background image

6

g

eneral

 m

eTer

 s

PeCifiCaTiOns

1. 

DISPLAY

: Negative image LCD

Top Line - 6 digit, 0.71" (18 mm), with tri-color backlight (red, green or 

orange), display range: -199999 to 999999;

Bottom Line - 9 digit, 0.35" (8.9 mm), with green backlight, display range: 

- 199,999,999 to 999,999,999

2. 

POWER

:

AC Power: 40 to 250 VAC, 50/60 Hz, 20 VA
DC Power: 21.6 to 250 VDC, 8 W
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.

3. 

ANNUNCIATORS

: Backlight color: Red

1 - setpoint alarm 1
2 - setpoint alarm 2
3 - setpoint alarm 3
4 - setpoint alarm 4
Line 1 Units Display – programmable 3 digit units annunciator with tri-color 

backlight (red, green or orange)

4. 

KEYPAD

: 2 programmable function keys, 4 keys total

5. 

A/D CONVERTER

: 24 bit resolution

6. 

UPDATE RATES

:

A/D conversion rate: programmable 5 to 160 readings/sec.
Step response: 

Input Type

Input Update Rate

Readings/

Sec

5

10

20

40

80

160

V/I/Resistance

400

200

100

50

30

20

msec 

response 

time *

Thermocouple

600

250

100

-

-

-

RTD

1000

500

250

-

-

-

* - max. to within 99% of final readout value (digital filter disabled)
Display update rate: 1 to 20 updates/sec.
Setpoint output on/off delay time: 0 to 3275 sec.
Analog output update rate: 0 to 10 sec
Max./Min. capture delay time: 0 to 3275 sec.

7. 

DISPLAY MESSAGES

:

“OLOL” - Appears when measurement e signal range.
“ULUL” - Appears when measurement exceeds - signal range
“Short” - Appears when shorted sensor is detected. (RTD range only)
“OPEN” - Appears when open sensor is detected. (TC/RTD range only)
“. . . . .” - Appears when display values display range.
“- . . . . .” - Appears when display values exceed - display range.

8. 

INPUT CAPABILITIES

:

Current Input

:

INPUT RANGE

ACCURACY * 

(18 to 28°C)

ACCURACY * 

(0 to 50°C)

IMPEDANCE

‡ 

RESOLUTION

± 250 µADC

0.03% of rdg 

 + 0.03µA

0.12% of rdg 

 + 0.04µA

1.11 K

W

10nA

± 2.5 mADC

0.03% of rdg 

 + 0.3µA

0.12% of rdg 

 + 0.4µA

111 

W

0.1µA

± 25 mADC

0.03% of rdg 

 + 3µA

0.12% of rdg 

 + 4µA

11.1 

W

1µA

± 250 mADC 

0.05% of rdg 

 + 30µA

0.12% of rdg 

 + 40µA

1.1 

W

10µA

± 2 ADC 

0.5% of rdg 

 + 0.3mA

0.7% of rdg 

 + 0.4mA

0.1 

W

0.1mA

 Higher resolution can be achieved via input scaling.

Voltage Input

:

INPUT RANGE

ACCURACY * 

(18 to 28°C)

ACCURACY * 

(0 to 50°C)

IMPEDANCE

‡ 

RESOLUTION

± 250 mVDC

0.03% of rdg 

 + 30µV

0.12% of rdg 

 + 40µV

451 K

W

10µV

± 2.0 VDC

0.03% of rdg 

 + 0.3mV

0.12% of rdg 

 + 0.4mV

451 K

W

0.1mV

± 10 VDC

0.03% of rdg 

 + 3mV

0.12% of rdg 

 + 4mV

451 K

W

1mV

± 25 VDC 

0.03% of rdg 

 + 3mV

0.12% of rdg 

 + 4mV

451 K

W

1mV

± 100 VDC 

0.3% of rdg 

 + 30mV

0.12% of rdg 

 + 40mV

451 K

W

10mV

± 200 VDC 

0.3% of rdg 

 + 30mV

0.12% of rdg 

 + 40mV

451 K

W

10mV

‡ Higher resolution can be achieved via input scaling.

Temperature Inputs

:

READOUT:

Scale: F or C

Offset Range: -199,999 to 999,999 display units.

Thermocouple Inputs:

Input Impedance: 20M

W

Lead Resisitance Effect: 0.03 µV/

W

Max Continuous Overvoltage: 30 V

INPUT 

TYPE

RANGE

ACCURACY* 

(18 to 28 °C)

ACCURACY* 

(0 to 50 °C)

STANDARD

WIRE COLOR

ANSI

BS 1843

T

-200 to 400°C

1.2°C

2.1°C

ITS-90

(+) blue 
(-) red

(+) white 
(-) blue

E

-200 to 750°C

1.0°C

2.4°C

ITS-90

(+) purple 
(-) red

(+) brown 
(-) blue

J

-200 to 760°C

1.1°C

2.3°C

ITS-90

(+) white 
(-) red

(+) yellow 
(-) blue

K

-200 to 1250°C

1.3°C

3.4°C

ITS-90

(+) yellow 
(-) red

(+) brown 
(-) blue

R

0 to 1768°C

1.9°C

4.0°C

ITS-90

no 
standard

(+) white 
(-) blue

S

0 to 1768°C

1.9°C

4.0°C

ITS-90

no 
standard

(+) white 
(-) blue

B

150 to 300°C 

300 to 1820°C

3.9°C 
2.8°C

5.7°C 
4.4°C

ITS-90

no 
standard

no 
standard

N

-200 to 1300°C

1.3°C

3.1°C

ITS-90

(+) orange 
(-) red

(+) orange 
(-) blue

(W5/W26)

0 to 2315°C

1.9°C

6.1°C

ASTM 

E988-90**

no 
standard

no 
standard

RTD Inputs

:

Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
Excitation current: 100 ohm range: 136.5 

µ

A ±10%

   

10 ohm range:  2.05 mA ±10%

Lead resistance: 100 ohm range: 10 ohm/lead max.
   

10 ohm range: 3 ohms/lead max.

Max. continuous overload: 30 V

INPUT TYPE

RANGE

ACCURACY* 

(18 to 28 

°

C)

ACCURACY* 

(0 to 50 

°

C)

STANDARD 

**

100 ohm Pt  

alpha = .00385

-200 to 850°C

0.4°C

1.6°C

IEC 751

100 ohm Pt  

alpha = .00392

-200 to 850°C

0.4°C

1.6°C

no official 

standard

120 ohm Nickel 

alpha = .00672

-80 to 259°C

0.2°C

0.5°C

no official 

standard

10 ohm Copper  

alpha = .00427

-110 to 260°C

0.4°C

0.9°C

no official 

standard

Resistance Inputs

:

INPUT 

RANGE

ACCURACY * 

(18 to 28°C)

ACCURACY * 

(0 to 50°C)

COMPLIANCE

MAX CONT. 

OVERLOAD

‡ 

RESOLUTION

100 ohm

0.05% of rdg 

+0.03 ohm

0.2% of rdg 

+0.04 ohm

0.175 V

30 V

0.01 ohm

1000 ohm

0.05% of rdg 

+0.3 ohm

0.2% of rdg 

+0.4 ohm

1.75 V

30 V

0.1 ohm

10 Kohm

0.05% of rdg 

+1 ohm

0.2% of rdg 

+1.5 ohm

17.5 V

30 V

0.1 ohm

‡ Higher resolution can be achieved via input scaling.

* After 20 min. warm-up, @ 5 sample per second input rate. Accuracy is 

specified in two ways: Accuracy over an 18 to 28ºC and 15 to 75% RH 
environment; and Accuracy over a 0 to 50ºC and 0 to 85% RH (non 
condensing) environment. The specification includes the A/D conversion 
errors, linearization conformity, and thermocouple ice point compensation. 
Total system accuracy is the sum of unit and probe errors. Accuracy may 
be improved by field calibrating the unit readout at the temperature of 
interest.

** These curves have been corrected to ITS-90.

Содержание PAX2A

Страница 1: ...1 User Manual PAX2A 1 8 DIN Analog Panel Meter Revision D Released 08 15 LP0830 ...

Страница 2: ...ment connected to it If equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired Do not use this unit to directly command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event of a fault to the unit CAUTION Risk of Danger Read complete instructions prior ...

Страница 3: ...Input Setup Parameters 1 INPUt 15 Module 2 User Input Function Key Parameters 2 FUNCt 16 Module 3 Display Parameters 3 dISPLY 19 Module 4 Secondary Function Parameters 4 SCNdrY 21 Module 5 Totalizer Integrator Parameters 5 totAL 22 Module 6 Setpoint Output Parameters 6 SEtPNt 23 Module 7 Serial Communications Parameters 7 SErIAL 25 Serial Communications Overview 26 PAX2A Frequently Used Modbus Reg...

Страница 4: ...DC10 Extended RS485 Serial Communications Card with Dual RJ11 Connector PAXCDC1C RS232 Serial Communications Card with Terminal Block PAXCDC20 Extended RS232 Serial Communications Card with 9 Pin D Connector PAXCDC2C DeviceNet Communications Card PAXCDC30 Profibus DP Communications Card PAXCDC50 PAXCDL Analog Output Card PAXCDL10 Accessories CBLUSB USB Programming Cable Type A Mini B CBLUSB01 RCP ...

Страница 5: ...puter and the find function be used The alternate method of finding information is to identify the programming parameter involved and review the information contained in the section of the manual that pertains to that parameter CrimsOn PrOgramming sOfTware PrOgramming Using CrimsOn Crimson is included on the Flash Drive that is shipped with the PAX2 Check for updates to Crimson at http www redlion...

Страница 6: ...rdg 30mV 0 12 of rdg 40mV 451 KW 10mV 200 VDC 0 3 of rdg 30mV 0 12 of rdg 40mV 451 KW 10mV Higher resolution can be achieved via input scaling Temperature Inputs READOUT Scale F or C Offset Range 199 999 to 999 999 display units Thermocouple Inputs Input Impedance 20MW Lead Resisitance Effect 0 03 µV W Max Continuous Overvoltage 30 V INPUT TYPE RANGE ACCURACY 18 to 28 C ACCURACY 0 to 50 C STANDARD...

Страница 7: ...lues 14 ENVIRONMENTAL CONDITIONS Operating Temperature Range 0 to 50 C Storage Temperature Range 40 to 60 C Vibration to IEC 68 2 6 Operational 5 150 Hz 2 g Shock to IEC 68 2 27 Operational 25 g 10 g relay Operating and Storage Humidity 0 to 85 max RH non condensing Altitude Up to 2000 meters 15 CERTIFICATIONS AND COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 1...

Страница 8: ...t full load rating External RC snubber extends relay life for operation with inductive loads QUAD RELAY CARD PAXCDS20 Type Four FORM A relays Isolation To Sensor User Input Commons 2300 Vrms for 1 min Contact Rating One Relay Energized 3 amps 240 VAC or 30 VDC resistive load Total current with all four relays energized not to exceed 4 amps Life Expectancy 100K cycles min at full load rating Extern...

Страница 9: ...s It is recommended to release the latch on one side then start the other side latch Warning Exposed line voltage exists on the circuit boards Remove all power to the unit AND load circuits before removing the unit from its case INPUT RANGE JUMPERS Voltage Input Two jumpers are used in configuring the unit for voltage resistance The first jumper T V must be in the V voltage position The second jum...

Страница 10: ...igh degree of immunity to Electromagnetic Interference EMI proper installation and wiring methods must be followed to ensure compatibility in each application The type of the electrical noise source or coupling method into a unit may be different for various installations Cable length routing and shield termination are very important and can mean the difference between a successful or troublesome ...

Страница 11: ...reserve the safety of the application the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must be at protective earth ground potential If not hazardous live voltage may be present at the User Inputs and User Input Common terminals Appropriate considerations must then be given to the potential of the user input common with respect to earth...

Страница 12: ...DE OPERATION PROGRAMMING MODE OPERATION D Index Line 2 through enabled max min input total readouts Quick exit to display mode P Access the parameter and hidden display loops Access the programming parameter menus store selected parameter and index to next parameter Function key 1 hold for 3 seconds for second function 1 Increment selected parameter value Function key 2 hold for 3 seconds for seco...

Страница 13: ...ot If the value is not required select the lock mode LOC If you decide to display the value you will need to assign it to a loop D for the Main Display Loop P for the Parameter Display Loop and HidE for the Hidden Display Loop In the case of the parameters such as the setpoint values you will also need to decide if the value can only be read rEd or entered ENt The and key will increment or decreme...

Страница 14: ...ODE P Parameters Display Loop D D D Hidden Parameters Display Loop P P P 6 0 PrOgramming The PaX2a Pro NO Pro 1 INPUt Pro 2 FUNCt Pro 3 dISPLY Pro 4 SCNdrY Pro 5 totAL Pro 6 SEtPNt Pro 7 SErIAL Pro 8 AnLOut Pro 9 FACtrY Signal Input Parameters User Input Function Key Parameters Display Program Lock out Parameters Secondary Function Parameters Totalizer Parameters Setpoint Parameters Serial Comms P...

Страница 15: ...t Range selected rANgE ROUNDING INCREMENT 1 2 5 10 20 50 100 Rounding selections other than one cause the Input Display to round to the nearest rounding increment selected ie rounding of 5 causes 122 to round to 120 and 123 to round to 125 Rounding starts at the least significant digit of the Input Display Remaining parameter entries scaling point values setpoint values etc are not automatically a...

Страница 16: ...P key to save and continue to the next parameter To update program this value apply the input signal that corresponds to Scaling Point 2 press key and the actual signal value will be displayed Then press the P key to accept this value and continue to the next parameter Follow the same procedure if using more than 2 scaling points DISPLAY VALUE FOR SCALING POINT 2 199999 to 999999 Enter the second ...

Страница 17: ...zer at transition to activate momentary action and Line 2 flashes bAtCh The Totalizer retains a running sum of each batch operation until the Totalizer is reset When this function is selected the normal operation of the Totalizer is overridden and only batched Input Display values accumulate in the Totalizer SELECT TOTALIZER DISPLAY The Totalizer display appears on Line 2 as long as activated main...

Страница 18: ...aintained action If a front panel key is used to select the list then the list will toggle for each key press momentary action The display will only indicate which list is active when the list is changed To program the values for LISt A and LISt b first complete the programming of all the parameters Exit programming and switch to the other list Re enter programming and enter the desired values for...

Страница 19: ...o 15 Enter the desired Display Contrast Level 0 15 by using the arrow keys The display contrast viewing angle will actively move up or down as the levels are changed This parameter also appears in the Parameter Display Loop when enabled LINE 1 DISPLAY INPUt totAL Hi Lo S1 S2 S3 S4 NONE Select the value to be assigned to the primary or top line of the unit display UNITS MNEMONIC OFF LISt This param...

Страница 20: ...RAST ACCESS LOC P rEd P ENt HidE When configured for P ENt the display contrast can be selected in the Parameter Display by using the and keys while viewing d Cont LINE 2 USER FUNCTIONS ACCESSIBLE ITEMS YES NO Select YES to display the following list of User functions that can be made available at the end of the Parameter P ENt or Hidden HidE display loops The more critical and frequently used Fun...

Страница 21: ... display value as the new MAX reading A delay time helps to avoid false captures of sudden short spikes MIN CAPTURE ASSIGNMENT rEL AbS Select the desired parameter that will be assigned to the Min Capture MIN CAPTURE TIME 0 0 to 3275 0 seconds When the Input Display is below the present MIN value for the entered delay time the unit will capture that display value as the new MIN reading A delay tim...

Страница 22: ...OTALIZER BATCHING The Totalizer Time Base and scale factor are overridden when a user input or function key is programmed for store batch bAt In this mode when the user input or function key is activated the Input Display reading is one time added to the Totalizer batch The Totalizer retains a running sum of each batch operation until the Totalizer is reset This is useful in weighing operations wh...

Страница 23: ...int Actions that pertains to the total is only active when the Setpoint Assignment is set to totAL NO No Setpoint Action Ab HI Absolute high with balanced hysteresis Ab LO Absolute low with balanced hysteresis AU HI Absolute high with unbalanced hysteresis AU LO Absolute low with unbalanced hysteresis dE HI deviation high with unbalanced hysteresis dE LO deviation low with unbalanced hysteresis bA...

Страница 24: ...arm output on at the trigger point per the Setpoint Action shown in Setpoint Alarm Figures Latch means that the alarm output can only be turned off by front panel function key or user input manual reset serial reset command or unit power cycle When the user input or function key is activated momentary or maintained the corresponding on alarm output is reset immediately and remains off until the tr...

Страница 25: ...quipment on the serial link The unit ignores the parity when receiving data and sets the parity bit for outgoing data If no parity is selected with 7 bit word length an additional stop bit is used to force the frame size to 10 bits UNIT ADDRESS 0 to 99 RLC Protocol 1 to 247 ModBus Select a Unit Address that does not match an address number of any other equipment on the serial link TRANSMIT DELAY 0...

Страница 26: ...low limit It is also returned in the response FC16 Preset Multiple Registers 1 No response is given with an attempt to write to more than 32 registers at a time 2 Block starting point cannot exceed the read and write boundaries 1 1280 3 If a multiple write includes read only registers then only the write registers will change 4 If the write value exceeds the register limit see Register Table then ...

Страница 27: ...ist A or B 14 Setpoint 3 Value Lo word 15 Setpoint 4 Value Hi word 199999 999999 400 Read Write Active List A or B 16 Setpoint 4 Value Lo word 17 Setpoint 1 Band Dev Value Hi word 199999 999999 0 Read Write Active List A or B Applicable only for Band or Deviation Setpoint Action 18 Setpoint 1 Band Dev Value Lo word 19 Setpoint 2 Band Dev Value Hi word 199999 999999 0 Read Write Active List A or B ...

Страница 28: ...hat the command affects The P command does not require a Register ID character It prints according to the selections made in print options 4 If constructing a value change command writing data the numeric data is sent next 5 All command strings must be terminated with the string termination characters or The unit does not begin processing the command string until this character is received See Tim...

Страница 29: ...anual Mode 1 the outputs are defined by the registers SOR and AOR When transferring from auto mode to manual mode the unit holds the last output value until the register is changed by a write Each output may be independently changed to auto or manual In a write command string VU any character besides 0 or 1 in a field will not change the corresponding output mode U abcde e Analog Output d SP4 c SP...

Страница 30: ... Figure LOGIC RS232 RS485 INTERFACE STATE 1 TXD RXD 3 to 15 V a b 200 mV mark idle 0 TXD RXD 3 to 15 V a b 200 mV space active Voltage levels at the Receiver COMMAND RESPONSE TIME The unit can only receive data or transmit data at any one time half duplex operation When sending commands and data to the unit a delay must be imposed before sending another command This allows enough time for the unit...

Страница 31: ...ETER MENU ANALOG OUTPUT TYPE 4 20 0 10 0 20 Enter the analog output type For 0 20 mA or 4 20 mA use terminals 18 and 19 For 0 10 V use terminals 16 and 17 Only one range can be used at a time ANALOG OUTPUT ASSIGNMENT NONE rEL AbS totAL Hi Lo S1 S2 S3 S4 Enter the source for the analog output to retransmit NONE Manual Mode operation See Module 7 Serial RLC Protocol rEL Relative net Input Value The ...

Страница 32: ... warm up period before calibrating the unit Selecting NO at any calibration step will cause the unit to maintain the existing calibration parameters for that step Selecting YES and pressing P key will cause the unit to store new calibration settings for the range selected Pressing D at any time will exit programming mode but any range that has been calibrated will maintain the new settings RTD Cal...

Страница 33: ...ta Validation Error Contact factory Error Code EE Lin Linear Output Card Data Validation Error Press any key to clear Error Code and cycle power If Error Code returns at next power up replace Linear Option Card or contact factory PARAMETER VALUE CHART Programmer ________________ Date ________ PAX2A Unit _____________ Security Code ________ 1 InPUt INPUT SETUP PARAMETERS DISPLAY PARAMETER USER SETT...

Страница 34: ...ARAMETER USER SETTING dECPNt TOTALIZER DECIMAL POINT t bASE TOTALIZER TIME BASE SCLFAC TOTALIZER SCALE FACTOR Lo Cut TOTALIZER LOW CUT VALUE PWrUP TOTALIZER POWER UP RESET 6 SEtPNt SETPOINT OUTPUT PARAMETERS DISPLAY PARAMETER USER SETTING USER SETTING USER SETTING USER SETTING SELECt SETPOINT SELECTION S1 S2 S3 S4 ASSIGN SETPOINT SOURCE ACtION ACTION FOR SETPOINT SEtPNt SETPOINT VALUE bn dEV SETPO...

Страница 35: ...ment MIN Capture Time Display Update Rate Pro 3 dISPLY P Color GrEEN Ln1 Display Color d LEV4 dSP Display Intensity LINE 1 INPUt dSP Line 1 Display d Cont 7 dSP Display Contrast UNItS OFF dSP Units Mnemonic ACCESS NO Ln2 Access Line 2 INPUt LOC Ln2 Line 2 Input Access tOtAL LOC Ln2 Line 2 Total Access Hi LOC Ln2 Line 2 MAX Access Lo LOC Ln2 Line 2 MIN Access bn dn LOC Ln2 Band and Deviation Value ...

Страница 36: ...LITY B WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE OR C WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY WHETHER EXPRESS OR IMPLIED BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OF TRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal ...

Отзывы: