Hampton® H200 Cast Freestanding Woodstove
|
9
9
|
installation
Residential Installation “C” Vent (Single Wall)
Unit (with Heat Shield)
From Unit From
From Flue Center-Line
Corner
A
B
C
D E
F
H200
17" (432 mm) 15" (381 mm) 13" (330 mm) 29" (737 mm) 17-1/8"(435 mm) 19-7/8" (505mm)
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling
level.
Unit (with Heat Shield)
From Unit From
From Flue Center-Line
Corner
A
B
C D
E
F
H200
15" (381 mm) 10" (254 mm) 9" (229 mm) 27" (686 mm) 12-1/8" (308 mm)
15-7/8" (403mm)
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations (refer to Mobile Home Instructions).
Unit (with Heat Shield)
From Unit From
From Flue Center-Line
Corner
A
B
C
D
E
F
H200
15" (381mm) 10" (254 mm) 9" (229mm) 27" (686mm) 12-1/8" (308mm)
15-7/8" (403mm)
MINIMUM ALCOVE CLEARANCE AND CLEARANCE TO COMBUSTIBLE MATERIALS
Please read the section below carefully. Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the
rear heat shield to a back wall.
Clearances may only be reduced by means approved by the regulatory authority.
NOTE: This clearance is also required for air space between the appliance and wall/ceiling.
NOTE:
Be aware that local Codes and Regulations may override some clearances listed in this manual.
Check with your local inspector.