30
Part II
Installation
Wiring for RCP100F / RCP100FT / RCP100FL
Figure 10. Connection diagram for RCP100F, RCP100FT and RCP100FL
Terminal Designation Operation
1
L
Line
230 V AC-
connection
3 N Neutral
4
EMI ground, yellow-green conductor
5
EMI
ground
10
DO1
For fan control, low speed. 230 V AC output.
Fan is connected between terminals 10 and N (Neutral).
11
DO2
For fan control, medium speed. 230 V AC output.
Fan is connected between terminals 11 and N (Neutral).
12
DO3
For fan control, high speed. 230 V AC output.
Fan is connected between terminals 12 and N (Neutral).
13
COM
Connection of L (Line)
Common pole for
DO1-3
20
GDO
24 V AC out common for DO4-DO5.
Terminals 20, 23
and 26 are
connected
internally, max total
load 12 VA.