Regency Horizon™ HZ42STE-10 Gas Fireplace
|
14
installation
MANTEL CLEARANCES
Note: Ensure the paint that is used on the mantel
and the facing is "High Quality" or the paint
may discolour.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
Due to the extreme heat this fireplace emits, the
mantel clearances are critical.
Combustible mantel
clearances from top of front facing are shown in the
diagram on the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
279
356
356
279
Finished Wall
Finished Wall
Horizontal venting clearance
requirements are shown.
If Vertically venting add 2” due
to the adapter and venting
pushing the unit away from the wall
Clearance to 1-1/2” mantel leg
mantel increases to 9”
Clearance to 4” mantel leg
increases to 13”
Clearance to a 7” mantel leg
increases to 16 inches
Important
Determine the wall thickness prior
to framing this unit. The finished
wall depending on thickness
would decrease the required
clearance of 7 or 9 inches depend-
ing if this is horizontally vented/
Vertically vented so thought must
be put into the framing details.
If the finished wall is 1/2 inch the
framing should be 1/2 inch deeper
to accommodate the finished wall
2
0
12
6
4
8
10
Top of
Fireplace
Opening
0
14
To Unit
Base
22”
1 ”
7
25- /4”
1
10
20
26
Combustible Material
2
0
12
6
4
8
10
Top of
Fireplace
Opening
Standoff
Metal Stud
(On Edge)
0
14
Non-combustible
Facing
1" (25mm)
10
20
26
2
0
12
6
4
8
10
Top of
Fireplace
Opening
12" (305mm)
0
14
To Unit
Base
1" (25mm)
21-1/2”
1 ”
7
25- /4”
1
10
20
26
12" (305mm)
21-1/2”