U32SE-5 FPI Direct Vent Gas Insert
9
INSTALLATION
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit must
be disconnected.
Gas Input Capacity:
Natural
Gas
24,500
Btu/h
Propane 20,500
Btu/h
Min. Input
Natural Gas
16,500 Btu/h
Propane 17,000
Btu/h
Fuels:
Approved for use with both natural gas,
and propane. Approved as is for use at 0' to 4,500'
(0-1370m).
Electrical:
120V A.C. system.
Circulation Fan:
Variable speed, 110 CFM.
Vent System:
3" co-linear aluminum fl ex.
The efficiency rating of the appliance is a
product thermal efficiency rating determined
under continuous operating conditions and was
determined independent of any installed system.
GAS PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than
1/2 psig. (3.45 kPa).
INSTALLATION INTO A
SOLID FUEL BURNING
FIREPLACE OR
FACTORY BUILT
FIREPLACE
The U32SE Gas Insert has been tested and
approved to be vented into any masonry fi replace or
approved solid fuel burning factory built fi replace that
will allow the insert to physically fi t into the fi rebox.
Refer to "Minimum Fireplace Dimensions" section
for minimum fi replace clearances.
If the factory built fi replace* height is too low for
your Insert, you may remove the smoke baffl e plate,
damper, refractory (fi rebricks), glass doors, screen
rails, screen mesh and log grates from the factory
built fi replace as long as these items are saved and
are reinstalled in the event that the Insert is removed.
Smoke shelves, shields and baffl es may be removed
if attached by mechanical fasteners. If any part is
removed it must not weaken the structural integrity
of the factory built fi replace.
NOTE: Any alterations made to the listed solid fuel
burning factory built fi replace may void the listing
of the fi replace.
*Check with your local inspector before commencing
with this installation.
Installer must mechanically attach the supplied label
to the inside of the fi rebox of the fi replace into which
the gas fi replace insert is installed.
"
WARNING
: This fi replace has been converted
for use with a gas fi replace insert only and
cannot be used for burning wood or solid fuels
unless all original parts have been replaced,
and the fi replace re-approved by the authority
having jurisdiction."