8
Regency Gemfire™ Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
F
B
E
D
A
Installed Close
to Floor
G
48
"(
12
19
m
m
)
4"
(102mm)
5-11/16
(144mm)
28
(71
1mm)
20"
(508mm)
22-1/2
52-5/8
60-1/2" (1537mm)
Non-combustible
Material
Non-combustible Material
Non-combustible
Material
Non-combustible
Material
Metal Stud (header)
Wood Stud
Wood Stud
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
20" (508mm)
Top of Fireplace Opening
B: Sidewall
4" (102mm)
Side of Fireplace Opening
C: Ceiling
(room and/or alcove)
40-7/8" (1038mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
13" (330mm)
30" Above Fireplace Opening
E: Alcove Width
83" (2108mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
Note
0"
No hearth required
F
B
C
Installed Close
to Ceiling
NON-COMBUSTIBLE REQUIREMENTS
Flue Clearances
Horizontal - Top
3" (76mm)
Horiztonal - Side
2" (51mm)
Horiztonal - Bottom
2" (51mm)
Vertical
2" (51mm)