Manual –TC.GXS
2016-09-16
27 / 43
Template V02.11
4.3. Examples of system configuration
4.3.1.
Configuration of the system in series
TopCon TC.GXS power supply devices connected in series (also inter
systems) are not allowed to exceed a total DC voltage of 1500 V
DC
.
If you do not comply with this specification:
•
You will no longer be covered by the scope of the Low
voltage directive.
•
Devices may be damaged.
•
Operation is at your own risk.
Avoidance:
⇒
Limit the value of the DC voltage to a maximum of 1500 V
DC
.
1
2
DC+
DC-
Dummy plug
1
Dummy plug
2
1
DC-
DC+
Dummy plug
Fig. 8 System in series operation. master device
-1
- and slave device
-2-.
Sources
-1-
-2-
Device addresses
Master device and its
address
Master
(AH:0 AL:0)
Slave devices and their
addresses
---
Slave
(AH:0 AL:1)
CAN Bus
CAN Cable connection
---
X101 of Slave 1 is
connected with
X102 of Master.
Dummy plug
1
X101 is terminated with
“CAN TERM interlock”
X102 is terminated with
„CAN TERM“.
Software configuration (TopControl
<CONFIG> tab : Matrix multi-unit system)
<Number of Devices Inline> 2
---
<Number of parallel lines> 1
---
Tab. 14 System configuration
1
One „CAN TERM“ und one „CAN TERM with Interlock“ is necessary.
It is not possible using sense in serial mode. Deactivate sense in the software
TopControl or in HMI.
CAUTION