8
|
Regency CI1150 Wood Cast Insert
installation
Clearance Diagram for installations
Note: Side and Top facing is a maximum of 1.5" thick.
**Measured from side/top of door.
Masonry And Factory Built Fireplace Clearances
The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below.
*Floor Protection
Thermal insulation/protection with a R value of 1.4 at a distance of 18" from door opening is required
for Canada and 16" for USA.
If unit raised minimum 4.5" from hearth, no thermal protection is required.
Please check to ensure that your floor protection and hearth will meet the standards for clearance
to combustibles. Your hearth extension must be made from a non-combustible material. Extending
16" for US and 18" for Canada—measured from the fuel loading door.
Unit
CI1150
Adjacent
Side Wall
(to side)
A**
Mantel***
(to top)
B**
Top
Facing
(to top)
C**
Side
Facing
(to side)
D**
Minimum
Hearth
Extension*
E
Minimum
Hearth Side
Extension*
F
From Top of
Door
G
15" (381 mm) 15" (381 mm)
for 3-1/2" (89
mm) mantel
14" (355 mm)
7 3/8"(187 mm)
16" (406 mm) USA
8" (203 mm)
20-1/2" (521 mm)
18"(457 mm) Canada
20" (508 mm)
for 12"(305 mm)
mantel
Clearances are critical.
***
Mantel can be installed anywhere in shaded area
or higher using the above scale.
Side View
12" (305mm) Mantel
3-1/2" (89mm) Mantel
20”
(508mm)
15”
(381mm)
2
0
12
6
4
8
10
2
0
12
6
16
4
14
8
18
20
10
Top of
Door