L234-10 Direct Vent Gas Insert
|
15
|
15
installation
GAS INSERT AERATION ADJUSTMENT
The burner aeration is factory set but may need adjusting due to either the
local gas supply or altitude. Open the air shutter for a blue flame or close for
a more yellow flame. To access burner aeration–see Steps below.
CAUTION: Carbon will be produced if the air shutter is closed
too much.
Minimum Air Shutter Openings
Vent Run
Burner Aeration
Setting
3"
x 3"
8' to 20'
NG: 3/16"
LP: 3/16"
20' to 35'
NG: 3/16"
LP: 3/16"
3" x 2"
8' to 20'
NG: 3/16"
LP: 3/16"
20' to 35'
NG: 1/8"
LP: 1/8"
Note: Any damage due to carboning resulting from improperly setting
the aeration controls is NOT covered under warranty.
Note: Aeration Adjustment should only be performed by an authorized
Regency Installer at the time of installation or service.
1. Remove the outer faceplate.
2. Remove the safety screen.
3. Remove the glass door.
a) Pull the spring hook on the left that holds the door in place. Place the
hook into the opening towards the outside of the bracket. Repeat on
right side
.
b) Swing the door out 45 degrees and lift up and out.
4. Remove the logs.
5. Remove brick panels, if installed.
6. Remove the burner by undoing the 3 screws.
7. Make necessary aeration adjustment - reverse Steps 6-1.
Burner Removed
Spring Hook
Outside opening
Содержание L234-LP10
Страница 37: ...Liberty L234 10 Direct Vent Gas Insert 37 37 warranty MAIN ASSEMBLY a ...
Страница 38: ...38 Liberty L234 10 Direct Vent Gas Insert 38 parts list 537 924 Low Profile Faceplate ...
Страница 39: ...Liberty L234 10 Direct Vent Gas Insert 39 39 notes ...
Страница 44: ...44 Liberty L234 10 Direct Vent Gas Insert 44 warranty ...
Страница 45: ...Liberty L234 10 Direct Vent Gas Insert 45 45 notes ...
Страница 46: ...46 Liberty L234 10 Direct Vent Gas Insert 46 notes ...
Страница 47: ......