11
4.1 POWER WIRING
1
2
AC/DC
AC/DC
4.2 VOLTAGE/RESISTANCE/CURRENT INPUT SIGNAL WIRING
IMPORTANT
: Before connecting signal wires, the Input Range Jumpers and Excitation Jumper should be verified for proper position.
Process/Current
Signal
(external powered)
Voltage Signal
Process/Current Signal
(2 wire requiring 18V
excitation)
Excitation Jumper: 18 V
7
8
+
̶
200VDC MAX.
V-
TC
-R
TD I
N
INP COMM
Current Signal (3 wire
requiring 18 V excitation)
Terminal 3: +Volt supply
Terminal 6: +ADC (signal)
Terminal 8: -ADC (common)
Excitation Jumper: 18 V
Voltage Signal (3 wire
requiring 18 V excitation)
Terminal 3: +Volt supply
Terminal 7: +VDC (signal)
Terminal 8: -VDC (common)
Excitation Jumper: 18 V
6
8
2A DC MAX.
I INPUT
INP COMM
Load
-
+
-
+
Resistance Signal
(2 wire requiring
excitation)
Terminal 3: Jumper to
terminal 7
Terminal 7: Resistance
Terminal 8: Resistance
Excitation Jumper:
1.05 mA REF.
T/V Jumper: V position
Voltage/Resistance Input
Jumper: Set per input signal
3
7
8
V EX
C
INP COMM
V-TC-RTD-IN
1.05 mA
REF.
10K MAX
Potentiometer Signal as Voltage Input
(3 wire requiring excitation)
Terminal 3: High end of pot.
Terminal 7: Wiper
Terminal 8: Low end of pot.
Excitation Jumper: 2 V REF.
T/V Jumper: V
Voltage/Resistance Input Jumper: 2 Volt
Module 1 Input Range: 2 Volt
Note: The Apply signal scaling style
should be used because the signal
will be in volts.
6
7
8
3
V-TC-RTD-IN
I INPUT
V EX
C
INP COMM
+
3 WIRE TRANSMITTER
_
Vout
Iout
3
7
8
Rmin=1K
Ω
V EX
C
INP COMM
V-TC-RTD-IN
2V REF.
2V
INPUT
6
3
V EX
C
I INPUT
2 WIRE
TRANSMITTER
-
+
CAUTION:
Sensor input common is NOT isolated from user input common. In order to preserve the safety of the application, the sensor input common
must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not, hazardous
live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the potential of the
user input common with respect to earth common; and the common of the isolated option cards with respect to input common.
4.3 TEMPERATURE INPUT SIGNAL WIRING
IMPORTANT
: Before connecting signal wires, verify the T/V Jumper is in the T position.
3-Wire RTD
Thermocouple
2-Wire RTD
5
7
8
RTD EX
C
V-TC-RTD-IN
INP COMM
Sense Lead
Jumper
5
7
8
RTD EX
C
V-TC-RTD-IN
INP COMM
Sense Lead
RTD (Excitation)
7
8
+
̶
V-TC-RTD-IN
INP COMM
CAUTION
: Sensor input common is NOT isolated
from user input common. In order to preserve the
safety of the application, the sensor input common
must be suitably isolated from hazardous live
earth referenced voltages; or input common must be
at protective earth ground potential. If not,
hazardous live voltage may be present at the User
Inputs and User Input Common terminals.
Appropriate considerations must then be given to
the potential of the user input common with respect
to earth common; and the common of the isolated
option cards with respect to input common.
+
-
+
-
OR
1
2
AC/DC
AC/DC
1
2
AC/DC
AC/DC
AC Power
DC Power
The power supplied to the unit shall employ a 15 Amp UL approved circuit breaker for AC input and a 1 Amp, 250 V UL approved fuse for DC input. It shall be
easily accessible and marked as a disconnecting device to the installed unit. This device is not directly intended for connection to the mains without a reliable means
to reduce transient over-voltages to 1500 V.