30
Regency GF1500L Gas Fireplace
installation
919-586
06/25/15
Installer Notice:
These instructions must be left
with the appliance.
After carrying out all adjustments, block the setting screws with paint,
taking care not to obstruct the breather orifice of the pressure.
Put back the modulator plastic cap.
WARNING: To ensure the correct operation of the modulator it is
necessary that the plastic cap (A) is returned to its original location.
20. Turn on gas supply and plug in power cord.
21. At the end of all setting and adjustment operations, check electrical
installation and gas leaks.
22. Check operation of flame control.
23. Check for proper flame appearance and glow on logs.
C
B
A
10.
Reinstall new burner orifice LP/ULPG and tighten.
11. Replace the yellow "NG" label with the red "LP or ULPG" label.
12. Carefully pull out the control box.
NOTE: The control box is held in place with velcro.
13. Remove the heat shield from the control box by removing the 2
screws.
14. Remove the control box cover by undoing the 3 screws.
Manoeuvre through antenna.
NOTE: The maximum outlet pressure must be set to 2.49 kPa.
Minimum pressure: Remove one of the cables connected to the electric
modulator. While holding the nut (B) with a wrench, screw in the screw
(C) to increase the pressure and screw it out to decrease it. Use a suitable
screwdriver.
Cable
Electric
Modulator
Control Box
Cover
Antenna
Jumper Location
15. Remove the jumper using pliers.
Jumper
NOTE: The minimum outlet pressure must be set to 1.6 kPa.
16. Reverse steps to reinstall.
17. Adjust Air shutter to correct opening (Refer to Page 26 for correct
opening).
18. Turn on gas supply and plug in power cord.
19. Adjusting the Outlet Pressure
All the adjustments must be carried out in the following order:
Remove the modulator plastic cap (A) using needle nose pliers.
Maximum pressure: Turn the unit ON to its highest input rating.
Screw in the nut (B) to increase the outlet pressure and screw it out
to decrease it. Use a 10 mm spanner.
NOTE: Do not screw in nut too far. If no pressure increases after
two full turns, Place manometer on inlet test point on gas
valve and check flowing inlet pressure.
2
GF1500L