)
*P.003
Minimum Speed
0.5 Hz - Value of P.004 in Hz
(on type V/Hz)
0 RPM - Value of P.004 in RPM
(on type Vector)
5.0 Hz
150
RPM
*P.004
Maximum Speed
0.5 Hz - Value of H.022, max. 200Hz
(on type V/Hz)
(H.022, Over-frequency limit)
0 RPM - U.017 (Motor Top speed)
(on type Vector)
50.0 Hz
1400
RPM
*P.005
(1)
Inverter Current Limit
50 - 100% or 110% of Power Unit Outp. Amps P.095 (V/Hz)
U.006 - 150% of value in U.004
(Vector)
100%
150%
*P.006
Expand to Second Menu List
'2nd menu' password. Refer to Section 3 of this manual.
0
P.007
Terminal Strip Digital Input
Configure
0 = Dig6= FWD/REV, DIG7=RAMP1/2,
DIG8=REM/LOC
1 =
DIG7=FWD/REV,
DIG8=RAMP1/2
2 =
DIG7=FWD/REV,
DIG8=REM/LOC
3 =
DIG7=RAMP1/2,
DIG8=REM/LOC
4 =
DIG8=FWD/REV
5 =
DIG8=RAMP1/2
6 =
DIG8=REM/LOC
7 =
not used
not used
not used
8 =
FWD/REV
TRQ/SPD
REM/LOC
9 =
not used
TRQ/SPD
REM/LOC
10 =
not used
TRQ/SPD
FWD/REV
11 =
not used
TRQ/SPD
RAMP1/2
12 =
not used
not used
TRQ/SPD
0
P.008
Terminal Strip Speed
Reference Source
With P.007 set to '7':
0 = Analog Reference
1 = MOP (uses dig. input 6 MOP inc., inp. 7 MOP decrease)
2 = 2 Preset Speeds (uses digital input 6)
3 = 4 Preset Speeds (uses digital inputs 6-7)
4 = 8 Preset Speeds (uses all terminal strip digital inputs)
5 = Analog Ref. and 1 preset speed (uses digital input 6)
6 = Analog Ref. and 3 preset speeds (uses digital inputs 6-7)
7 = Analog Ref. and 7 preset speeds (uses all digital inputs)
0
*P.009
(2)
Term. Strip Analog Input Offset (-)900 - (+)900
0
*P.010
(2)
Term. Strip Analog Input Gain
0.100 - 5.000
1.000
*P.011
(2) (3)
Term. Strip Analog Input
Configure
* Alarm, drive continues to run
using the value of the
analog input 4 to 5 seconds
prior to loss.
** Alarm, drive continues to run
using Preset Speed 1
(P.031)
0 = +/- 10 VDC
Jumper J4 pins 2-3
1 = +/- 10 VDC inverted
J4 pins 2-3
2 = 0 to 10 VDC
J4 pins 2-3
3 = 0 to 10 VDC inverted
J4 pins 2-3
4 = 4 to 20 mA
(fault > 2 mA)
J4 pins 1-2
5 = 4 to 20 mA inverted
(fault > 2 mA)
J4 pins 1-2
6 = 0 to 20 mA
J4 pins 1-2
7 = 0 to 20 mA inverted
J4 pins 1-2
8 = 4 to 20 mA
( * alarm > 2 mA)
J4 pins 1-2
9 = 4 to 20 mA inverted
( * alarm > 2 mA)
J4 pins 1-2
10 = 4 to 20 mA
(** alarm > 2 mA)
J4 pins 1-2
11 = 4 to 20 mA inverted (** alarm > 2 mA)
J4 pins 1-2
12 = 0 to 10 VDC Start and stop the drive
based on analog input value.
J4 pins 2-3
2
*P.012
Terminal Strip Analog Output
Source
0 = Speed /Frequency feedback
bipolar
1 = Current
feedback
bipolar
2 = Speed /Frequency feedback
unipolar
3 = Current
feedback
unipolar
0
Notes: (1) P.047, P.005 and H.000 must be set before activating at V/Hz mode the Identification Request (H.020)
(2) This parameter is not used at Vector Torque Reference (U.000=1)
(3) Inverting of rotation is only effective with P.027 at 0.
Содержание GV3000SE
Страница 2: ......
Страница 4: ......
Страница 5: ...GV3000 SE Power Units Instruction Manual User Manual 49 1327e 11...
Страница 6: ......
Страница 8: ......
Страница 14: ...2 DESCRIPTION 2 4 GV3000 SE 49 1327 e PE Figure 2 2b Typical System Block Diagram Type GV3000 SE AC024 and 030...
Страница 77: ......
Страница 80: ......
Страница 86: ...2 2 GV3000 SE 49 1329 e...
Страница 94: ...3 8 GV3000 SE 49 1329 e...
Страница 134: ...4 40 GV3000 SE 49 1329 e...
Страница 188: ...7 10 GV3000 SE 49 1329 e...
Страница 196: ...8 8 GV3000 SE 49 1329 e...
Страница 197: ......