8    | 

Regency I2404

8    |

installation

Clearance diagram for Installations

Side and Top facing is a maximum of 1.5" thick. 

Floor protection must be non-combustible, insula-

tive material with an R value of 1.1 or greater.

*  Hearth thickness of 0.5" with k value = 0.84", 

r value = 0.6 or greater. 

**   A non-combustible mantel may be installed 

at a lower height if the framing is made of 

metal studs covered with a non-combustible 

board.

**  Max. mantle depth is 10" (254mm).

Thermal floor protection is not required if the unit is 

raised 3.5" minimum (measured from the bottom of 

the stove). However, standard ember floor protec

-

tion is required. It will need to be a non-combustible 

material that covers 16"  (406 mm) in the US and 

18" (450 mm) in Canada to the front of the unit and 

8" (200 mm) to the sides.

If  the  unit  is  not  raised,  thermal  floor  protection 

required is 18" (450 mm) in the US and Canada.

All floor protection must be non-combustible (i.e., 

metals, brick, stone, mineral fiber boards, etc.) Any 

organic materials

 

(i.e. plastics, wood paper prod-

ucts, etc.)

 

are combustible and must not be used. 

The floor protection specified includes some form 

of thermal designation such as R-value (thermal 

resistance) or k-factor (thermal conductivity).

MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES 

The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below. 

H

HOW TO DETERMINE IF ALTERNATE 
FLOOR PROTECTION MATERIALS ARE ACCEPTABLE

The  specified  floor  protector  should  be  3/8" 

(18mm)  thick  material  with  a  K  -  factor  of 

0.84.

The proposed alternative is 4" (100mm) brick 

with a C-factor of 1.25 over 1/8" (3mm) mineral 

board with a K-factor of 0.29.

Step (a): 

 

Use formula above to convert specification 

to R-value.

 

R = 1/k x T = 1/0.84 x .75 = 0.893.

Step (b): 

 

Calculate R of proposed system.

 

4" brick of C = 1.25, therefore

 

Rbrick = 1/C = 1/1.25 = 0.80

 

1/8" mineral board of k = 0.29, therefore 

Rmin.bd. = 1/0.29 x 0.125 = 0.431

 

Total R = Rmineral board =

 

0.8 + 0.431 = 1.231.

Step (c): 

  Compare proposed system R of 1.231 to 

specified R of 0.893. Since proposed system 

R is greater than required, the system is 

acceptable.

DEFINITIONS

 

Thermal Conductance:

 

 

=         Btu  

=          W

                    (hr)(ft

2  

)(

o

F)                 (m

2)

)(K)

   

Thermal Conductivity:

 

k  =  (Btu)(inch)    =     W      =     Btu

 

 (hr)(ft

3

)(

o

F)            (m)(K)       (hr)(ft)(

o

F)

 

Thermal Resistance:

 

R     =      (ft

2

)(hr)(

o

F)      =        (m

2

)(K)

 

  

      Btu           

           W

Minimum Hearth Extension for the front 

(E) and sides (G) are measured from the 

fuel door opening.

 Unit

Adjacent 

Side Wall

(to Side)

A

Mantle **

(to Top)

B

Top

Facing

(to Top of Unit)

C

Side 

Facing

(to Side of Unit)

D

Minimum

Hearth 

Extension*

E

Minimum

Hearth 

Thickness

F

Minimum

Hearth Side

Extension*

G

From Top of 

Unit

H

Medium 

Flush Insert 

(I2404)

11"/280mm

20" (508mm)

12"(305mm)

8"(200mm)

18"(455mm) 

1/2"(13mm)

8" (203mm)

20"(508mm)

Содержание I2404M

Страница 1: ...a V4G 1H4 919 032c MODELS I2404M WOOD Fireplace Insert 01 30 18 Owners Installation Manual Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Pl...

Страница 2: ...of the chimney is within the building envelope and fully lined It is against federal regulation to operate this wood heater in a manner inconsistent with operating instructions in this manual or if an...

Страница 3: ...allation 10 Installation of the Faceplate and Trim 11 Installation of the Fan blower 12 Floor Protection 13 Firebrick Assembly 13 Draft Control 13 Flue Baffle Secondary Air Tube Installation 13 Door H...

Страница 4: ...THE MANUFACTURER SUPPLIED SCREEN MUST BE USED REPLACE GLASS ONLY WITH CERAMIC GLASS 5MM INSPECT AND CLEAN CHIMNEY FREQUENTLY UNDER CERTAIN CONDITIONS OF USE CREOSOTE BUILDUP MAY OCCUR RAP IDLY DO NOT...

Страница 5: ...Regency I2404 5 5 dimensions 5 5 9 UNIT DIMENSIONS I2404M...

Страница 6: ...Install and use only in accordance with manufac turer sinstallationandoperatinginstructions 2 Check your local building codes Building Inspection Department You may require a permit before installing...

Страница 7: ...nto position The insert can be made a little lighter by removing the cast iron door by opening it and lifting it off its hinges Be sure to protect your hearth extension with a heavy blanket or carpet...

Страница 8: ...RANCES The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below H HOW TO DETERMINE IF ALTERNATE FLOOR PROTECTION MATERIALS ARE...

Страница 9: ...flue or liner is in use the insert is able to breathe better by allowing a greaterdrafttobecreated Thegreaterdraftcan decrease problems such as difficult start ups smoking out the door and dirty glas...

Страница 10: ...h bolts and slide defector upward and out Install new defector and hand tighten bolts Ensure positive location of the defector prior to hand tightening WARNING Operation of the unit with out proper in...

Страница 11: ...on and attached to the connection system 5 Onceconnectionismade theinsulationstrips should be installed between the insert face plates and the fireplace face The faceplate top may now be installed wit...

Страница 12: ...temperature or at least 30 minutes after starting fire Your fan should only be installed once the unit is in place in order to prevent any damage to the fan To attach follow the instructions provided...

Страница 13: ...he air tube into the holes in the side channels The notch goes on the right hand side with the air holes facing toward the door Slide the tube into the left hand side as far as possible and then bring...

Страница 14: ...ondition 3 Do not burn large quantities of paper in your insert 4 Ifyouhavesmokedetectors preventsmoke spillage as this may set off a false alarm 5 Donotoverfireyourinsert Iftheinsertbegin to glow you...

Страница 15: ...luelining Whenignited this creosote can make an extremely hot fire FAN OPERATION The fan is to be operated only with the draft control rod pulled out at least 1 2 from the fully closed position The fa...

Страница 16: ...all deposits GLASS REPLACEMENT Your Regency Insert is supplied with 5 mm Neoceram ceramic glass Part 846 304 that will withstand the highest heat that your unit will produce In the event that you brea...

Страница 17: ...3 Regency Logo Nickel 948 216 Regency Logo Gold 48 820 482 Stainless smoke deflector 918 993 Manual Not available as a replacement part Part Description 1 850 152 Door Assy Large Gold 850 151 Door Ass...

Страница 18: ...lar 287 Trim Left Regular 288 Faceplate Side Regular 289 Faceplate Top Regular 140 913 Faceplate Trim Set Oversize 180 572 Black Trim Oversize set of 3 295 Trim Right Oversize 296 Trim Top Oversize 29...

Страница 19: ...2404 19 19 parts list BRICK PANELS I2404M Part Description 180 960 Firebrick Complete Set 70 902 111 Brick Regular Full Size 1 1 4 x 4 1 2 x 9 75 Brick Partial 1 1 4 x 4 1 2 x 2 76 Brick Partial 1 1 4...

Страница 20: ...rorated 3 Venting Chimney 1 Screens 1 Conditions Warranty protects against defect in manufacture or FPI factory assembled components only unless herein specified otherwise Any part s found to be defec...

Страница 21: ...ype operator error abuse misuse use of improper fuels such as unseasoned cordwood mill ends construction lumber or debris off cuts treated or painted lumber metal or foil plastics garbage solvents car...

Страница 22: ...additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the authorized selling dealer to obtain warranty service In the event the authorized...

Страница 23: ...r us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Produ...

Страница 24: ......

Страница 25: ...25...

Страница 26: ...26 Regency I2404 26 notes...

Страница 27: ...Regency I2404 27 27 notes...

Страница 28: ...______________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No _____________...

Отзывы: