Installation Instructions

   When used on wet pipe systems, Reliable Model F3QR56 

dry sprinklers may be installed in ductile or malleable cast iron 

threaded  tees,  or  CPVC  tees  and  adapters  upon  verification 
that the sprinkler inlet fitting does not interfere with the interior 
of the fitting (see Figure 12). 

   When used on dry pipe systems, Reliable Model F3QR56 

dry pendent sprinklers MUST ONLY BE installed in the outlets 

of ductile or malleable cast iron threaded tees on horizontal pipe 
such that the inlet of the sprinkler protrudes above the bottom 
level of the pipe. 

   When used on dry pipe systems, Reliable Model F3QR56 

dry sidewall and dry upright sprinklers may be installed in duc-
tile or malleable cast iron threaded tees, or CPVC tees and 

adapters upon verification that the sprinkler inlet fitting does not 
interfere with the interior of the fitting (see Figure 12).

   DO NOT install Reliable dry sprinklers into elbows or cou-

plings, welded outlets, mechanical tees, or gasket sealed CPVC 

fittings.

   Dry sprinklers connected to wet pipe systems must be in-

stalled as indicated in Figure 11 and as required by NFPA 13 

with the Exposed Minimum Barrel Length located in a heated 

area.

An orange protective clip is factory installed on the sprinkler 

to protect the glass bulb thermal element from damage. The 
clip should remain in place during installation of the sprinkler 
and be removed when the sprinkler system is placed in service. 
Sprinklers with 3/4” NPT and ISO7-1R3/4 inlets are supplied 
with a protective cap on the inlet that must be removed before 
installation.

Use the following steps for installation:

1.  Cut a hole in the wall or ceiling directly in-line with the 

outlet of the fitting. See the Installation Data table for the 

recommended hole diameter based on the escutcheon 
or cover plate option selected.

2.  Apply pipe joint compound or PTFE tape to the male 

threads of the sprinkler’s inlet fitting.

3. 

Install  the  sprinkler  in  the  fitting  using  the  installation 
wrench specified in the Installation Data table. The Mod

-

el F3R wrench is designed to be inserted into the groves 
in the sprinkler’s wrench boss as shown in Fig. 13. The 

Model XLO2 wrench is designed to fit into the cup and 

engage the wrench boss as shown in Fig. 14. Do NOT 
wrench any part of the sprinkler assembly other than the 
wrench boss. When inserting or removing the wrench 
from the sprinkler, care should be taken to prevent dam-
age to the sprinkler. The sprinkler is then tightened into 

the  pipe  fitting  to  achieve  a  leak  free  connection.  The 

recommended minimum to maximum installation torque 
is 22 - 30 lb-ft (30 – 40 N-m) for 1” NPT and ISO7-1R1 
sprinklers, and 14 - 20 lb-ft (19 – 27 N-m) for 3/4” NPT 
and ISO7-1R3/4 sprinklers.

3a. Alternatively, where access to the outer tube of the 

sprinkler is available, the Model F3QR56 Dry sprin-
kler may be installed using a pipe wrench. The pipe 
wrench shall only be permitted to interface with the 
galvanized steel outer tube portion of the sprinkler 
(Item #8 in Fig. 15). Do NOT wrench any other por-
tion of the sprinkler assembly. A pipe wrench can in-

stall the sprinkler into the fitting with a large amount 

of torque; consideration should be given to the need 
for future removal of the sprinkler because the instal-
lation torque will have to be matched or exceeded to 
remove the sprinkler. The recommended minimum to 
maximum installation torque is 22 - 30 lb-ft (30 – 40 
N-m) for 1” NPT and ISO7-1R1 sprinklers, and 14 - 
20 lb-ft (19 – 27 N-m) for 3/4” NPT and ISO7-1R3/4 
sprinklers.

4.  Standard and Model HB escutcheons can be installed 

by slipping the escutcheon over the can until the es-
cutcheon is seated against the ceiling or wall. Model F1 
escutcheons are installed by pressing the escutcheon 
onto the collar until the escutcheon is seated against 
the ceiling or wall. The Model FP escutcheon is installed 
by pressing or threading the escutcheon into the cup 
by hand; the escutcheon can be tightened against the 
ceiling or wall by turning the escutcheon in a clockwise 
direction and removed by turning the escutcheon in a 
counter-clockwise direction. To install the Model CCP 

cover  plate,  first  remove  the  protective  clip.  Install  the 

Model CCP cover plate on the sprinkler by pressing or 
threading the cover plate into the cup by hand; the cov-
er plate can be tightened against the ceiling by turning 
the cover plate in a clockwise direction and removed by 
turning the cover plate in a counter-clockwise direction. 

5.  Remove the orange protective clip when placing the 

sprinkler system in service.

18.

Содержание F3QR56

Страница 1: ...re quick response standard coverage sprinklers with a nominal K Factor of 5 6 80 metric Available in Dry Pendent Dry Horizontal Sidewall and Dry Up right configurations Model F3QR56 Dry sprinklers all...

Страница 2: ...2 to 48 50 to 1200 mm cULus FM NYC 1 NPT or ISO7 1R1 HB Extended Escutcheon 3 1 2 to 48 90 to 1200 mm F1 Recessed Escutcheon FP Recessed Escutcheon CCP Cover Plate F3QR56 Dry Horizontal Sidewall Stan...

Страница 3: ...rinkler Temperature Rating Cover Plate Temperature Rating Maximum Ceiling Temperature Listings and Approvals 1 Ordinary Orange 135 F 57 C 135 F 57 C 100 F 38 C cULus FM NYC Red 155 F 68 C Intermediate...

Страница 4: ...ments for 3 4 connections Sprinkler Guard Model C2 Finish Combinations Standard Escutcheon Sprinkler Escutcheon 2 3 Bronze Polished Stainless Bronze Laquered Brass Chrome Polished Stainless White Poly...

Страница 5: ...12 7mm to 12 7mm A dimension adjustment range Fig 2 5 Sprinkler Guard Model C2 Finish Combinations HB Escutcheon Sprinkler Escutcheon 2 3 Bronze Chrome Chrome Chrome White Polyester 1 White Polyester...

Страница 6: ...or 3 4 connections Finish Combinations FP Recessed Escutcheon Sprinkler 1 Escutcheon 3 4 Bronze Chrome Bronze Brass Chrome Chrome White Polyester 2 White Polyester Black Polyester 2 Black Polyester Cu...

Страница 7: ...the Model F3QR56 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have positive pressure in the space above Fig 4 7 Finish Combinations CCP Conical Cover Plate Sprinkler Cover P...

Страница 8: ...g 5 8 Finish Combinations F1 Recessed Escutcheon Sprinkler Escutcheon 2 3 Bronze Chrome Bronze Brass Chrome Chrome White Polyester 1 White Polyester Black Polyester 1 Black Polyester Custom Color Poly...

Страница 9: ...m in 1 4 6mm increments for 3 4 connections Finish Combinations Standard Escutcheon Sprinkler Escutcheon 2 3 Bronze Polished Stainless Bronze Laquered Brass Chrome Polished Stainless White Polyester 1...

Страница 10: ...djustment provides 12 7mm to 12 7mm A dimension adjustment range Fig 7 Finish Combinations HB Escutcheon Sprinkler Escutcheon 2 3 Bronze Chrome Chrome Chrome White Polyester 1 White Polyester Black Po...

Страница 11: ...ith respect to the protected space Fig 8 Finish Combinations FP Recessed Escutcheon Sprinkler 1 Escutcheon 3 4 Bronze Chrome Bronze Brass Chrome Chrome White Polyester 2 White Polyester Black Polyeste...

Страница 12: ...ctions Fig 9 Finish Combinations F1 Recessed Escutcheon Sprinkler Escutcheon 2 3 Bronze Chrome Bronze Brass Chrome Chrome White Polyester 1 White Polyester Black Polyester 1 Black Polyester Custom Col...

Страница 13: ...127 mm to 1219 mm Fig 10 Finish Combinations Upright Sprinkler Escutcheon Bronze NA Electroless Nickel PTFE 1 NA Notes 1 UL Listed as Corrosion Resistant 2 Escutcheons do not carry corrosion resistan...

Страница 14: ...Fig 11 14...

Страница 15: ...Fig 12 15...

Страница 16: ...Fig 14 Model XLO2 Wrench Fig 13 Model F3R Wrench 16...

Страница 17: ...Fig 15 17...

Страница 18: ...O2 wrench is designed to fit into the cup and engage the wrench boss as shown in Fig 14 Do NOT wrench any part of the sprinkler assembly other than the wrench boss When inserting or removing the wrenc...

Страница 19: ...rd Escutcheon 2 1 8 54 mm F3R Not Applicable HB Extended Escutcheon 2 1 2 64 mm F3R F1 Recessed Escutcheon 2 1 4 57 mm XLO2 FP Recessed Escutcheon 2 1 2 64 mm XLO2 CCP Cover Plate XLO2 F3QR56 Dry Hori...

Отзывы: