background image

6HBWDOG1 

 

Heartbeat Relay

 

Connect

.Monitor

.

Control

.

 

3

 

DIP-Switch Settings 

3.1  Setting DIP-Switches 

Configuration: 

Once installed in a system, the heartbeat signal must be configured. The controller is configured first to 

toggle the discrete output which is connected to IN+/IN- at the desired frequency. Once the controller is configured in 
this way the DIP switches located on the top of the Heartbeat Watchdog Module can be set to monitor the heartbeat 
signal. Two time settings are provided in the Heartbeat Watchdog Module: 

Boot Delay:

 This time setting causes the Heartbeat Watchdog Module to wait a specific time after Power-Up or 

Reset before monitoring the Heartbeat Input. The purpose for this delay is to provide sufficient time for the 
system controller to boot up and begin toggling the heartbeat signal before the Heartbeat Watchdog Module 
begins monitoring the signal. This time delay setting should be configured to account for the worst case boot 
time of the system. If the boot delay is set too short, the Heartbeat Watchdog module will sense the lack of 
input signal changes while the system boots as a failure of the system. 

Heartbeat Timeout:  

This time setting defines the maximum period between rising edges of the Heartbeat input 

signal which indicates proper operation of the system. If the Heartbeat input period exceeds this time setting, 
then the Heartbeat Watchdog Module will detect this as a failure of the system. 
Each time setting is assigned to four DIP switches, and each group of four switches is divides into two pairs of 
switches. One pair is used to configure a base time and the other pair will configure a multiplier for that base 
time, so a wide range of times can be accommodated. The switch settings are shown in the diagram below: 

 
 

As an example, if the intention is to set a boot delay of 100 seconds, switches 1-2 would both be set in the up 
position for a time of 25 seconds, and switches 3-4 would be set down (3) and up (4) for a multiplier of 4. This 
setting provides 25 seconds x4 for 100 seconds boot delay. 
Another example using the heartbeat timeout switches for a desired heartbeat period of 5 seconds would be: 
switches 5-6 set up (5) and down (6) for a 5 second time, while switches 7-8 would both be set down for a x1 
multiplier. 5 seconds x 1 yields a heartbeat interval of 5 seconds. Power Wiring Alternatives 

1 2 3 4 5 6 7 8

Boot 

Delay 

Heartbeat 

Timeout 

Time 

Time

 

Multiplier 

Time

 

Multiplier 

DIP Switch Configuration Settings 

1 Second

5 Seconds

10 Seconds 

25 Seconds 

Time Switch Positions 

Timex1

Timex2 

Timex4

1 Second 

1 Second 

Timex8

1 Second 

1 Second 

Multiplier Switch Positions 

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание Watchdog 6HBWDOG1

Страница 1: ...1 Watchdog Relay 6HBWDOG1 User Manual December 2014 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 2: ...CHANGE HISTORY Version Date Description R01 9 2013 First Draft Revision R02 11 2013 Added power consumption specification and fixed typos R03 12 2014 Remove pending references Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 3: ... Getting Started with Red Lion Controls Hardware 7 2 Assembly and Instruction 8 2 1 Panel Assembly 8 3 DIP Switch Settings 10 3 1 Setting DIP Switches 10 4 Power Requirements 11 5 Module Wiring Screw Terminal Assignments 11 6 Safety Relay Status LED s and Buttons 13 7 Product Support 14 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 4: ...G EXPLOSION HAZARD SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 3 WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS 4 WARNING EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE SEALED RELAY DEVICE 5 FIELD WIRING CONDUCTOR MINIMUM INSULATION RATING 75 C ...

Страница 5: ...ch toggles on and off under processor control If the processor malfunctions the heartbeat will cease to toggle and the Heartbeat Watchdog Module will sense this failure and shut down the system by opening the relay powering the system The Heartbeat Watchdog Module is designed for extreme reliability using no microprocessor or other programmable logic elements in its design Using hard wired logic e...

Страница 6: ... Polarity Sourcing Input isolation 150 Volts Guaranteed ON voltage 9 VDC Guaranteed OFF voltage 1 0 VDC Guaranteed OFF current 1 0 mA DC Input resistance 24VDC 2 6 Kohms Input current 24 VDC 10 mA Input Protection High Impedance with overvoltage protection Heartbeat Frequency 1 50Hz Heartbeat timeout configurable 1s to 200s 1Hz may not work at fastest heartbeat timeout time of 1 second Output Circ...

Страница 7: ...activated after the boot delay time expires 6 Press the bypass button to enable bypass mode Using a pen or a small screw driver press the bypass button on the front of the watchdog relay once The boot bypass LED will illuminate and remain ON until the button is pressed again The bypass mode will activate the form C relay so power will be applied to the PLC instruments connected to the relay 7 Appl...

Страница 8: ...ooking the top of the DIN rail mounting bracket on the top of the DIN rail then pressing down See the mounting diagrams below The watchdog relay module is approximately 4 high and 1 wide refer to the Mechanical Dimensions diagram below The screw terminals size is M3 and can support wire sizes of 30 to 12AWG The recommended torque is 5 IN LB Mechanical Dimensions Buy www ValinOnline com Phone 844 3...

Страница 9: ...6HBWDOG1 Heartbeat Relay Connect Monitor Control Applying to DIN Rail Removing from DIN Rail Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 10: ...signal which indicates proper operation of the system If the Heartbeat input period exceeds this time setting then the Heartbeat Watchdog Module will detect this as a failure of the system Each time setting is assigned to four DIP switches and each group of four switches is divides into two pairs of switches One pair is used to configure a base time and the other pair will configure a multiplier f...

Страница 11: ...artbeat Watchdog Module is a pluggable screw terminal block with retaining screws which secure the block to the module The connections on the screw terminals are described in the diagram below IN IN N C COM N O V GND Heartbeat Input Isolated 10 30VDC Heartbeat Signal Input Screws Form C Relay Output Relay will connect N O to COM when Heartbeat signal is valid N C to COM will connect if Heartbeat i...

Страница 12: ...vices is below When the heartbeat pulse is present on IN input the product powered by the relay will be powered When the heartbeat pulse stops for the configured heartbeat timeout the optional external lamp will be powered to indicate an alarm state Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 13: ...e relay state during the maintenance period Reset Button Pressing this button causes the Heartbeat Watchdog Module to perform a hard reset the same as if the power had been cycled to the module The relay will close followed by the normal boot delay time after which heartbeat input monitoring will begin Power Indicator This indicator will illuminate whenever adequate power is supplied to the Heartb...

Отзывы: