Installation
Installing the Pump
16
Figure 12. Locating Return Line Fitting On Packer
8.
Lay the siphon return line tubing beside the column pipe. Stop 1 - 3 inches (25 - 76 mm) above the discharge
head.
9.
Secure the siphon return line tubing to the column pipe with tie straps. Locate the tie straps approximately 6
inches (152 mm) from the manifold, 6 inches from the discharge head and in the middle of the tubing (see
Figure 13).
Do not overtighten tie straps as a pinched or flattened return line will restrict flow,
interfering with proper operation of siphon system.
FOR FIXED-LENGTH PUMPS, SKIP TO Step 14.
Figure 13. Attaching Return Line Tubing To Pump
10. Pull on the pigtail wires where they exit the packer wiring compartment. Snip pigtail wires approximately 8
inches (200 mm) beyond the top of the packer.
11. There will be six wires - three wires from the male connector installed in the packer’s housing and three-wires
from the UMP’s pigtail.
12. Strip insulation off all six wires 3/8 inch (10 mm).
rjpumps/fig33.eps
Siphon return line barbed fitting
2" discharge port
Power wiring compression
bushing
3/4” FNPT
UMP
NOTICE
rjpumps/fig30.eps
1 - 3" (25 - 76 mm)
6" (151mm)
1/2 Distance
1/2 Distance
Don't crimp tubing with tie straps
6" (151mm)