Regency Horizon
®
HZ33CE-11 Gas Fireplace
| 35
installation
UNIT INSTALLATION WITH HORIZONTAL TERMINATION
**
** Note: Riser vent is only for use in above grade terminations.
Diagram 3
Diagram 1
5) Mark the wall for a 10" x 10" square hole. The
center of the square hole should line up with the
centerline of the horizontal pipe. Cut and frame
the 10 inch square hole in the exterior wall where
the vent will be terminated. If the wall being
penetrated is constructed of non-combustible
material, i.e. masonry block or concrete, a
7"(178mm) diameter (7-1/2"(191mm) dia. for
flex) hole is acceptable.
Note:
a) The horizontal run of vent must be level, or
have a 1/4 inch rise for every 1 foot of run
towards the termination. Never allow the
vent to run downward. This could cause
high temperatures and may present the
possibility of a fire.
b) The location of the horizontal vent
termination on an exterior wall must meet
all local and national building codes, and
must not be blocked or obstructed. See
"Exterior Vent Terminal Locations" Section.
c) Snorkel Terminations:
For installations requiring a vertical rise on
the exterior of the building, 14-inch and 36-
inch tall Snorkel Terminations and the Riser
Vent as shown in Dia. 2 & 2a are available.
Follow the same installation procedures as
used for standard Horizontal Termination.
NEVER install the snorkel upside down.
*As specified in CGA B149 Installation Code.
Local codes or regulations may require different
clearances.
6) The arrow on the vent cap should be
pointing up. Insure that the 1-1/2" clearances
to combustible materials are maintained (Dia.
3). Install the termination cap.
AstroCap
TM
or
Dura-Vent Horizontal Termination Cap may be
used.
The four wood screws provided should be
replaced with appropriate fasteners for stucco,
brick, concrete, or other types of sidings.
Diagram 2a
Install the vent system according to the manufac-
turer's instructions included with the components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in the
way when the venting system is attached. If this
is the case, you may want to adjust the location
of the unit. Rough in the gas preferably on the
right side of the unit and the electrical (junction
block is on the left side) on the left.
2) Direct Vent pipe and fittings are designed with
special twist-lock connections to connect the
venting system to the appliance flue outlet.
A twist-lock appliance adaptor is an available
option that must be used in conjunction with
the Simpson Dura-Vent Direct Vent system.
3) Put a bead of Mill-Pac inside the outer section
of the adapter and on the inner collar. Slip the
adapter over the existing inner and outer flue
collar and fasten to the outer collar only with the
3 supplied screws (drilling pilot holes will make
this easier). Level the fireplace and fasten it to
the framing using nails or screws through the
nailing strips.
4) Assemble the desired combination of pipe and
elbows to the appliance adaptor and twist-lock
for a solid connection.
Note:
a) Twist-lock procedure: Four indentations,
located on the female ends of pipes and
fittings, are designed to slide straight onto
the male ends of adjacent pipes and fittings,
by orienting the four pipe indentations so
they match and slide in to the four entry
slots on the male ends, Dia. 1. Push the pipe
sections completely together, then twist-lock
one section clockwise approximately one-
quarter turn, until the two sections are fully
locked. The female locking lugs will not be
visible from the outside, on the Black Pipe or
fittings. They may be located by examining
the inside of the female ends.
NOTE: For best results and optimum perfor-
mance with each approved venting system, it is
highly recommended to apply “Mill-Pac” sealant
(supplied) to every inner pipe connection. Failure
to do so may result in drafting or performance
issues not covered under warranty.
b) Horizontal runs of vent must be supported
every three feet. Wall straps are available
for this purpose.
Note: If installing termination on a siding
covered wall, a vinyl siding standoff or
furring strips must be used to ensure
that the termination is not recessed into
the siding.
7) Before connecting the horizontal run of vent pipe
to the vent termination, slide the Wall Thimble
(Part # 620-926) over the vent pipe.
Window
Well
Adequate
Drainage
Gravel
Snorkel
(305 mm)
Min. 12”
B e l o w G r a d e S n o r k e l I n s t a l l a t i o n
If the Snorkel Termination must be installed below
grade, i.e. basement application, proper drainage
must be provided to prevent water from entering the
Snorkel Termination. Refer to Dura-Vent Installation
instructions for details. Do not attempt to enclose
the Snorkel within the wall, or any other type of
enclosure. See Diagram 2b.
**Note: Riser vent is only for use in above
grade terminations.
Diagram 2
Diagram 2b