HZ42 Regency Horizon
TM
Gas Fireplace
32
INST
ALLA
TION
AERATION
ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue fl ame or
close for a more yellow fl ame.
Minimum Air Shutter Opening:
NG Fully Closed
LP 3/8"
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1)
Make sure the valve is in the "OFF"
position.
2)
Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a
1/8"
wide
fl at screwdriver.
3)
Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON"
position.
5)
The pressure check should be carried out
with the unit burning and the setting should
be within the limits specifi ed on the safety
label.
6)
When
fi nished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not
over tighten.
HIGH ELEVATION
This unit is approved for altitude 0 to 4500 ft.
(CAN1 2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional
local codes it is always best to consult with
your local authorities and the CAN/CGA B149
installation code.
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI
Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and fl ex
connectors are usually considered to meet this
requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks
with a soap and water solution or gas leak
detector. Do not use open fl ame for leak
testing.
Periodically check the pilot fl ames. Correct
fl ame pattern has three strong blue fl ames:
1 fl owing around the thermopile, 1 around
the thermocouple and 1 fl owing across the
burner.
Note: If
you
have an incorrect fl ame pattern,
contact your Regency
®
dealer for
further instructions.
Incorrect fl ame pattern will have small,
probably yellow fl ames, not coming into
proper contact with the burner or thermopile
or thermocouple.
PILOT ADJUSTMENT
HZ42-NG SYSTEM DATA
Min. Supply Pressure
5" WC (1.25 kpa)
Low Setting Man.
Pressure
1.6" WC (0.40kpa)
Max. Manifold
Pressure
3.5" WC (0.87 kpa)
Orifi ce Size
#40 DMS
Minimum Input
17,500 Btu/h
(5.13 kW)
Maximum Input
26,000 Btu/h
(7.62 kW)
INSTALLATION
S.I.T. VALVE DESCRIPTION
1)
Gas on/off knob
2)
Manual high/low adjustment
3)
Pilot
Adjustment
4)
Thermocouple Connection -
option
5)
Outlet Pressure Tap
6)
Inlet
Pressure
Tap
7)
Pilot
Outlet
8)
Main Gas Outlet
9)
Alternative TC Connection Point
HZ42-LP SYSTEM DATA
Min. Supply Pressure
12" WC (2.98 kpa)
Low Setting Man.
Pressure
6.4" WC (1.59kpa)
Max. Manifold
Pressure
10" WC (2.49 kpa)
Orifi ce Size
#53 DMS
Minimum Input
19,500 Btu/h
(5.71 kW)
Maximum Input
24,500 Btu/h
(7.18 kW)
Содержание Horizon HZ42
Страница 53: ...HZ42 Regency HorizonTM Gas Fireplace 52 NOTES ...
Страница 54: ...HZ42 Regency HorizonTM Gas Fireplace 53 NOTES ...
Страница 55: ...HZ42 Regency HorizonTM Gas Fireplace 54 NOTES ...