6    | 

Regency I2404

6    |

installation

CHIMNEY  
SPECIFICATIONS

Before installing, check and clean your chimney 

system thoroughly. If in doubt about its condi-

tion, seek professional advice. Your Regency 

Insert is designed for installation into a masonry 

fireplace that is constructed in accordance with 

the requirements of "The Standard for Chimneys, 

Fireplaces, Vents, and Solid Fuel Burning Ap

-

pliance",  N.F.P.A.  211,  the  National  Building 

Code of Canada, or the applicable local code 

requirements.  

The appliance, when installed, must be electri-

cally grounded in accordance with local codes or, 

in the absence of local codes, with the National 

Electrical Code, ANSI/NFPA 70, or the Canadian 

Electrical code, CSA C22.1.

Regency Inserts are designed to use either a 

5.5" (140mm) or  6" (152mm) flue.

Requirements for Installing 
Solid-fuel Inserts in Factory-built 
Fireplaces.

1)

  The insert must be tested and meet the 

requirements of UL 1482 (U.S.) and or ULC 

S628 (Canada) when tested in a masonry 

fireplace built per ULC S628.

2)

  The factory-built fireplace must be listed per 

UL 127 or ULC S610.

3)

  Clearances obtained from the masonry fire

-

place tests are also relevant for installation 

in factory-built fireplaces.

4)

  Installation must include a full height listed 

chimney liner type HT requirements (2100 

degree  F.)  per  UL  1777  (U.S.)  or  ULC 

S635 (Canada). The liner must be securely 

attached  to  the  insert  flue  collar  and  the 

chimney top.

5)

  Means must be provided to prevent room 

air passage to the chimney cavity of the 

fireplace.  This  may  be  accomplished  by 

sealing the damper area around the chimney 

liner, or sealing the fireplace front.

6)

  Alteration of the fireplace in any manner is 

not permitted with the following exceptions; 

 

a. 

  external trim pieces which do not affect 

the operation of the fireplace may be 

removed providing they can be stored 

on or within the fireplace for re-assembly 

if the insert is removed.

 

b.

   the chimney damper may be removed 

to install the chimney liner.

 

Regency Inserts are constructed with the high-

est quality materials and assembled under strict 

quality control procedures that insure years of 

trouble free and reliable performance.

It is important that you read this manual thor-

oughly and fully understand the safe instal-

lation and operating procedures.  The more 

you understand the way your Regency Insert 

operates, the more enjoyment you will experi-

ence from knowing that your unit is operating 

at peak performance.

BEFORE INSTALLING 
YOUR INSERT

1)

  Please read this entire manual before you 

install and use your new wood insert. Failure 

to follow instructions may result in property 

damage, bodily injury or even death. Install 

and use only in accordance with manufac-

turer’s installation and operating instructions.

2)

  Check your local building codes - Building 

Inspection Department.  You may require 

a  permit  before  installing  your  insert.  Be 

aware that local codes and regulations may 

override some items in the manual.

  WARNING:  Careless installation is the 

major cause of safety hazard.  Check all 

local building and safety codes before 

installation of unit.

3)

  Notify your home insurance company that 

you plan to install a fireplace insert or hearth 

heater.

4) 

Your fireplace insert is heavy and requires 

two or more people to move it safely.  The 

insert can be badly damaged by mishandling.

5)

  If  your  existing  fireplace  damper  control 

will become inaccessible once you have 

installed your Regency Insert, you should 

either remove or secure it in the open posi-

tion.

6)

  Inspect  your  fireplace  and  chimney  prior 

to installing your insert to determine that it 

is free from cracks, loose mortar or other 

signs of damage.  If repairs are required, 

they should be completed before installing 

your insert.  Do not remove bricks or mortar 

from your masonry fireplace.

7)

 

Do not connect the insert to a chimney 

system servicing another appliance or 

an air distribution duct.

7)

  Circulating air chambers (i.e. in a steel 

fireplace liner or metal heat circulator) shall 

not be blocked.

8)

  Means must be provided for removal of the 

insert to clean the chimney flue.

9)

  Inserts that project in front of the fireplace 

must be supplied with appropriate supporting 

means.

10)

 Installer must mechanically attach the sup-

plied label to the inside of the firebox of the 

fireplace into which the insert is installed.

In order for a solid-fuel insert to be certified for use 

in factory-built fireplaces, the above information 

must be clearly stated in the installation manual 

and appropriate markings. Final approval is 

contingent on the authority having jurisdiction.

WOOD INSERT  
SPECIFICATIONS

Your  fireplace  opening  requires  the  following 

minimum sizes:

  Height:   

21.5"

 Width:

    25"

 Depth:

    17"

Two faceplates are available to seal the fireplace 

opening:  

 

   Standard 

    Oversize

40" W x 30" H 

48" W x 33" H

Emissions from burning  wood or gas could 

contain chemicals known to the State of Cali-

fornia to  cause cancer, birth defects or other 

reproductive harm.

"

WARNING

: This fireplace has been converted 

for use with a wood insert only and cannot be 

used for burning wood or solid fuels unless 

all original parts have been replaced, and the 

fireplace re-approved by the authority having 

jurisdiction."

Important: 

The blower to this appliance must be turned 

off  anytime  the  fuel  door  is  opened.  Prior  to 

turning the blower back on, ensure there are no 

embers near the blower which may have fallen 

onto the hearth when the fuel door was opened. 

Once the fuel door is closed, the blower may 

be turned back on.

Содержание I2404M

Страница 1: ...a V4G 1H4 919 032c MODELS I2404M WOOD Fireplace Insert 01 30 18 Owners Installation Manual Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Pl...

Страница 2: ...of the chimney is within the building envelope and fully lined It is against federal regulation to operate this wood heater in a manner inconsistent with operating instructions in this manual or if an...

Страница 3: ...allation 10 Installation of the Faceplate and Trim 11 Installation of the Fan blower 12 Floor Protection 13 Firebrick Assembly 13 Draft Control 13 Flue Baffle Secondary Air Tube Installation 13 Door H...

Страница 4: ...THE MANUFACTURER SUPPLIED SCREEN MUST BE USED REPLACE GLASS ONLY WITH CERAMIC GLASS 5MM INSPECT AND CLEAN CHIMNEY FREQUENTLY UNDER CERTAIN CONDITIONS OF USE CREOSOTE BUILDUP MAY OCCUR RAP IDLY DO NOT...

Страница 5: ...Regency I2404 5 5 dimensions 5 5 9 UNIT DIMENSIONS I2404M...

Страница 6: ...Install and use only in accordance with manufac turer sinstallationandoperatinginstructions 2 Check your local building codes Building Inspection Department You may require a permit before installing...

Страница 7: ...nto position The insert can be made a little lighter by removing the cast iron door by opening it and lifting it off its hinges Be sure to protect your hearth extension with a heavy blanket or carpet...

Страница 8: ...RANCES The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below H HOW TO DETERMINE IF ALTERNATE FLOOR PROTECTION MATERIALS ARE...

Страница 9: ...flue or liner is in use the insert is able to breathe better by allowing a greaterdrafttobecreated Thegreaterdraftcan decrease problems such as difficult start ups smoking out the door and dirty glas...

Страница 10: ...h bolts and slide defector upward and out Install new defector and hand tighten bolts Ensure positive location of the defector prior to hand tightening WARNING Operation of the unit with out proper in...

Страница 11: ...on and attached to the connection system 5 Onceconnectionismade theinsulationstrips should be installed between the insert face plates and the fireplace face The faceplate top may now be installed wit...

Страница 12: ...temperature or at least 30 minutes after starting fire Your fan should only be installed once the unit is in place in order to prevent any damage to the fan To attach follow the instructions provided...

Страница 13: ...he air tube into the holes in the side channels The notch goes on the right hand side with the air holes facing toward the door Slide the tube into the left hand side as far as possible and then bring...

Страница 14: ...ondition 3 Do not burn large quantities of paper in your insert 4 Ifyouhavesmokedetectors preventsmoke spillage as this may set off a false alarm 5 Donotoverfireyourinsert Iftheinsertbegin to glow you...

Страница 15: ...luelining Whenignited this creosote can make an extremely hot fire FAN OPERATION The fan is to be operated only with the draft control rod pulled out at least 1 2 from the fully closed position The fa...

Страница 16: ...all deposits GLASS REPLACEMENT Your Regency Insert is supplied with 5 mm Neoceram ceramic glass Part 846 304 that will withstand the highest heat that your unit will produce In the event that you brea...

Страница 17: ...3 Regency Logo Nickel 948 216 Regency Logo Gold 48 820 482 Stainless smoke deflector 918 993 Manual Not available as a replacement part Part Description 1 850 152 Door Assy Large Gold 850 151 Door Ass...

Страница 18: ...lar 287 Trim Left Regular 288 Faceplate Side Regular 289 Faceplate Top Regular 140 913 Faceplate Trim Set Oversize 180 572 Black Trim Oversize set of 3 295 Trim Right Oversize 296 Trim Top Oversize 29...

Страница 19: ...2404 19 19 parts list BRICK PANELS I2404M Part Description 180 960 Firebrick Complete Set 70 902 111 Brick Regular Full Size 1 1 4 x 4 1 2 x 9 75 Brick Partial 1 1 4 x 4 1 2 x 2 76 Brick Partial 1 1 4...

Страница 20: ...rorated 3 Venting Chimney 1 Screens 1 Conditions Warranty protects against defect in manufacture or FPI factory assembled components only unless herein specified otherwise Any part s found to be defec...

Страница 21: ...ype operator error abuse misuse use of improper fuels such as unseasoned cordwood mill ends construction lumber or debris off cuts treated or painted lumber metal or foil plastics garbage solvents car...

Страница 22: ...additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the authorized selling dealer to obtain warranty service In the event the authorized...

Страница 23: ...r us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Produ...

Страница 24: ......

Страница 25: ...25...

Страница 26: ...26 Regency I2404 26 notes...

Страница 27: ...Regency I2404 27 27 notes...

Страница 28: ...______________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No _____________...

Отзывы: