88
Part V
Signals
RCPSettings.RegioDo4
X,3
38
4
Connected signal on DO4
RCPSettings.RegioDo5
X,3
39
0
Connected signal on DO5
RCPSettings.RegioDo6
X,3
40
5
Connected signal on DO6
RCPSettings.RegioDo7
X,3
41
6
Connected signal on DO7
RCPInternal.RegioNotUsedX X,3
42
-
Not
used
RCPInternal.RegioNotUsedX X,3
43
-
Not
used
RCPSettings.RegioModbusSlaveAddr X,3 44
Modbus
slave
address
RCPSettings.RegioModbusParity
X,3
45
2
Modbus parity bit:
0 = No parity bit
1 = Odd parity bit
2 = Even parity bit
RCPInternal.RegioNotUsedX X,3
46
-
Not
used
RCPInternal.RegioNotUsedX X,3
47
-
Not
used
RCPSettings.RegioDispBacklightLO
X,3
48
20
Display lighting low (0…255)
RCPSettings.RegioDispBacklightHi
X,3
49
100
Display lighting high (0…255)
RCPSettings.RegioDispContrast X,3
50
15
Contrast
(0…15)
RCPSettings.RegioDisplayViewMode
X,3
51
0
Select viewmode for the display:
0 = Room temp
1 = Heat setpoint
2 = Cool setpoint
3 = Average cool/heat setpoint
4 = Only setpoint offset
RCPInternal.RegioNotUsedX X,3
52
-
Not
used
RCPInternal.RegioNotUsedX X,3
53
-
Not
used
RCPInternal.RegioNotUsedX X,3
54
-
Not
used
RCPInternal.RegioNotUsedX X,3
55
-
Not
used
RCPSettings.RegioBypassTime
I,3
56
120 min
Time in Bypass mode (min)
RCPSettings.RegioPresenceOffTime
I,3
57
10 min
Off delay for changing to no presence
(min)
RCPSettings.RegioPresenceOnTime
I,3
58
0 min
On delay for changing to presence (min)
RCPSettings.RegioCVHeatPeriodTime I,3 59
60
sec
Period time if pulse prop. control valves
heating (sec)
RCPSettings.RegioCVCoolPeriodTime
I,3
60
60 sec
Period time if pulse prop. control valves
cooling (sec)
RCPSettings.RegioCVHeatRunTime
I,3
61
120 sec
Run time close to open valve heating
(sec)
RCPSettings.RegioCVCoolRunTime
I,3
62
120 sec
Run time close to open valve cooling
(sec)
RCPInternal.RegioNotUsedX X,3
63
-
Not
used
RCPInternal.RegioNotUsedX X,3
64
-
Not
used
RCPInternal.RegioNotUsedX X,3
65
-
Not
used
RCPInternal.RegioNotUsedX X,3
66
-
Not
used
RCPInternal.RegioNotUsedX X,3
67
-
Not
used
RCPSettings.RegioOccSetPHeat
R,3
68
22 °C
Basic heating setpoint
RCPSettings.RegioOccSetPCool
R,3
69
24 °C
Basic cooling setpoint
RCPSettings.RegioStandbySetPDeadBand R,3
70
3 °C
Deadband in Standby mode
RCPSettings.RegioUnOccSetPHeat
R,3
71
15 °C
Heating setpoint in Unoccupied mode
RCPSettings.RegioUnOccSetPCool
R,3
72
30 °C
Cooling setpoint in Unoccupied mode
RCPSettings.RegioFrostSetP
R,3
73
8 °C
Frost protection setpoint
Содержание Regio Maxi
Страница 1: ...Regio Maxi Manual ...
Страница 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Страница 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Страница 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Страница 47: ...Regio Manual Maxi Chapter 7 Commissioning 47 P Pa ar rt t I II II I C Co on nf fi ig gu ur ra at ti io on n ...
Страница 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Страница 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...