6

4.0 r

evieWinG

 

the

 f

ront

 B

uttonS

 

and

 d

iSplay

SEL

RST

PROGRAMMING MODE ENTRY (SEL BUTTON)

It is recommended that all programming changes be made off line, or before 

installation. The meter normally operates in the Display Mode. No parameters 

can be programmed in this mode. The Programming Mode is entered by 

pressing and holding the 

SEL

 button. If it is not accessible then it is locked by 

either a security code, or a hardware lock.

MODULE ENTRY (SEL & RST BUTTONS)

The Programming Menu is organized into separate modules. These modules 

group together parameters that are related in function. The display will alternate 

between 

Pro

 and the present module. The 

RST 

button is used to select the desired 

module. The displayed module is entered by pressing the 

SEL

 button.

MODULE MENU (SEL BUTTON)

Each module has a separate module menu (which is shown at the start of each 

module discussion). The 

SEL

 

button is pressed to advance to a particular 

parameter to be changed, without changing the programming of preceding 

parameters. After completing a module, the display will return to 

Pro NO

Programming may continue by accessing additional modules.

SELECTION / VALUE ENTRY

For each parameter, the display alternates between the present parameter and 

the selections/value for that parameter. The 

RST

 button is used to move through 

the selections/values for that parameter. Pressing the 

SEL

 button, stores and 

activates the displayed selection/value. This also advances the meter to the next 

parameter.

For numeric values, press the 

RST

 button to access the value. The right hand 

most digit will begin to flash. Pressing the 

RST

 button again increments the digit 

by one or the user can hold the 

RST

 button and the digit will automatically 

scroll. The 

SEL

 button will advance to the next digit. Pressing and holding the 

SEL

 button will enter the value and move to the next parameter.

PROGRAMMING MODE EXIT (SEL BUTTON)

The Programming Mode is exited by pressing the 

SEL

 button with 

Pro NO

 

displayed. This will commit any stored parameter changes to memory and 

return the meter to the Display Mode. (If power loss occurs before returning to 

the Display Mode, verify recent parameter changes.)

PROGRAMMING TIPS

It is recommended to start with Module 1 and proceed through each module 

in sequence. When programming is complete, it is recommended to record the 

parameter programming and lock out parameter programming with the user 

input or programming security code.

FACTORY SETTINGS

Factory Settings may be completely restored in Module 2. This is useful 

when encountering programming problems.

Pressing both the 

SEL

 and the 

RST

 button on power-up will also load the 

factory settings and display 

rESEt

. This allows operation in the event of a 

memory failure or corrupted data.

ALTERNATING SELECTION DISPLAY

In the explanation of the modules, the following dual display with arrows will 

appear. This is used to illustrate the display alternating between the parameter 

on top and the parameter’s Factory Setting on the bottom. In most cases, 

selections and values for the parameter will be listed on the right.

5.0 p

roGraMMinG

 

the

 M

eter

Parameters

Output

Setpoint

Parameters

Signal Input

Pro

DISPLAY

MODE

Panel Key

Function

Parameters

3-dSP

Parameters

Display and Front

NO

SEL

RST

SEL

SEL

SEL

SEL

2-SEC

1-INP

4-SPt

5-SEr

SEL

Serial

Setup

Parameters

Secondary

OVERVIEW

PROGRAMMING MENU

Indicates Program Mode Alternating Display

Factory Settings are shown.

Parameter 

Selection/Value

BUTTON DISPLAY MODE OPERATION

ENTERING PROGRAM MODE

PROGRAMMING MODE OPERATION

SEL

Index display through enabled values

Press and hold for 2 seconds to activate

Store selected parameter and index to next parameter

RST

Resets values (MIN / MAX) or outputs

Advances through the program menu 

Increments selected parameter value or selection

OPERATING MODE DISPLAY DESIGNATORS

MAX

 

- Maximum display capture value

MIN

 

- Minimum display capture value

“1” - To the right of the display indicates setpoint 1 output activated.

“2” - To the right of the display indicates setpoint 2 output activated.

Pressing the 

SEL

 button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between 

the enabled display values. 

N0

USrIN

Содержание CUB 5TC-K

Страница 1: ...ure personal safety and to prevent damage to either the device or equipment connected to it Do not use these products to replace proper safety interlocking No software based device or any other solid...

Страница 2: ...nstallation Guidelines for additional information 8 MEMORY Nonvolatile E2PROM memory retains all programming parameters and max min values when power is removed 9 CONNECTIONS Wire clamping screw termi...

Страница 3: ...nstalling the Meter INSTALLATION The meter meets NEMA 4X IP65 requirements when properly installed The unit is intended to be mounted into an enclosed panel Prepare the panel cutout to the dimensions...

Страница 4: ...tive The following EMI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 Line Filters for input power cables Schaffner FN2010 1 07 Red Lion Co...

Страница 5: ...order to preserve the safety of the meter application the power input common and the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must b...

Страница 6: ...ges to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module...

Страница 7: ...SELECTION VOLt tc n N K tc b tc S tc K B S J tc j E tc E T tc t 0 OFSEt DISPLAY OFFSET VALUE The temperature display can be corrected with an offset value This can be used to compensate for probe erro...

Страница 8: ...it will display CAL NO 3 Press the RST button to select INP 4 Press the SEL button Display reads 0 0u 5 With the voltage source set to zero press SEL Display reads CALC for about eight seconds 6 When...

Страница 9: ...rogramming Immediate Access Entering Code 222 allows access regardless of security code 5 3 MODULE 3 Display and Front Panel Button Parameters 3 dSP SEL Pro Front Panel Display Select Enable Display U...

Страница 10: ...anced Hys LO bL OUTPUT STATE OFF ON Hys SP SP Hys OFF TRIGGER POINTS High Acting Unbalanced Hys HI Ub 2 HYS n HYSTERESIS VALUE 1 to 59999 Enter desired hysteresis value See Setpoint Output Figures for...

Страница 11: ...the output operates normally per the Setpoint Action and OutputReset Action NO Stb n STANDBY OPERATION YES NO When the user input or RST button is activated momentary action the corresponding on outpu...

Страница 12: ...gramming Security Code CodE Display Decimal Point Thermocouple Type tYPE Cold Junction Compensation CJC 1 INP Temperature Scale SCALE dECPt USrIN User Input Function Filter Setting Display Offset Valu...

Отзывы: