• Vent must be supported at offsets.
• Firestops are required at each floor level and
whenever passing through a wall.
• Maintain clearances to combustibles as listed in
the "Clearances" section.
• Refer to the "Vent Restrictor Position" section
for details on how to change the vent restrictor
from the factory setting of Set 1 to Set 2 or Set 3
if required.
Note: Must use optional flue adaptor when using
Rigid Pipe (Part # 770-994).
Maximum:
40
ft.
(12.2m)
Minimum 86
(2.6m)
Min.
44
(1
118mm)
Max. 10 (3m)(centerline to centerline)
Minimum length of pipe
between elbows 12 (305mm)
Maximum:
27
ft.
(8.2m)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
Vertical
Height
(Feet)
32
34
36
38
6
8
Horizontal (Feet)
2
0
4
10
12
16
18
14
20
Vent Restrictor on Set 2
Vent Restrictor on Set 3
Vent Restrictor on Set 1
(factory setting)
VENTING ARRANGEMENTS
ALLOWABLE VERTICAL TERMINATIONS FOR GEM54-NG
The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90
o
elbows, with
Rigid Pipe Venting
Systems
for Natural Gas. Two 45
o
elbows equal to one 90
o
elbow. Maximum of four 45
o
elbows allowed.
Please note min. 0.3m between 90
o
elbows
is required.
"THIS UNIT MUST ALWAYS
TERMINATE / VENT
DIRECTLY TO THE OUTDOORS."