Gi29 Direct Vent Gas Insert | 15
installation
Diagram 1
MinimumClearancestoCombustibles
Clearance:
Dimension
Measured From:
A: Sidewall
8" / 203 mm
***From inside edge of faceplate / doors
B: Ceiling
63-3/4" / 1873 mm From base of unit
D: Min. Hearth Depth
12" / 305 mm
Not required if unit raised 3" (76 mm) off the floor.
E: Min. Hearth Length
36"/ 914 mm
Not required if unit raised 3" (76 mm) off the floor.
J***
27-1/4" (692 mm) inside edge of the faceplate/doors - reference only.
K: Min. Alcove Width
54" / 1372 mm
L: Max. Alcove Depth
36" / 914 mm
From the front of the unit.
M: Mantel Deflector
2-1/2"/ 89 mm*
A
B
E
K
D
L
J***
NO
TES
•
A 36” (914 mm) wide x 12” (305 mm) deep, non-combustible hearth
is required in front of the appliance unless the unit is raised 3” (76 mm) off the floor.
•
*An optional 2-1/2" (64 mm) mantel deflector reduces the mantel height to 13" (330 mm) from top of the unit @ 1" (25 mm) depth.
The clearances listed below are minimum distances unless otherwise stated.
A major cause of fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this decorative gas
appliance is installed only in accordance with these instructions.