5.1 - Connecting the collectors
For collector mounting follow the instructions in chapter
5.2. Fasten the
fi
rst collector and lay the following one
next to the
fi
rst one, maintaining a suf
fi
cient gap. Then
put the threaded
fi
ttings on both the upper and lower
outlets and push the collector to the already mounted
one until stop. Hold the
fi
tting with a spanner (Fig. 24)
to prevent turning, and tighten the nuts. Continue in the
same way with further collectors.
Put the insulation on the threaded
fi
ttings only
after a successful leak test.
5.2 - Interconnecting the collectors
Hydraulic interconnection of collectors shall be done
according to Fig. 23a. Maximum of 5 collectors may be
connected with threaded
fi
ttings in a row. If there are
more than 5 collectors in a row, a compensator shall be
installed in the middle of the array. With a compensator,
max. of 10 collectors in a row may be installed. The con-
necting pipes shall be lead the shortest way. The recom-
mended pipe diameters and
fl
ow rates through collector
arrays are shown in Tab. 1.
Collectors may be also connected as shown in Fig.
23b. This kind of connection is permitted when
up to 3
collectors are used and the max. fl ow rate is 1 l/min/
collector
. Then the cold liquid inlet is at one side bottom
and the hot liquid outlet is at the same side top. Both the
other ends shall be plugged..
A brass elbow shall be installed at the inlet to the collec-
tor array with a transition to the interconnection piping. At
the outlet from the collector array, a brass adapter shall
be installed that will enable connection to the piping.
The brass elbow and adapter are involved in Regulus
connection kits, code 10413 and 10414.
All solar components must be carefully and safely sea-
led and must be made of material resistant to glycol and
temperatures up to 160 °C. For connection piping we
recommend using KOMBIFLEX stainless-steel
fl
exible
pipes, or copper pipes joined by soldering.
5. HYDRAULIC CONNECTION
Fig. 23a:
The recom-
mended
method of
collector
intercon-
necting
Fig. 23b:
Alternative
one-sided
connection
method
Fig. 24: Col-
lector con-
necting (the
pic. shows
connection
of the upper
fi tting; the
lower fi tting
shall be
connected
and tighte-
ned in the
same way.)