Gi29 Direct Vent Gas Insert | 27
installation
GasPipePressureTesting
It is necessary to isolate the unit from the gas supply
piping system prior to gas pipe pressure testing.
Close the unit's manual shut-off valve during test
-
ing at pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect the piping from the valve
at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control and should be checked
at the pressure test point.
HighElevation
This unit is approved for altitude 0 to 4,500 ft.
Gas Line Installation
Some municipalities have local codes for gas line
installation. Consult with your local authorities and
the CAN/CGA B149 installation code.
For USA installations, follow local codes and/or
the current National Fuel Gas Code, ANSI Z223.1.
When installing copper or flex connectors, use
approved fittings only. Flare nuts for copper lines
and flex connectors usually meet this requirement.
Provide a union for easy disconnection of gas lines
when servicing.
An incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact with
the rear burner or flame sensor.
PilotAdjustment
Periodically check the pilot flames. A correct flame
pattern has two strong blue flames: one flowing
around the flame sensor and one flowing across the
burner (it does not have to be touching the burner).
NGSystemData
Min. Supply Pressure
5" WC (1.25kPa)
Low Setting Man.
Pressure
1.1 WC (0.27 kPa)
Max. Manifold Pressure
3.8" WC (0.95 kPa)
Factory equipped for altitude 0-2000 ft. (0-610 m)
Orifice Size
#38 DMS
Minimum Input
17,000 Btu/h (4.98 kW)
Maximum Input
31,500 Btu/h ((9.22 kW)
Field convertible for altitude 2000-4500 ft. (610 m -
1,370 m) - use conversion kit #311-980
Orifice
#39 DMS
Minimum Input
16,500 Btu/h (4.83kW)
Maximum Input
30,500 Btu/h (8.93 kW)
LPSystemData
Factory equipped for altitude 0-4,000 ft. (0-1,370 m)
Min. Supply Pressure
11" WC (2.74 kPa)
Low Setting Man. Pressure
2.9 WC (0.72 kPa)
Max. Manifold Pressure
10.5 WC (2.61 kPa)
Orifice Size
#52 DMS
Maximum Input
31,500 Btu/h (9.22
kW)
Minimum Input
17,000 Btu/h (4.98
kW)
820ValveDescription
1.
Gas On/Off Knob
2.
Manual High/Low Adjustment
3.
Pilot Adjustment
4.
Thermocouple Connection
5.
Main Operator
6.
Outlet Pressure Tap (Manifold Pressure)
7.
Inlet Pressure Tap (Supply Pressure)
8.
Pilot Outlet
9.
Main Gas Outlet
10.
Flange Securing Screw Holes
11.
Alternative TC Connection Point
12.
Thermoelectric Unit
13.
Additional Valve Mounting Hole
NO
TE
To properly check gas pressure, both inlet
and manifold pressures should be checked
using the valve pressure ports on the valve.
1. Make sure the unit is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3. Attach manometer to "IN" or "OUT" pressure
tap(s) using a 5/16" ID hose.
4. Turn the unit on using the remote or wall switch.
5. Do the pressure check with the unit burning.
The setting should be within the limits specified
on the safety label.
NO
TE
If you have an incorrect flame pattern, contact
your Regency
®
dealer for further instructions.
NO
TE
•
The screw should be snug, but do not
over-tighten.
6. When finished reading the manometer, turn off
the unit, disconnect the hose, and tighten the
screw clockwise with a 1/8" flat screwdriver.
NO
TE
A shutoff / dante valve should be supplied in
or near the unit (or as per local codes) for
ease of servicing this appliance.
IMPOR
TANT
Alwayscheckforgasleakswitha
soapandwatersolutionorgasleak
detector.Donotuseopenflamefor
leaktesting.