background image

14

REC Installation Manual - REC Alpha 72 Series  - IEC 61215 /61730
Rev A - 02.20 

Ref: NE-06-23

ANNEX 1: INSTALLATIONS ON WATER PLATFORMS

This section is applicable to the following products only:

•  REC Alpha 72 Series 

The above named REC solar panels may be installed on water platform-type mounting systems (note that the certification testing of solar panels 

does not include testing on these types of systems). When installing any of the above named REC solar panels on fixed position (e.g., anchored) water 

platforms, for example, floating pontoons, follow the instructions below specific to such applications. Failure to do so will invalidate the warranty.

INSTALLATION ENVIRONMENT
i)  Installation site

•  REC solar panels may only be installed on closed bodies of fresh water where water salinity does not exceed 25 mS/cm at 25°C (15 PSU). This 

specifically excludes mounting on sea and ocean applications.

•  The maximum permitted wave height must not exceed 1 m from the crest to the trough of the wave.

ii)  Floating platforms

•  When using a floating platform, follow the manufacturer’s instructions regarding installation, maintenance, inspection and cleaning at all times.

iii)  Minimum installation height

•  The minimum installation height of REC solar panels on floating platform systems is 15 cm and is defined as the height between the water 

surface and the lowest edge/part of the panel during normal operation. This will help to shield the panel from direct water spray.

INSTALLATION INSTRUCTIONS
i)  System installation

•  All cables used for the installation must have sufficient length and slack to prevent damage due to water level changes and wave motions.

ii)  Mounting panels

•  Installation of REC solar panels must be in accordance with the aforementioned standard mounting instructions.
•  The junction box should be oriented as far as possible from the water surface according to system design and the junction box, cables and 

connectors must be protected from direct water splash.

•  The installation must allow for sufficient spacing between individual panels, in order to avoid all contact as caused by the natural movement 

and flexing of the floating structure.

iii)  Panel protection

•  In areas with high avian activity, additional bird repelling devices may be installed as long as they do not adversely affect system performance, e.g., 

shading or to the local environment etc.

•  If using lightning protection equipment on the floating installation, all relevant local regulations must be respected.

MAINTENANCE

•  Regularly inspect the installation to ensure all panels are securely mounted.

SAFETY

•  Immediately disconnect the system if the installation or the floating platform exhibits deviation from standard operating conditions.
•  In the event of the floating platform being submerged, disconnect the DC connection at the inverter immediately. Do not attempt to salvage 

panels when sunlight is present.

NOTE

For all installations on water platforms, first advise REC before the start of installation in case of any site specific instructions or constraints.

i

NOTE

Negative system grounding is required for REC solar panels installed on a floating platform.

i

NOTE

For installations with high avian activity, system cleaning may be required at more frequent intervals to reduce shading of panels caused by bird defecation.

i

Содержание Alpha 72 Series

Страница 1: ...rec Alph 72 SERIES INSTALLATION MANUAL FOR ALL REC ALPHA 72 SOLAR PANELS CERTIFIED ACCORDINGTO IEC 61215 IEC 61730 STANDARDS...

Страница 2: ...AGEMENT 11 PANEL MAINTENANCE 12 RECYCLING 12 DISPOSAL OF OLD ELECTRICAL AND ELECTRONIC EQUIPMENT 12 PANEL CHARACTERISTICS 13 Technical Properties REC Alpha 72 Series 13 ANNEX 1 INSTALLATIONS ON WATER...

Страница 3: ...ore installers are responsible for the following Only qualified personnel must perform work on photovoltaic systems such as installation commissioning maintenance and repairs Be sure to follow the saf...

Страница 4: ...erved during handling to avoid the risk of sparking fire hazards burns and lethal electric shocks Exercise extreme caution when wiring panels and look out for damaged or dirty cables etc Never insert...

Страница 5: ...voiddamageordegradationtothepackagingorpanelcomponents pallets and panels must be stored in a controlled environment ideally internal where it is protected from the elements e g rain dust and direct s...

Страница 6: ...bundled together so loops are as small as possible String configurations must be checked before commissioning If open circuit voltage Voc and short circuit current Isc deviate from specification this...

Страница 7: ...mp grip length and the central point of the fixation e g the bolt is fully within the required clamping zone as indicated on the following pages CLAMP SPECIFICATIONS Clamp installation must be carried...

Страница 8: ...g 3 Clamping zones for panels with rails parallel to short side CAUTION The minimum grip length of each clamp and its center point must be fully located in the same color zone to be rated to that load...

Страница 9: ...eledgeofeachpanelmustbesupportedbytworails figs 2a 2b ofaluminiumorgalvanized steelsuitablefortheapplicationandappropriateforthelocalenvironment Observethefollowingprocedureswhenusingmountingholes The...

Страница 10: ...hown in fig 9 and can be further identified by the grounding symbol stamped in the frame next to it Check all applicable requirements before beginning installation Suitable grounding clips lugs or oth...

Страница 11: ...standards e g IEC 62852 or UL 6703 to ensure they are fit for purpose and safety Useofanychemicalsorlubricantsontheconnectorsorcontactsmayonlybecarriedoutinlinewiththeconnectormanufacturer sinstructio...

Страница 12: ...local guidelines and regulations By ensuring REC solar panels are disposed of correctly you will help prevent potential negative impact on the environment and human health The majority of the panel c...

Страница 13: ...ewithIEC62790 Connectors St ubliMC4Evo2 PV KBT4 EVO 2 PV KST4 EVO 2 4mm inaccordancewithIEC62852 IP68onlywhenconnected Cable 4 mm solar cable 1 2 m 1 3 m in accordance with EN 50618 Dimensions 2063 x...

Страница 14: ...installation must have sufficient length and slack to prevent damage due to water level changes and wave motions ii Mounting panels Installation of REC solar panels must be in accordance with the afor...

Страница 15: ...r instructions to ensure optimum mounting of MLPE device and prevent any slippage during operation MLPE devices may also be attached to the mounting construction In such cases refer to the instruction...

Страница 16: ...nformity of the product with the requirements of the above mentioned EC Directive and its conformity with the safety requirements of the EC Low Voltage Directive 2014 35 EU DIN EN 61215 VDE 0126 31 20...

Страница 17: ...RECInstallationManual RECAlpha72Series IEC61215 61730 Rev A 02 20 Ref NE 06 23 17 DOCUMENTHISTORY Date Revision Reason 02 2020 A First release...

Страница 18: ...RECSOLARPTE LTD 20TUASSOUTHAVENUE14 SINGAPORE637312 SINGAPORE Tel 6564959228 Mail post recgroup com www recgroup com 18 RECInstallationManual RECAlpha72Series IEC61215 61730 Rev A 02 20 Ref NE 06 23...

Отзывы: