Red Jacket 344-001-5 Скачать руководство пользователя страница 12

4” Standard Pump Installation, Operation & Service Manual

Adjusting the Functional Element

9

Adjusting the Functional Element

DANGER! Always disconnect, lock out, and tag the power before starting to service the pump.

 

The functional element contained in this package is an adjustable model. All new functional elements are factory 
set at relief pressures of 11.5 – 16 psi (79 – 93 kPa) but can be adjusted to a maximum of approximately 30 psi 
(207 kPa) by turning down the pressure adjustment screw.

This adjustment feature allows the use of the Red Jacket Standard pump with electronic line leak detection 
systems that require higher relief pressures and enhances performance of electronic line leak detection systems 
where field conditions have necessitated minor adjustments to the relief pressure.

To Adjust the Relief Pressure

1.

Remove the cap (see Figure 6).

2.

Turn down the pressure adjustment screw (see Figure 6). Tightening the screw clockwise will increase the 
pressure. When the adjustment screw is fully down, the relief pressure is approximately 30 psi (207 kPa). Fully 
up will result in relief pressures between 0 – 3 psi (0 – 20 kPa).

3.

Lubricate the cap’s o-ring with petroleum jelly and replace cap by turning it until it contacts the functional 
element body. Hand tightening is sufficient as the o-ring completes the seal. 

There are two methods to verify the relief pressure setting:

a.The pressure reading can be taken from the control unit of an electronic line leak detection system if one is 

in operation. Observe the pressure that occurs after the pump turns off - this is the adjusted relief pressure.

b.Pressure may be observed using a gauge attached at the impact valve or the line test port at the pump. 

Observe the pressure that occurs after the pump turns off - this the adjusted relief pressure.

Figure 6.   Functional Element Cap And Pressure Adjustment Screw

WARNING!
When the adjustable functional element is installed, the pump/motor unit must operate at a minimum 
of 5 psi (34 kPa) greater than the relief (seating) pressure at which the functional element has been 
set. An improper pressure setting may cause mechanical damage and will void the warranty.

OFF

C

a

p

Pre

ssu

re

Adj

us

tment 

S

crew

Содержание 344-001-5

Страница 1: ...Installation Guide 4 AG Pump Service Kit Manual No A042 078 Revision E Part No 344 001 5...

Страница 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Страница 3: ...justing the Functional Element 9 To Adjust the Relief Pressure 9 Functional Element Parts List 11 Figures Figure 1 Electronic Line Leak Detector 4 Figure 2 Packer 4 Figure 3 Locating 7 Packer O Ring A...

Страница 4: ...ask someone who does WEAR EYE PROTECTION Wear eye protection when working with pressurized fuel lines or epoxy sealant to avoid possible eye injury WARNING This product operates in the highly combust...

Страница 5: ...Prevent Explosions and Fires Fuels and their vapors will explode or burn if ignited Spilled or leaking fuels cause vapors Even filling customer tanks will cause potentially dangerous vapors in the vic...

Страница 6: ...A OSHA regulations and federal state and local fire codes and other applicable local regulations The selection of any Veeder Root product must be based upon physical specifications and limitations and...

Страница 7: ...the pump close it 2 If an electronic line leak detection transducer is installed it must be removed from the leak detector port following instructions in the appropriate Line Leak installation manual...

Страница 8: ...ld remove the old quad seal from the base of the packer under the line leak port see Figure 3 9 Clean the seating surface and the sealing surface of the quad seal 10 Lubricate the quad seal with petro...

Страница 9: ...anifold Discharge Port 7 O Ring Packer Seal 7 O Ring Packer Seal Manifold Functional Element Functional Element Packer Packer Leak Detector Port Plug or Line Leak Detector Leak Detector Port Plug or L...

Страница 10: ...lb 40 61 N m NOTE suggested tools non sparking include a 3 4 wrench pipe wrench 1 4 Allen wrench 9 16 wrench screw driver wire cutter and wire stripper 20 If applicable open ball valve down line from...

Страница 11: ...gure 5 Functional Element 5 Carefully lift the functional element and remove it from the packer The old check valve and spring will be resting inside the packer NOTE The check valve and spring should...

Страница 12: ...s fully down the relief pressure is approximately 30 psi 207 kPa Fully up will result in relief pressures between 0 3 psi 0 20 kPa 3 Lubricate the cap s o ring with petroleum jelly and replace cap by...

Страница 13: ...with the dispenser furthest from the pump and work toward the pump 5 Pump start up is now complete Table 1 Approximate Pressures At Shut Off Pump Approximate Shut Off Pressure AGUMP33R1 UMP33R1 25 ps...

Страница 14: ...Casting 2 017 526 1 Diaphragm 3 066 883 1 Poppet 4 072 641 1 O Ring 41 64 x 5 64 5 076 421 3 Adjustment Screw 6 012 956 3 Cap 7 080 767 1 Spring 8 066 620 1 Plug 9 060 332 1 Seal 10 012 965 3 Top Cast...

Страница 15: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: