13 

3.  Adjusting of actuator 

 

Abide by safety measures! 

 
 

· 

electric switching the electric motor from the manual control status to the electric way of control, 

· 

electric blocking of the electric actuator while other mechanisms or devices operate, 

· 

adjustment of torque rate, 

· 

remote information about valve's stage of opening on the control board with variable resistance of 

the remote resistance transmitter (potentiometer).  

 
 

The  adjustment  can  be  performed  at  a  mechanically  and  electrically  connected  EA.  This  part 

describes adjustment of EA to specified parameters in case that any unit of EA is reset. Laying of 
adjusters of the control board is shown on Fig.2. 
 

3.1  EPV – the 2-wire version (Fig. 6) 

 

The  position  transmitter  with  the  converter  PTK1  is  in  the  plant  adjusted  to  have  the  output 

current signal on the terminals 81-82 (the wiring diagram Z23) as follows:  

· 

in the position “open“ .............................. 20 mA 

· 

in the position “closed“  ............................. 4 mA 

If the transmitter requires a new adjustment follow these steps: 

· 

Put  the  actuator to the position “closed“ and switch the 
power supply off. 

· 

Adjust the resistive transmitter according to the previous 
chapter.  The  resistance  is  to  be  metered  on  the 
terminals X-Y (Fig. 6). The used transmitter resistance is

 

100 

W

· 

Switch the converter

¢

s power supply on. 

· 

Turn  the  adjusting  trimmer  ZERO  (Fig.  6)  to  adjust  the 
output current signal rate measured on the terminals 81-
82 to  4mA. 

· 

Set the actuator to the position “open“. 

· 

Turn  the  adjusting  trimmer  GAIN  (Fig.  6)  to  adjust  the 
output current signal rate measured on the terminals 81-
82 to  20mA. 

· 

Check  the  output  signal  of  the  converter  in  the  both  limit  positions,  and  repeat  the 
procedure if needed..  

 

Note: 
The output signal of 4-20mA can be adjusted at the range from 75 up to 100% of the rated stroke stated on the 
actuator

¢

s nameplate. At values less than 75% the value  20mA is reduced proportionally. 

 

3.2   EPV – 3-wire version (Fig. 7) 

 

The  resistive  transmitter  with  the  converter  is  in  the  plant adjusted to have the output current 

signal metered on the terminals 81-82 (the wiring diagram Z257 - without power supply) as follows: 

· 

in the position „open“..................................... 20 mA or 5 mA 

· 

in the position „closed“ .................................. 0 mA  or4 mA 

according to the specified version of the converter. 
If the transmitter requires a new adjustment follow these steps: 

· 

Put the actuator to the position „closed“ and switch the power supply off. 

· 

Adjust the resistive transmitter according to the previous chapter. The resistance is to be metered 
on the terminals X-Y (Fig. 7). The used transmitter resistance is

 2000

W

 or 100 

W

.

 

· 

Switch the converter

¢

s power supply on. 

Fig. 6 

!

Содержание MP 52 200

Страница 1: ...74 0767 02 Electric part turn actuators MP 52 200 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Страница 2: ...ng diagram Operation time s 90 Operation angle Transmitter potentiometer Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance with...

Страница 3: ...7 Specifications 8 1 8 Packaging Transport Storing and Unpacking 10 1 9 Liquidation of the Product and the Package 11 2 Installation and Dismantling of the Actuator 11 2 2 Dismantling 12 3 Adjusting...

Страница 4: ...Operation Conditions and regarding its exposure rate is designated as a device with high exposure rate group A when it is an electric device of the group A see Regulation of MPSvR Ministry of Work and...

Страница 5: ...y service is provided by the service department of the producer on the basis of a written claim While claiming it is advised to present the following basic data from the nameplate type and serial numb...

Страница 6: ...llution AF 2 with a possibility of influences of mechanical stress medium sinusoid vibrations with frequency in range 10 up to 150 Hz with shift amplitude of 0 15 mm for f fp and acceleration amplitud...

Страница 7: ...ule M3 a gearbox with a manual control mechanism The gear train is located in the case 1 The gears are placed on the output shaft 3 and they make up an independent assembly set The rim 44 with interna...

Страница 8: ...o the control board place into the control box a transmission unit of the control board a position an indication unit a torque unit a transmitter block space heater local position indicator electric c...

Страница 9: ...ig 5 Position unit 11 After loosen a nut of the position unit 51 is possible to rotate 53 54 56 57 The construction of position unit is designed so that transforming one of the cams it does not distur...

Страница 10: ...ends 29 The flange 27 is screwed onto the actuator box 1 penetrated With a shaft and on its free end the lever is mounted Fig 8 1 7 Specifications Basic Specifications are given in the table 1 1 7 1...

Страница 11: ...lue Adjustment of the capacitive transmitter the position open 20 mA the position close 0 4 mA Weight 27 up to 29 kg Lubrication grease HF 401 0 GLEITM m Gearbox oil PP 80 1 7 2 Mechanical Connection...

Страница 12: ...or message LED SYS mode error message LED Adjusters communication connector 2x calibrating and adjusting button Local position indication with position indicator visible through aperture in upper cove...

Страница 13: ...gle parts of the package and the product should not be thrown away after its lifetime but sorted according to the related regulations and rules about environment protection and delivered for next trea...

Страница 14: ...rection open Press the lever 42 in the direction to the output shaft what switches contacts 20 MO S1 and the actuator should stop Press the button SB1 closed on the control board The output shaft shou...

Страница 15: ...Y Fig 6 The used transmitter resistance is 100 W Switch the converter s power supply on Turn the adjusting trimmer ZERO Fig 6 to adjust the output current signal rate measured on the terminals 81 82 t...

Страница 16: ...ust be power supplied In opposite case it is not guaranteed disconnection of remote control after switching the mode switch to the mode LOCAL Fig 10 4 Service maintenance and troubleshooting 4 1 Servi...

Страница 17: ...upply the EA stops in the position where it was before the failure If needed the EA can be set only with the manual control the handwheel After restoration of power the EA is prepared for operation In...

Страница 18: ...16 MP 52 200 4 4 Wiring diagrams...

Страница 19: ...er 2 wire with power supply Z295 connection of 1 phase electric motor Z298 connection of torque and position switches and space heater Z299 connection of torque and position switches and space heater...

Страница 20: ...18 MP 52 200 4 5 Dimensional drawings...

Страница 21: ...MP 52 200 19...

Страница 22: ...20 MP 52 200...

Отзывы: