Service And Repair
Installing a Siphon Assembly
28
8.
Replace the protective plug over the service screw, and fully thread into place to ensure a good seal.
9.
Turn the air purge screw 2 - 3 turns counterclockwise (see Figure 26).
The air purge screw is retained by a hitch pin to limit travel. Do not attempt to rotate
beyond 3 turns.
10. Turn the pump on and let it run for about 2 minutes to purge air from the manifold’s hydraulic cavities. While
the pump is still running, turn the air purge screw clockwise until it is completely closed.
11. If applicable, open the ball valve down line from the pump.
Figure 27. Inserting Siphon Assembly Into Manifold
WARNING
rjp
u
mp
s
/fig
38
.ep
s
S
iphon port pl
u
g
u
pper o-ring
(-121 [1.049'' ID x 0.10
3
'' wide])
S
iphon
ass
em
b
ly
u
pper o-ring
s
(-121 [1.049'' ID x 0.10
3
'' wide])
S
iphon port pl
u
g lower o-ring
(-117 [0.799'' ID x 0.10
3
'' wide])
S
iphon
ass
em
b
ly lower o-ring
(-117 [0.799'' ID x 0.10
3
'' wide])