56 |
Grandview® G600EC Gas Fireplace
installation
Vertical Venting With Two (2) 90
o
Elbows
Vertical Venting With Three (3) 90
o
Elbows
V1
V
H
V
H1
H
V1
*
*
One 90
o
elbow = Two 45
o
elbows.
Option
V
H
V + V1
W i t h t h e s e
o p t i o n s ,
maximum total
pipe length is
30 feet (9.14 m)
with minimum
of 7 feet (2.13
m) total vertical
and maximum
8 feet (2.44 m)
total horizontal.
Please note
minimum 1
foot between
90
o
elbows is
required.
A)
0' Min.
2' (0.61 m) Max.
1' (0.3 m) Min.
B)
1' (0.3 m) Min.
4' (1.22 m) Max.
3' (0.91 m) Min.
C)
2' (0.61 m) Min.
5' (1.52 m) Max.
4' (1.22 m) Min.
D)
3' (0.91 m) Min. 6' (1.82 m) Max.
5' (1.52 m) Min.
E)
4' (1.22 m)Min. 7' (2.13 m) Max.
6' (1.82 m) Min.
F)
5' (1.52 m) Min. 8' (2.43 m) Max.
7' (2.13 m) Min.
Restrictor Set #1 - 2" (51 mm) open
Lengths do not include elbow indicated.
*Required when using rigid venting
One 90
o
elbow = Two 45
o
elbows.
Option
V
H + H1
V + V1
With these options,
m a x i m u m t o t a l
pipe length is 30
feet (9.14 m) with
minimum of 10 feet
(3.05 m) total vertical
and maximum 8
feet (2.44 m) total
horizontal.
Please note mini-
mum 1 foot be-
tween 90
o
elbows
is required.
A)
0' Min.
2' (0.61 m) Max.
2' (0.61 m) Min.
B)
1' (0.3 m) Min.
2' (0.61 m) Max.
3' (0.91 m) Min.
C)
2' (0.61 m) Min.
3' (0.91 m) Max.
4' (1.22 m) Min.
D)
3' (0.91 m) Min.
4' (1.22 m) Max.
6' (1.82 m) Min.
E)
4' (1.22 m) Min.
5' (1.52 m) Max.
7' (2.13 m) Min.
F)
5' (1.52 m) Min.
6' (1.82 m) Max.
8' (2.44 m) Min.
G)
6' (1.82 m) Min.
7' (2.13 m) Max.
9' (2.74 m) Min.
H)
7' (2.13 m) Min.
8' (2.44 m) Max. 10' (3.043 m) Min.
Restrictor Set #1 - 2" (51 mm) open
Lengths do not include elbow indicated.
*Required when using rigid venting