Application
Model F156, F142, F1XLH, F128 & Model F156, F142, F1XLH &
F128 Recessed sprinklers are used in fixed fire protection systems:
Wet, Dry, Deluge or Preaction. Care must exercised that the orifice
size, temperature rating, deflector style and sprinkler type are in ac-
cordance with the latest published standards of the National Fire
Protection Association or the approving Authority Having Jurisdic-
tion Installation.
Installation
Model F156, F142, F1XLH & F128 Series sprinklers are stan-
dard response sprinklers intended for installation as specified in
NFPA 13. They must also be installed with the Model W2 Sprinkler
Wrench specifically designed by Reliable for use with these sprin-
klers.
The Model F156, F142, F1XLH & F128 Recessed Sprinklers
are to be installed with a maximum recess of ¾ inch (19mm). The
Model F1, F2, and FP Escutcheon illustrated are the only recessed
escutcheon to be used with the Model F156, F142, F1XLH & F128
Recessed Sprinklers. The use of any other recessed escutcheon
will void all approvals and negate all warranties. When installing
Model F156, F142, F1XLH & F128 Recessed Sprinklers use the
Model GFR2 Sprinkler Wrench. Any other type of wrench may
damage these sprinklers.
Note:
A leak tight ½” NPT (R½) sprinkler joint can be obtained with
a torque of 8 - 18 ft-lbs (11 - 24 N-m). Do not tighten sprinklers over
maximum recommended torque. It may cause leakage or impair-
ment of the sprinklers.
Glass bulb sprinklers have orange covers to protect the bulb dur-
ing the installation process. REMOVE THIS PROTECTION ONLY
AFTER THE SYSTEM HAS BEEN HYDROSTATICALLY TESTED
AND, WHEN APPLICABLE, THE ESCUTCHEONS HAVE BEEN
INSTALLED. RASCO wrenches are designed to install sprinklers
when covers are in place.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Nominal K-Factor
4. Temperature Rating
5. Sprinkler Finish
6. Thread Type: [½” NPT] [ISO 7-1R½]
7. Escutcheon Finish (where applicable)
Note:
When Models F156, F142, F1XLH & F128 Recessed Sprinklers
are ordered, the sprinklers and escutcheons are packaged separately.
Escutcheon Data
(1)
(1)
SIN: RA1335 - cULus and FM permits use with F1 or F2 escutcheons for light
hazard only.
Maintenance
The Model F156, F142, F1XLH & Model F156, F142, F1X-
LH & F128 Recessed Sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia
or any other cleaning fluid. Replace any sprinkler which has
been painted (other than factory applied) or damaged in
any way. A stock of spare sprinklers should be maintained
to allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to minimize
the potential for damage to sprinklers that would cause im-
proper operation or non-operation.
Temperature Ratings
Classification
Sprinkler
Temperature
Max. Ambient
Temp.
Bulb
Color
°C
°F
Ordinary
Ordinary
Intermediate
Intermediate
High
(1)
Extra High
(1)
Ultra High
(1) (2)
57
68
79
93
141
182
260
135
155
175
200
286
360
500
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
300°F (149°C)
475°F (246°C)
Orange
Red
Yellow
Green
Blue
Mauve
Black
(1)
Not available for recessed Sprinklers.
(2)
cULus listed for SIN RA1325 and RA1314 only.
Maximum Working Pressure
175 psi (12 bar)
SIN RA1325 & RA1314 cULus listed for 250 psi (17 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finish
(1)
Standard Finishes
Sprinkler
Escutcheon
Bronze
Chrome
Polyester Coated
(6)(7)(9)
Brass
Chrome
White Painted
Special Application Finishes
Sprinkler
Escutcheon
Electroless Nickel PTFE
(3)(10)
Bright Brass
(2)
Black Plated
Black Paint
(3)(9)
Off White
(3)(9)
Chrome Dull
Lead Plated
(3)(4)(8)
Wax Coated
(3)(4)(5)(8)
Wax Over Lead
(3)(4)(5)(8)
Electroless Nickel PTFE
Bright Brass
Black Plated
Black Paint
Off White
Chrome Dull
(1)
Other colors and finishes are available on special order. Consult factory for
details. Custom color painted sprinklers may not retain their UL Corrosion
resistance listing.
(2)
200°F (93°C) maximum.
(3)
UL and ULC listed only.
(4)
155°F to 200°F (68°C to 93°C) ratings only.
(5)
286°F (141°C) sprinklers may be coated for ambient conditions not exceeding
150°F (66°C).
(6)
cULus listed “corrosion resistant” applies to SIN Number RA1325 (Upright)
RA1323 (upright), RA1321(Upright), RA1335 (HSW), RA1385(VSW) and
RA1314 (Pendent) in standard black or white. Corrosion resistance in other
polyester colors is available upon request.
(7)
FM Approved finish as “Polyester Coated” applies to SIN number RA1314,
RA1335 & RA1325 in standard black or white.
(8)
FM Approved finish applies only to SIN number RA1335 & RA1385.
(9)
LPCB and VdS Approved finish applies only to RA1325, RA1314 and RA1375.
(10)
cULus listed Corrosion Resistant applies to SIN RA1325 ,RA1314 ,RA1323,
RA1313 ,RA1321, RA1311, RA1385 and RA1335
5.