Enter the probe burn-out action. In the event of a temperature probe failure 

(open), the output can be programmed to be on or off.

PROBE BURN-OUT ACTION

ON

OFF

This parameter enables the backlight CUB5 to switch the backlight color when 

the output state changes. This parameter is only active for the backlight version.

CHANGE DISPLAY COLOR w/OUTPUT STATE

YES

NO

SEL

Data Bit

Baud Rate

Parity Bit

Print 

Options

Meter 

Address

Abbreviated 

Printing

5-SEr

bAUd

dAtA

PAr

Addr

Abbr

OPt

Pro

The Serial Setup Parameters are only active when one of the optional serial communications/programming cards is installed in the meter. 

Refer to the CUB5COM bulletin for details and setup for the CUB5 RS232 or RS485 serial communications.

Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements.

PARAMETER MENU

This parameter enables the 

RST

 button or user input to reset the output when 

the display is reset.

Note: For this parameter to operate, the 

RST

 button or User Input being used 

must be set to 

dSP

 and the Input value must be displayed. If these conditions are 

not met, the output will not reset.

YES

rEn-n

OUTPUT RESET WITH DISPLAY RESET

YES

NO

When 

YES

, the output is disabled (after a power up) until the  trigger point is 

crossed. Once the output is on, the output operates normally per the Setpoint 

Action and OutputReset Action.

NO

Stb-n

STANDBY OPERATION

YES

NO

When the user input or 

RST

 button is activated (momentary action), the 

corresponding “on” output is reset immediately and remains off until the 

trigger point is crossed again. (Previously latched alarms will be off if power 

up Display Value is lower than setpoint value.)

L-dLY

 = Latch with delay reset action; This action latches the output on at the 

trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch 

means that the output can only be turned off by the front panel 

RST

 button 

or user input manual reset, serial reset command or meter power cycle. When 

the user input or 

RST

 button is activated (momentary action), the meter 

delays the event until the corresponding “on” output crosses the trigger off 

point. (Previously latched outputs are off if power up Display Value is lower 

than setpoint value. During a power cycle, the meter erases a previous 

L-dLY

 

reset if it is not activated at power up.)

OUTPUT

STATE

OFF

ON

Hys

SP

Auto

OFF

ON

OFF

OFF

ON

OFF

ON

OFF

OFF

ON

OFF

ON

OFF

MANUAL

RESET

LAtCH

L-dLY

SP - Hys

(       )

(         )

(         )

{

Setpoint Output Reset Actions

NO

ChC-n

OFF

brn-n

RED LION CONTROLS TECHNICAL SUPPORT

If for any reason you have trouble operating, connecting, or simply have questions concerning your new product, 

contact Red Lion’s technical support.

Support: 

support.redlion.net

Website: 

www.redlion.net

Inside US: +1 (877) 432-9908

Outside US: +1 (717) 767-6511
Red Lion Controls, Inc.

20 Willow Springs Circle York, PA 17406

Содержание CUB 5TC-K

Страница 1: ...ure personal safety and to prevent damage to either the device or equipment connected to it Do not use these products to replace proper safety interlocking No software based device or any other solid...

Страница 2: ...nstallation Guidelines for additional information 8 MEMORY Nonvolatile E2PROM memory retains all programming parameters and max min values when power is removed 9 CONNECTIONS Wire clamping screw termi...

Страница 3: ...nstalling the Meter INSTALLATION The meter meets NEMA 4X IP65 requirements when properly installed The unit is intended to be mounted into an enclosed panel Prepare the panel cutout to the dimensions...

Страница 4: ...tive The following EMI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 Line Filters for input power cables Schaffner FN2010 1 07 Red Lion Co...

Страница 5: ...order to preserve the safety of the meter application the power input common and the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must b...

Страница 6: ...ges to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module...

Страница 7: ...SELECTION VOLt tc n N K tc b tc S tc K B S J tc j E tc E T tc t 0 OFSEt DISPLAY OFFSET VALUE The temperature display can be corrected with an offset value This can be used to compensate for probe erro...

Страница 8: ...it will display CAL NO 3 Press the RST button to select INP 4 Press the SEL button Display reads 0 0u 5 With the voltage source set to zero press SEL Display reads CALC for about eight seconds 6 When...

Страница 9: ...rogramming Immediate Access Entering Code 222 allows access regardless of security code 5 3 MODULE 3 Display and Front Panel Button Parameters 3 dSP SEL Pro Front Panel Display Select Enable Display U...

Страница 10: ...anced Hys LO bL OUTPUT STATE OFF ON Hys SP SP Hys OFF TRIGGER POINTS High Acting Unbalanced Hys HI Ub 2 HYS n HYSTERESIS VALUE 1 to 59999 Enter desired hysteresis value See Setpoint Output Figures for...

Страница 11: ...the output operates normally per the Setpoint Action and OutputReset Action NO Stb n STANDBY OPERATION YES NO When the user input or RST button is activated momentary action the corresponding on outpu...

Страница 12: ...gramming Security Code CodE Display Decimal Point Thermocouple Type tYPE Cold Junction Compensation CJC 1 INP Temperature Scale SCALE dECPt USrIN User Input Function Filter Setting Display Offset Valu...

Отзывы: