22
Regency GF900C Gas Fireplace
INSTALLATION
VERTICAL TERMINATIONS
RIGID PIPE 4" X 6-5/8
" (
102MM X 175MM)
The minimum components required for a basic vertical
termination are:
1 Vertical Termination Cap
1 Rigid Pipe Adaptor (510-994)
1 Ceiling Firestop
1 Flashing
1 Storm Collar
1 Length of pipe to suit wall thickness
(see chart)
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent, Selkirk Direct-Temp, Ameri Vent Direct Venting, ICC Excel Direct
and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is
deemed acceptable and does not affect the Intertek WHI listing of components.
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCap
TM
and FPI Riser is acceptable with all systems.
The FPI AstroCap
TM
and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent
®
Direct Vent, Ameri-
can Metal Products Ameri Vent Direct Vent, Security Secure Vent
®
, ICC Excel, Selkirk Direct-Temp. AstroCap
TM
is a proprietary trademark of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
Roof Pitch Minimum Vent Height
Feet Meters
flat to 7/12
2
0.61
over 7/12 to 8/12
2
0.61
over 8/12 to 9/12
2
0.61
over 9/12 to 10/12
2.5
0.76
over 10/12 to 11/12
3.25
0.99
over 11/12 to 12/12
4
1.22
over 12/12 to 14/12
5
1.52
over 14/12 to 16/12
6
1.83
over 16/12 to 18/12
7
2.13
over 18/12 to 20/12
7.5
2.29
over 20/12 to 21/12
8
2.44
Galvanized pipe is desirable above the roofline due to its higher
corrosion resistance. Continue to add pipe sections through the
flashing until the height of the vent cap meets the minimum height
requirements specified in local codes. Note that for steep roof
pitches, the vertical height must be increased. A poor draft, or
down drafting can result from high wind conditions near big trees
or adjoining roof lines, in these cases, increasing the vent height
may solve the problem.
Pipe Length
Storm Collar
Flashing
Ceiling Firestop
Rigid Pipe Adapter
Vertical Terminal