11 - SAFETY DEVICES AND ALARMS
Technical Dept. - All rights reserved - Reproduction is prohibited
ALARM SIGNALLING
When a condition occurs other than the one expected for regular operation of the boiler, an alarm is triggered.
The reason for the alarm is given on the control panel. The sound signal is not enabled for alarms A01-A02 in order not to disturb the user
when there is an absence of pellets in the night tank.
Panel signalling
type of problem
Solution
A01
The flame does not light
Check the level of pellets in the tank.
Check that the brazier is correctly positioned in its
seat and has no build-up or unburned material.
Make sure the ignition plug warms up.
Thoroughly empty and clean the brazier before
restarting.
A02
The flame is extinguished unexpectedly.
Check the level of pellets in the tank.
A03
Thermostats alarm
The temperature of the pellet hopper or the
water temperature exceeds the safety threshold.
Wait until the end of the cooling phase, stop the
alarm and re-ignite the boiler setting the supply of
fuel to minimum (SETTINGS menu - pellet recipe). If
the alarm persists, contact the service centre.
A04
Smoke overtemperature
The set smoke threshold has been exceeded. Reduce
the load of pellets (SETTINGS menu - Pellet recipe).
A05
Pressure switch alarm
Fumes pressure switch intervention or water
pressure insufficient.
Check for chimney obstructions / door open or the
pressure of the hydraulic system.
A08
Anomalous operation of smoke fan.
If the alarm persists, contact the service centre.
A09
Fault with the smoke sensor.
If the alarm persists, contact the service centre.
A19
Fault with water sensor.
Water sensor detached / interrupted / defective / not
recognised.
A20
Puffer probe alarm.
Puffer probe detached / interrupted / defective / not
recognised.
Service
Routine maintenance warning (does not seize) When this blinking message appears upon start-up, it
means it is time to carry out scheduled maintenance.
Call the assistance centre.
ALARM RESET
NEVER open the appliance door whilst the stove is either in the initial startup or on its shut down cycle, pellets will
still be smoldering or therefore volatiles may be present.
ATTENTION!
If during operation or initial ignition you encounter smoke spillage in to the room from the appliance or the flue
then please switch off the appliance, ventilate the room and contact the installation / service engineer immediately.
Содержание COMPACT SLIM 15
Страница 1: ...INSTALLATION GUIDE GB Translation of original instructions PELLET BOILER COMPACT SLIM 15...
Страница 30: ...28 B C A 6 PANEL REMOVAL Upper top Lift top A remove and secure tops B and C Tops B and C are only supported...
Страница 38: ...36 n V r 7 HYDRAULIC CONNECTION FIGURE3 FIGURE4...
Страница 71: ...69 13 MAINTENANCE AND CLEANING Technical Dept All rights reserved Reproduction is prohibited Figure5 Figure4...