Regio Manual Maxi
Chapter 6
Installation
39
81
DI1
Digital input 1, 24 V DC.
Occupancy detector (FS), potential-free, NO. Open contact
corresponds to absence.
See also the section Occupancy detector in the chapter
Operating modes.
Wiring:
Potential-free contact is connected between terminals 81 and 80,
+C.
Alternatives:
- Window contact, potential-free, NO. Open contact corresponds
to closed window.
- Condensation detector, potential-free, NO. Open contact
corresponds to no condensation.
- Change-over sensor, potential-free, NO. Open contact
corresponds to heating demand.
See Regio tool
©
for
configuration of
NO/NC. The
factory setting is
normally open
(NO) contacts, but
the contacts can be
configured to NC.
82
DI2
Digital input 2, 24 V DC.
Window contact, potential-free, NO. Open contact corresponds
to closed window. (FS)
Wiring:
Potential-free contact is connected between terminals 82 and 80,
+C.
Alternatives:
- Condensation detector, potential-free, NO. Open contact
corresponds to no condensation.
- Occupancy detector, potential-free, NO. Open contact
corresponds to absence.
- Change-over sensor, potential-free, NO. Open contact
corresponds to heating demand.
See Regio tool
©
for
configuration of
NO/NC. The
factory setting is
normally open
(NO) contacts, but
the contacts can be
configured to NC.
83
+C
24 V DC out common for DI3
84
DI3
Digital input 3, 24 V DC.
Not configured for use (FS).
Wiring:
Potential-free contact is connected between terminals 84 and 83,
+C.
Alternatives:
- Window contact, potential-free, NO. Open contact corresponds
to closed window.
- Condensation detector, potential-free, NO. Open contact
corresponds to no condensation.
- Occupancy detector, potential-free, NO. Open contact
corresponds to absence.
- Change-over, potential-free, NO. Open contact corresponds to
heating demand. For switching between heating and cooling on
a two-pipe system.
See Regio tool
©
for
configuration of
NO/NC. The
factory setting is
normally open
(NO) contacts, but
the contacts can be
configured to NC.
90
Gnd
Reference ground for AO1-AO2 when high-ohm loads are used
and maximal accuracy is desired.
91
AO1
Analogue output 1.
Valve actuator, 0...10 V DC, max 5 mA. Control state: heating
(FS).
Wiring:
Valve actuator is connected between terminals 91 and 30, G0.
Alternative:
- Valve actuator, 0...10 V DC, max 5 mA. Control state:
cooling.
Содержание Regio Maxi
Страница 1: ...Regio Maxi Manual ...
Страница 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Страница 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Страница 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Страница 47: ...Regio Manual Maxi Chapter 7 Commissioning 47 P Pa ar rt t I II II I C Co on nf fi ig gu ur ra at ti io on n ...
Страница 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Страница 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...