SenSmart 3000 User's Manual
Document: UM-1003
Revision Level B
7
sufficient length to allow access to the back of the display assembly where 2 position TB1 is
located. Route the receiver wires through the conduit entry and connect to TB1. Steering diodes
in the SenSmart 2000 2-wire 4-20mA output automatically correct for polarity so positive and
negative are interchangeable. Reassemble the SenSmart 2000. Follow the procedures and
recommendations in the receiver manual to complete the installation. Be sure the SenSmart
2000 enclosure and conduit are properly grounded. Apply loop power by appropriately powering
the receiver device (DCS, PLC, Controller, etc) and the SenSmart 2000 should function. Proceed
to section-3.
Figure 2-4: 10-0232 Display / SenSmart 2000 2-Wire 4-20mA Assembly