background image

REC Installation Manual - REC Alpha 72 Series  - IEC 61215 /61730
Rev A - 02.20 

Ref: NE-06-23

11

CONNECTIONS AND CONNECTORS

The connector type(s) used on REC panels are indicated in the product specifications at the rear of this manual. The connector IP rating is only valid 

when correctly connected. All connectors and cables must be secure and tight as well as electrically and mechanically sound. UV-resistant cables 

and connectors approved for outdoor use must be used. Conductor gauge must be chosen to ensure DC power losses (voltage drop) are kept to a 

minimum (<1%).

Observe all local regulations when selecting cables.

•  For string connections, use minimum 4 mm

2

 or copper wires insulated for a maximum operating temperature of 90°C,

•  Avoid exposing cables to direct sunlight and permanent tension.

In order to ensure durable and safe connections between panels and BOS equipment, the following instructions must be followed in order to protect 

the electrical connections from the elements. 

CONNECTORS

To ensure connector compatibility and reduce the potential for damage to the panels and the wider installation, the connectors used on the REC 

Alpha 72 Series are detailed in the Panel Characteristics at the rear of this manual. REC only permits the mating of factory-installed connectors to 

connectors of the same manufacturer, type, and system rating as shown in the table below (fig. 8):

Fig. 8:  Connector mating matrix

Connector 1

+

Connector 2

Permitted?

REC Factory-Installed

+

Stäubli MC4 Evo-2

On 1500V Systems

REC Factory-Installed

+

Stäubli MC4

On 1000V Systems 

only

REC Factory-Installed

+

REC Factory-Installed 

REC Factory-Installed

+

Any other connector

CUTTING THE CABLES 

The cutting of cables is only permitted in order to replace a factory-installed connector with another brand of connector to ensure ‘like-for-like’ 

mating when connected to a non-REC external device. All other changes are prohibited and will invalidate the REC warranty. 

•  The connector replacement procedure must be carried out correctly and according to the replacement connector manufacturer’s instructions. 
•  The selected replacement connector must also fulfil all relevant technical specifications and be certified according to applicable standards 

(e.g., IEC 62852 or UL 6703) to ensure they are fit for purpose and safety. 

•  Use of any chemicals or lubricants on the connectors or contacts may only be carried out in line with the connector manufacturer’s instructions.

The REC warranty does not extend to cover any fault traceable to the replaced connectors. Any other modification to the panel is prohibited, 

including the opening of the junction box, unless explicitly authorized by REC. Doing so will invalidate the warranty.

CABLE MANAGEMENT

To ensure a long life span of the cables and reduce the potential for damage to the cables, follow the instructions below:

•  To prevent stress on the junction box casing, ensure the cable exits the junction box in a straight line before any bend in the cable,
•  The cables must have a minimum bending radius of 30 mm to avoid damage to the insulation (fig. 9),
•  Ensure cables do not hang loose where they may be damaged through friction or stress, e.g., caused by mechanical abrasion or grazing animals,
•  Protect connectors from falling or dropping water by locating them directly beneath a panel,
•  Cables must be firmly secured to the structure, without over-tightening, as this can deform the cable insulation using UV-resistant cables,
•  When securing the connector, place it so that it has with sufficient air circulation all around. This allows the connector to dry effectively and 

avoids the risk of damage or degradation of the connection,

•  Secure the cable either side of the connectors to ensure no stress is exerted on the connector casing or cable entry,
•  To enable correct cooling and drying of the connectors, do not add extra protection to the connector, e.g., heat shrink, grease or tape.

More detailed information is given in the 

Guide to Best Practice - Connections and Connectors which can be found via the REC online Download 

Center (www.recgroup.com/downloads)

NOTE

Some countries and/or regions have specific regulations regarding the mating of connectors. Installers are responsible for ensuring the compliancy of the 

system with such local regulations.

i

DANGER - 

Electrical shock

Safety is paramount when working with electrical connectors.

•  Ensure that any installation work is not carried out on live or load-carrying parts. 
•  Connections must not be disconnected under load and the system must be isolated from the grid before carrying out any maintenance or 

repair work.

< 60 mm >

< 30 mm 

>

Fig. 9:   Minimum cable bend radius

Содержание Alpha 72 Series

Страница 1: ...rec Alph 72 SERIES INSTALLATION MANUAL FOR ALL REC ALPHA 72 SOLAR PANELS CERTIFIED ACCORDINGTO IEC 61215 IEC 61730 STANDARDS...

Страница 2: ...AGEMENT 11 PANEL MAINTENANCE 12 RECYCLING 12 DISPOSAL OF OLD ELECTRICAL AND ELECTRONIC EQUIPMENT 12 PANEL CHARACTERISTICS 13 Technical Properties REC Alpha 72 Series 13 ANNEX 1 INSTALLATIONS ON WATER...

Страница 3: ...ore installers are responsible for the following Only qualified personnel must perform work on photovoltaic systems such as installation commissioning maintenance and repairs Be sure to follow the saf...

Страница 4: ...erved during handling to avoid the risk of sparking fire hazards burns and lethal electric shocks Exercise extreme caution when wiring panels and look out for damaged or dirty cables etc Never insert...

Страница 5: ...voiddamageordegradationtothepackagingorpanelcomponents pallets and panels must be stored in a controlled environment ideally internal where it is protected from the elements e g rain dust and direct s...

Страница 6: ...bundled together so loops are as small as possible String configurations must be checked before commissioning If open circuit voltage Voc and short circuit current Isc deviate from specification this...

Страница 7: ...mp grip length and the central point of the fixation e g the bolt is fully within the required clamping zone as indicated on the following pages CLAMP SPECIFICATIONS Clamp installation must be carried...

Страница 8: ...g 3 Clamping zones for panels with rails parallel to short side CAUTION The minimum grip length of each clamp and its center point must be fully located in the same color zone to be rated to that load...

Страница 9: ...eledgeofeachpanelmustbesupportedbytworails figs 2a 2b ofaluminiumorgalvanized steelsuitablefortheapplicationandappropriateforthelocalenvironment Observethefollowingprocedureswhenusingmountingholes The...

Страница 10: ...hown in fig 9 and can be further identified by the grounding symbol stamped in the frame next to it Check all applicable requirements before beginning installation Suitable grounding clips lugs or oth...

Страница 11: ...standards e g IEC 62852 or UL 6703 to ensure they are fit for purpose and safety Useofanychemicalsorlubricantsontheconnectorsorcontactsmayonlybecarriedoutinlinewiththeconnectormanufacturer sinstructio...

Страница 12: ...local guidelines and regulations By ensuring REC solar panels are disposed of correctly you will help prevent potential negative impact on the environment and human health The majority of the panel c...

Страница 13: ...ewithIEC62790 Connectors St ubliMC4Evo2 PV KBT4 EVO 2 PV KST4 EVO 2 4mm inaccordancewithIEC62852 IP68onlywhenconnected Cable 4 mm solar cable 1 2 m 1 3 m in accordance with EN 50618 Dimensions 2063 x...

Страница 14: ...installation must have sufficient length and slack to prevent damage due to water level changes and wave motions ii Mounting panels Installation of REC solar panels must be in accordance with the afor...

Страница 15: ...r instructions to ensure optimum mounting of MLPE device and prevent any slippage during operation MLPE devices may also be attached to the mounting construction In such cases refer to the instruction...

Страница 16: ...nformity of the product with the requirements of the above mentioned EC Directive and its conformity with the safety requirements of the EC Low Voltage Directive 2014 35 EU DIN EN 61215 VDE 0126 31 20...

Страница 17: ...RECInstallationManual RECAlpha72Series IEC61215 61730 Rev A 02 20 Ref NE 06 23 17 DOCUMENTHISTORY Date Revision Reason 02 2020 A First release...

Страница 18: ...RECSOLARPTE LTD 20TUASSOUTHAVENUE14 SINGAPORE637312 SINGAPORE Tel 6564959228 Mail post recgroup com www recgroup com 18 RECInstallationManual RECAlpha72Series IEC61215 61730 Rev A 02 20 Ref NE 06 23...

Отзывы: