20
Regency GF1500L Gas Fireplace
installation
FLUEING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency
®
Direct Vent System
These flueing systems, in combination with GF1500L, have been tested and listed as a Direct Vent system by AGA. The location of the termination
cap must conform to the requirements in the Flue Terminal Locations diagram from the "Exterior Flue Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the GF1500L using a flexible vent.
FPI Kit #
Length
Contains:
#946-615
1.2 m
1)
203mm flexible liner (Kit length)
2)
127mm flexible liner (Kit length)
3)
spring spacers
4)
thimble
5)
AstroCap
termination cap
6)
screws
7)
tube of Mill Pac
8)
plated screws
9)
S.S. screws #8 x 38mm drill point
#946-618
1.8 m
#946-616
3 m
Notes:
1) Liner sections should be continuous without any joints
or seams.
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal flue must be supported every 0.9m.
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.
203mm dia.
Flue pipe
127mm dia. flue pipe
spring spacer
Termination Cap
AstroCap XL
TM
(Part #946-623/P)
Flue Guard - if required *
(Part #946-506/P)
Wall Thimble
(Mandatory in all
Horizontal Terminations)