B-4
USB Converter User Manual
05
[DF1 Packets Rcvd
Displays the number of DF1 packets
received by the converter. The value of
this parameter is normally approximately
equal to the value of
DF1 Packets Sent
(04)
.
Default:
0
Minimum: 0
Maximum: 65535
Type:
Read Only
06
RTU DSI Addr Cfg
Sets the node address of the converter for
use with the converter operating mode set
with
Adapter Cfg (01)
. In Auto, Master or
Slave mode, the converter node address
can be any valid value. In RTU Master or
RTU Master Passthru mode, the converter
node address must match the address of
any drive on the network. Each network
drive address, set using Comm Node
Addr (104), must be unique. In any case,
the RTU DSI address is a decimal value.
Default:
1
Minimum: 1
Maximum: 247
Type:
Read/Write
Reset Required: Yes
07
RTU DSI Addr Act
Displays the node address of the drive
with which the converter is communicating
when the converter is set to RTU Master
or RTU Passthru mode using
Adapter
Cfg (01)
.
Default:
1
Minimum: 1
Maximum: 247
Type:
Read Only
08
Adapter Type
Displays the present operating mode for
the converter.
Default:
0 = Master
Values:
0 = Master
1 = Slave
2 = RTU Master
3 = RTU Passthru
Type:
Read Only
No.
Name and Description
Details
Содержание 1203-USB
Страница 1: ...Instruction Manual USB Converter 1203 USB D2 3559...
Страница 4: ...II USB Converter User Manual Appendix A A 1 Appendix B B 1 Appendix C C 1 Appendix D D 1 Glossary...
Страница 6: ...1 2 USB Converter User Manual...
Страница 28: ...4 10 USB Converter User Manual...
Страница 42: ...A 4 USB Converter User Manual...
Страница 56: ...C 10 USB Converter User Manual...
Страница 65: ...Using RTU Master Mode D 9...
Страница 66: ...D 10 USB Converter User Manual...
Страница 70: ...Glossary 4 USB Converter User Manual...
Страница 74: ...Index 4 USB Converter User Manual...
Страница 75: ......