Technical data:

Models

Nominal K-Factor

Response

Thread

Size

Max.

Working

Pressure

Min.

Working

Pressure

Temperature

Rating

Finish

F156

5.6 (80 Metric)

Standard

½” NPT

(R½)

250 PSI

*

7 PSI

See

 “Temperature 

Ratings” Table

See

“Finish Table”

F142 

F1XLH

4.2 (60 Metric)

175 PSI

F128

2.8 (40 Metric)

Material Data:

Frame

Deflector

Load Screw

Pintle

Cup

Washer

Bulb

DZR Brass

QM Brass

CDA Alloy 260,

CDA Alloy 220

or

CDA Alloy 510

CDA Alloy 360

or

CDA Alloy 544

CDA Alloy 360

or

CDA Alloy 544

CDA Alloy 651

or

CDA Alloy 693  

Nickel Alloy 440 or Alloy 360

coated with PTFE Adhesive 

Tape

Glass

*Note:

 Model F156 upright, pendent, and recessed pendent sprinklers (SIN RA1325 and RA1314) are cULus Listed 

for 250 psi (17 bar).

2.

Model F142, F1XLH Upright

Содержание F1 Series

Страница 1: ...active Beautifully versatile is the description for the Reliable Models F156 F142 F1XLH F128 Series Recessed glass bulb sprinkler Recessing the F156 F142 F1XLH F128 Series enhances its already low profile decorative appearance and facilitates a rapid and perfect installa tion The recessed escutcheon of the Models F156 F142 F1XLH F128 are highly adjustable The two piece con struction makes field in...

Страница 2: ... F128 2 8 40 Metric Material Data Frame Deflector Load Screw Pintle Cup Washer Bulb DZR Brass QM Brass CDA Alloy 260 CDA Alloy 220 or CDA Alloy 510 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 651 or CDA Alloy 693 Nickel Alloy 440 or Alloy 360 coated with PTFE Adhesive Tape Glass Note Model F156 upright pendent and recessed pendent sprinklers SIN RA1325 and RA1314 are cU...

Страница 3: ...A1375 5 1 Refer to Bulletin 024 for Special Response Sprinklers F1S5 56 2 cULus Listed corrosion resistant Polyester coated sprinkler 3 Polyester coated FM Approved sprinkler 4 5 Polyester coated LPCB VdS approved sprinkler RA1325 RA1314 RA1375 6 Electroless Nickel PTFE Plated UL listed Corrosion Resistant Pendent Conventional Upright Model F156 F142 F1XLH F128 F1 or F2 Model F156 F142 F1XLH F128 ...

Страница 4: ... lead wax and wax over lead 4 Electroless Nickel PTFE Plated cULus listed Corrosion Resistant Model F156 Horizontal Sidewall Sprinkler Deflector HSW Installation Wrench Model W2 Sprinkler Wrench Installation Data Horizontal Sidewall Nominal Orifice Thread Size Nominal K Factor Sprinkler Height Approval Organizations Sprinkler Identification Numbers SIN US Metric Light Hazard Ordinary Hazard 15mm N...

Страница 5: ...t clean sprinklers with soap and water ammonia or any other cleaning fluid Replace any sprinkler which has been painted other than factory applied or damaged in any way A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprin klers Prior to installation sprinklers should be maintained in the original cartons and packaging until used to minimize the p...

Страница 6: ...rtment connection Reliable offers a wide selection of sprinkler components Following are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Offices 800 848 6051 Sales Fax 914 829 2042 Corporate Offices www reliablesprinkler com Internet Address Manufactured...

Отзывы: