SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad

Installation Instructions

Product Summary

The ITI

®

 SuperBus 2000 2 x 20 VFD (vacuum fluorescent 

display) Alphanumeric Touchpad gives you complete on-
site system programming and operation control of a com-
patible security system (see the section “Specifications”).

A two-line, 40-character display provides visual system 
status messages. The display identifies any programmed 
location, allowing the user to determine where an alarm, 
trouble, or open-sensor condition exists. 

Other features include:

Touchpad buttons that light up after the first button 
press and remain lit until about 15 seconds after the last 
button press.

Adjustable display brightness.

Built-in hardwire input (can be supervised with EOL 
resistor in SuperBus 2000 panels).

Built-in door, which covers right-side buttons (60-810 
only).

SuperBus 2000 Panels 

vs. 

SuperBus Panels

SuperBus 2000 panels assign module unit numbers 
automatically when the panel is powered up. This 
eliminates manually setting unit numbers and the chance of 
identical unit number conflicts.

SuperBus 2000 Panels

Advent

Concord (software versions 2.0 and newer)

Concord Express

SuperBus panels communicate with SuperBus 2000 
modules but require the module unit number to be set 
manually. Touchpads automatically default to unit number 
001.

SuperBus Panels

UltraGard

Concord (software versions 1.0–1.6)

Installation Guidelines

For the maximum number of bus devices and 
touchpads per panel see Table 1.

Do not exceed the total panel output power when using 
panel power for bus devices, touchpads, and hardwired 
sensors that require it (see specific panel Installation 
Instructions
).

Maximum current draw from the touchpad is 120 mA.

Minimum current draw from the touchpad when the 
panel is operating only on backup battery is 15 mA.

Mount the touchpad in an environmentally controlled 
area (32° to 140°F) (0° to 60°C).

When using the optional touchpad hardwire input, use 
only shielded wire (22-gauge or larger), and do not 
exceed the maximum wire length limits in Table 2 
between the touchpad and detection device.

Note

Shield wire must be connected to earth ground.

When mounting the touchpad back-plate, allow a 1-
inch clearance on all sides since the touchpad is larger 
than the back-plate.

Use 4-conductor, 22-gauge or larger stranded wire from 
the touchpad to the control panel.

Follow the wire length limits outlined in the specific 
panel Installation Instructions between the touchpad 
and control panel.

Table 1: Maximum Bus Devices Per Panel

Panel

Maximum Bus 

Devices

UltraGard

8

Concord

16

Advent

62

Concord Express

4

Table 2: Hardwire Input Wire Length Limits

Gauge

Max. Wire 

Length

18 (shielded)

1000 Feet

22 (shielded)

350 Feet

 

  

Document Number: 466-1633 Rev. B
September 2000

ITI Part No. 60-804 & 60-810

Содержание 60-804-04 - Concord LCD/VFD Alphanumeric SuperBus Keypad

Страница 1: ...cally default to unit number 001 SuperBus Panels UltraGard Concord software versions 1 0 1 6 Installation Guidelines For the maximum number of bus devices and touchpads per panel see Table 1 Do not ex...

Страница 2: ...hors 4 Secure the back plate to the wall with included screws 5 Cut a hole in the wall where the wire access hole was marked to pull your cable through Figure 1 Touchpad Mounting Slots To mount the to...

Страница 3: ...tch must be unsupervised and a resistor must not be used Note The optional touchpad hardwire input must be added to panel memory See the Concord Concord Express panel Installation Instructions for set...

Страница 4: ...and make sure it is working properly before connecting additional touchpads Whenever possible such as in new installations assign alphanumeric touchpad unit numbers before beginning all other panel p...

Страница 5: ...at steps 11 through 16 for any other new alphanumeric touchpads Be sure to disconnect each touchpad after assigning its unit number 17 After assigning unit numbers to all the new touchpads connect eac...

Страница 6: ...ystem status Note If after pressing the touchpad does not display the current system status see Troubleshooting Powering Up Advent Panels New Installations 1 Verify that all wiring between the panel a...

Страница 7: ...nd no beeps when buttons are pressed 1 Check for correct wiring connec tions at the touchpad and panel terminals 2 Make sure the panel battery is connected correctly and that the panel transformer is...

Страница 8: ...ce with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interfer ence in which case users wil...

Отзывы: