Troubleshooting
5-3
Table 5.3 – RX Status Indicator
Status
Cause
Corrective Action
Off
Converter is not receiving
data.
•
Verify that data is being
transmitted by the PC.
•
Securely connect cables.
•
Apply power to the drive.
•
Configure the computer
software to use the same port
rate as the converter.
Flashing
Green
Converter is receiving data
from the computer.
No action required.
Table 5.4 – TX Status Indicator
Status
Cause
Corrective Action
Off
Converter is not transmitting
data.
•
Verify that data is being
transmitted.
•
Securely connect cables.
•
Apply power to the drive.
Flashing
Green
Converter is transmitting data
to the computer.
No action required.