Regency GF900C Gas Fireplace
23
INSTALLATION
VENTING ARRANGEMENT FOR VERTICAL TERMINATIONS
Vertical Venting with One(1) 90
o
Elbows (1 - 90
o =
2 - 45
o
)
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
45
o
elbow, with
Rigid Pipe Venting Systems
.
• Vent must be supported at offsets.
• Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the
"Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever
passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994)
when using rigid pipe vent systems.
•
Refer to the "Vent Restrictor Position" section for details
on how to change the vent restrictor from the factory
setting of Set 0 to Set 1 or Set 2 if required.
6.7m
4m
Restrictor Set #3
15mm open
"THIS UNIT MUST ALWAYS
TERMINATE / VENT
DIRECTLY TO THE OUTDOORS."
N
OTE
: Restrictor settings
LP: Set #2 - 18mm
ULPG: Set#1 - 26mm