9

The Security Code determines the programming mode and the accessibility 

of programming parameters. This code can be used along with the Program 

Mode Lock-out (

P-Loc

) in the User Input Function parameter (Module 1).

Two programming modes are available. Full Programming mode allows all 

parameters to be viewed and modified. Quick Programming mode permits only 

the Setpoint values to be modified, but allows direct access to these values 

without having to enter Full Programming mode.

Programming a Security Code other than 0, requires this code to be entered 

at the 

CodE

 prompt in order to access Full Programming mode. Depending on the 

code value, Quick Programming may be accessible before the 

CodE

 prompt 

appears (see chart).

PROGRAMMING SECURITY CODE

000 

to

 999

USER INPUT 

FUNCTION

USER INPUT 

STATE

SECURITY 

CODE

MODE WHEN “SEL” 

BUTTON IS PRESSED

FULL PROGRAMMING 

MODE ACCESS

0

Full Programming

Immediate Access

not 

P-Loc

______

1-99

Quick Programming

100-999

CodE

 prompt

With correct code entry 

at 

CodE

 prompt *

0

Programming Lock

No Access

Active

1-99

Quick Programming

No Access

P-Loc

100-999

CodE

 prompt

With correct code entry 

at 

CodE

 prompt *

Not Active

0-999

Full Programming

Immediate Access

* Entering Code 222 allows access regardless of security code.

5.3  Module 3 - d

iSplay

 

and

 f

ront

 p

anel

 B

utton

  

 

 

 

 

 

 

 

 

p

araMeterS

 (

3-dSP

)

SEL

Pro

Front Panel 

Display 

Select Enable

Display 

Update Time

Front Panel 

Reset Enable

Programming 

Security Code

Display 

Scroll 

Enable

Display 

Color

Backlight Unit Only

3-dSP

dSP-t

SEL

rSt

ScroL

COLOr

CodE

Display 

Intensity 

Level

d-LEV

PARAMETER MENU

The 

yES

 selection allows the 

SEL

 button to toggle through the enabled 

displays.

FRONT PANEL DISPLAY SELECT ENABLE (SEL)

This selection allows the 

RST

 

button to reset the selected value(s).

FRONT PANEL RESET ENABLE (RST)

The 

yES

 selection allows the display to automatically scroll through the 

enabled displays. The scroll rate is every 4 seconds.

DISPLAY SCROLL ENABLE

NO

yES

dSP

NO
HI

LO
HI-LO

NO

yES

Enter the desired display color, red or green. This parameter is active for 

backlight units only.

DISPLAY COLOR (BACKLIGHT UNIT ONLY)

6rn

rEd

Enter the desired Display Intensity Level (1-5). The display will actively dim 

or brighten as levels are changed. This parameter is active for backlight units only.

DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)

to

 5

1

dSP-t

yES

SEL

dSP

rSt

NO

ScroL

rEd

COLOr

5

d-LEV

000

CodE

DISPLAY UPDATE TIME

This parameter sets the display update time in seconds.

1

0.5

2

seconds

After Quick 

Programming with 

correct code entry at 

CodE

 prompt *

Содержание CUB 5TC-K

Страница 1: ...ure personal safety and to prevent damage to either the device or equipment connected to it Do not use these products to replace proper safety interlocking No software based device or any other solid...

Страница 2: ...nstallation Guidelines for additional information 8 MEMORY Nonvolatile E2PROM memory retains all programming parameters and max min values when power is removed 9 CONNECTIONS Wire clamping screw termi...

Страница 3: ...nstalling the Meter INSTALLATION The meter meets NEMA 4X IP65 requirements when properly installed The unit is intended to be mounted into an enclosed panel Prepare the panel cutout to the dimensions...

Страница 4: ...tive The following EMI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 Line Filters for input power cables Schaffner FN2010 1 07 Red Lion Co...

Страница 5: ...order to preserve the safety of the meter application the power input common and the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must b...

Страница 6: ...ges to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module...

Страница 7: ...SELECTION VOLt tc n N K tc b tc S tc K B S J tc j E tc E T tc t 0 OFSEt DISPLAY OFFSET VALUE The temperature display can be corrected with an offset value This can be used to compensate for probe erro...

Страница 8: ...it will display CAL NO 3 Press the RST button to select INP 4 Press the SEL button Display reads 0 0u 5 With the voltage source set to zero press SEL Display reads CALC for about eight seconds 6 When...

Страница 9: ...rogramming Immediate Access Entering Code 222 allows access regardless of security code 5 3 MODULE 3 Display and Front Panel Button Parameters 3 dSP SEL Pro Front Panel Display Select Enable Display U...

Страница 10: ...anced Hys LO bL OUTPUT STATE OFF ON Hys SP SP Hys OFF TRIGGER POINTS High Acting Unbalanced Hys HI Ub 2 HYS n HYSTERESIS VALUE 1 to 59999 Enter desired hysteresis value See Setpoint Output Figures for...

Страница 11: ...the output operates normally per the Setpoint Action and OutputReset Action NO Stb n STANDBY OPERATION YES NO When the user input or RST button is activated momentary action the corresponding on outpu...

Страница 12: ...gramming Security Code CodE Display Decimal Point Thermocouple Type tYPE Cold Junction Compensation CJC 1 INP Temperature Scale SCALE dECPt USrIN User Input Function Filter Setting Display Offset Valu...

Отзывы: