Finned copper tube gas boilers & water heaters – Boiler manual

FTXLF-IOM-HN-1-110308 Copyright 2008 Mestek, Inc.

intake air option – Horizontal guidelines 

The maximum equivalent length for the horizontal intake air pipe is 

100 ft, 30.5 m. Each 90

o

 elbow and the intake air terminal are equal 

to 10 linear ft, 3.0 m of pipe. If horizontal runs exceed 5 ft, 1.5 m 

they must be supported at 3 ft, 0.9 m intervals with overhead hangers. 

The certified intake air terminal from RBI must be used, see Figure 1, 

page 8, Figure 2, page 8 and Figure 4, page 9.

GenerAL VentinG GUiDeLines

  The vent installation must be in accordance with 

Part  7,  Venting  of  Equipment,  of  the  National 

Fuel  Gas  Code,  ANSI  Z223.1/NFPA  54– 

latest revision or applicable provisions of the local  

building codes. Canadian installations must comply 

with  CAN/CGA  B149.1  or  .2  Installation  Code.  

Improper venting can result in excessive levels of 

carbon monoxide which can result in severe personal 

injury or death!

All vent systems must be fully supported by the building structure 

and not by the boiler/water heater. Appropriate thimbles and fire-

stops must be used where required.

  Common vent systems must be properly engineered 

and sized to provide a negative draft of   0.03 inch, 

0.8 mm to 0.1 inch, 2.5 mm W.C. at the flue outlet. 

Common positive pressure vent systems are not to be 

used. Improper installation can result in excessive levels 

of carbon monoxide which can cause severe personal 

injury or death!

  Common-vent systems — 

the  boiler  closest  to 

the vertical vent must be assigned as the master 

boiler and always fired First to ensure proper 
draft and reliable operation

. Consult the factory 

if any questions. Improper installation can result in 

excessive levels of carbon monoxide which can cause 

severe personal injury or death! 

eXistinG common Vent systems

If an existing boiler/water heater is removed from an existing com-

mon venting system, the common venting system may then be too 

large for the proper venting of the remaining appliances connected 

to it. At the time of removal of an existing boiler/water heater, the 

following steps shall be followed with each appliance remaining con-

nected to the common venting system placed in operation, while 

the other appliances remaining connected to the common venting 

system are not in operation.

Seal any unused openings in the common venting system. 

1. 

Visually inspect the venting system for proper size and horizontal 

2. 

pitch and determine there is no blockage or restriction, leakage, 

corrosion and other deficiencies which could cause an unsafe 

condition.

Insofar  as  is  practical,  close  all  building  doors  and  win-

3. 

dows  and  all  doors  between  the  space  in  which  the  ap-

pliances  remaining  connected  to  the  common  venting  

system are located and other spaces of the building. Turn  

on clothes dryers and any appliance not connected to the  

common  venting  system.  Turn  on  any  exhaust  fans,  such  

as range hoods and bathroom exhaust, so they will operate at 

maximum speed. Do not operate a summer exhaust fan for a 

boiler installation. Close fireplace dampers.

Place in operation the appliance being inspected. Follow the 

4. 

lighting instructions. Adjust thermostat so appliance will oper-

ate continuously.

Test for spillage at the draft hood relief opening after 5 minutes 

5. 

of main burner operation. Use the flame of a match or candle, or 

smoke from a cigarette, cigar or pipe.

After it has been determined that each appliance remaining 

6. 

connected to the common venting system properly vents when 

tested as outlined above, return doors, windows, exhaust fans, 

fireplace dampers and any other gas-burning appliance to their 

previous condition of use. 

Any improper operation of the common venting system should 

7. 

be corrected so the installation conforms with the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion 

of the common venting system, the common venting system 

should be resized to approach the minimum size as determined 

using the appropriate Tables in Appendix F in the National Fuel 

Gas Code, ANSI Z223.1/ NFPA 54 and or CAN/CGA B149 

Installation Codes.

Vent system options 

The flue products in the vent system may be cooled below their dew 

point and form condensate in the flue. The materials used for a Cat-

egory IV vent must be resistant to any corrosive damage from flue 

gas condensate. The flue from a Category IV vent system must have 

a condensate drain with provisions to properly collect and dispose 

of any condensate that may occur in the venting system. 

  Category IV vent/air piping lengths must not exceed 

100 equivalent feet. If longer runs are required,  use a 

Category II (negative pressure) vent system, specially 

engineered/designed to meet all applicable codes.

the Futera XLF may be vented the following ways:

 

option 1 — Direct Vent, positive pressure 

1. 

category iV (individual venting only) (page 7) 

Combustion air is piped from the outdoors to the blower inlet.  

Vent system is certified to UL 1738 for installations in the 

United States, ULC S636 for installations in Canada. Maxi-

mum equivalent length of vent and air piping must not exceed 

100 feet each.

option 2 — Vertical Vent, positive pressure 

2. 

category iV (individual venting only) (page 10) 

Combustion air is obtained from the space in which the unit is 

installed. Vent system is certified to UL 1738 for installations in 

the United States, ULC S636 for installations in Canada. Maxi-

mum equivalent length of vent piping must not exceed 100 feet.

Содержание Futera XLF 4000

Страница 1: ...boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property...

Страница 2: ...DP switch blocked air 10 inlet DP switch blocked flue 11 DP switch blower prov 12 ing DP switch pilot air prov 13 ing Ignitor 14 Pilot gas valve and pilot gas 15 pressure regulator Flow switch 16 Low...

Страница 3: ...ommonwealth of Massachusetts you MUST FOLLOW the additional instructions contained in RBI s instruc tion sheet MACODE 3 located in the back of this manual The owner should maintain a record of all ser...

Страница 4: ...it abledrainpanthat sadequatelydrainedmustbeinstalledunder the unit DO NOT place this boiler water heater in a location that 5 would restrict the introduction of combustion air into the unit or subjec...

Страница 5: ...ating the free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh s...

Страница 6: ...nd win 3 dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appl...

Страница 7: ...be joined and sealed in accordance with the vent system manufacturer s instructions Whenhorizontalventrunsexceed5ft 1 5mtheymustbesupported at 3 ft 0 9 m intervals with overhead hangers The vent syst...

Страница 8: ...nning horizontal combustion air and venting for single or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences...

Страница 9: ...ot exceed 100 feet each See Table 3 or 4 for min pipe diameters Locate exhaust terminal downwind from air intake to reduce potential for flue gas recirculation Failure to complycouldresultinsevere per...

Страница 10: ...ed and sized Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems Table 5 lists the equivalent breeching and flue sizes required for the boiler...

Страница 11: ...alent lengths up to100 feet maximum In this configuration the boiler water heater blower is used to push the flue products horizontally to the outdoors see Figure 7 The air for combustion is taken fro...

Страница 12: ...s than 33 input Category II chimney inspection sizing Masonry chimneys when used must be lined with a metal liner certified for Category IV venting A thorough inspection of the masonry chimney must be...

Страница 13: ...vent system is designed using accepted engineering practices and the design calculations prove there is no need for barometric dampers the barometric dampers may be omitted When required by ap plicab...

Страница 14: ...proved method If the unit must be shut off for any reason the electric 3 gas and water supplies MUST be shut off and the unit and its pump completely drained Improper outdoor installation of this unit...

Страница 15: ...15 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Futera XLF Piping Figure 9...

Страница 16: ...rmal expansion must be installed in the heating system An expansion tank must be installed close to the boiler on the suction side of the pump An air scoop and automatic air vent must also be installe...

Страница 17: ...2 requirements All boilers furnished with factory mounted 3 outlet water temperature gauge Boiler pump purging required Use termi 4 nals supplied All primary secondary piping systems re 5 quire a rem...

Страница 18: ...intain Inlet Temperature Above Dew Point T1 Temp Min 140o F 60o C Sealed Combustion 1 Turn heater on and open valves A B 2 After steady state operation if T1 is less than Temp Min slowly close valve B...

Страница 19: ...ghaFuteraXLF water heater is 260 GPM 16 4 L when equipped with coppertubes Thecupronickelheatexchangerallowsfor 315 GPM 19 9 L s See Table 9 page 20 RBI water heaters are designed to run scale free Du...

Страница 20: ...ditional precautions must be observed due to unusual characteristics of the local water supply Call the nearest RBI representative for details To properly size the pump a grain hardness andpHtestmustb...

Страница 21: ...th 30 total 6 90 4 o elbows full pipe size CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 5 The pH and water hardness must be measured before selecting heat exchanger and pump Consult the Heat Exch...

Страница 22: ...y piping has the capacity to meet the demand Figure16depictstheproperwaytoconnecttheboiler waterheater to the gas supply piping The manual shut off valve MUST be in stalled in the supply piping It sho...

Страница 23: ...Gate valve Gas cock 2 5 2 10 3 1 2 3 0 2 6 2 12 3 1 4 3 5 3 7 7 15 3 1 8 4 5 4 10 1 20 2 2 4 6 0 5 12 6 25 2 2 9 7 3 6 15 2 30 4 3 5 13 4 Equivalent lengths above are for threaded fittings Multiply v...

Страница 24: ...the heating system piping Close the make upwatervalveandcheckandcleanthestrainersandmake upwater pressure reducing valve Openthemake upwatervalveandadjustthesystempressureifnec essary The system shou...

Страница 25: ...loweroperatesatminimumignitionsetting Seethecalibra 1 tionsectioninthe HeatNetControl IOM to enter the calibra tion menus The ignition transformer is energized The pilot solenoid valve 2 opens for the...

Страница 26: ...tch on HeatNet control 13 board to the LOW FIRE position The boiler will begin the start up sequence 14 Allow the boiler to pre purge and enter the pilot ignition cycle 15 Ifpilotlights indicatedbyago...

Страница 27: ...ARED STATE A few random speckles of red are acceptable but large concentrations of spots or large areas of red are not If large amounts of red concentrations are observed verify combustion readings Le...

Страница 28: ...orrectly When finished disable the low fire hold switch and replace test 8 portstonormalstate Removethemanometerconnectionsand close the control panel door The Futera XLF boiler allows for many modes...

Страница 29: ...could indicate undersized gas line or insufficient gas supply Staticandoperatinggaspressurerequiredatthegasvalveinletis 2 listed in the Table above If the gas pressure is above the limit above a lock...

Страница 30: ...he gas supply lines and turn 1 off electrical power to the boiler water heater RemoveburnerfollowingtheinstructionsintheBurnerRemoval 2 section Remove the front jacket panel and combustion chamber doo...

Страница 31: ...does contact a qualified service technician to have it inspected NEVERtrytocleanorrepairthereliefvalve Ifthevalve fails to operate properly have it replaced Theaquastathighlimitcontrolsthemaximumwater...

Страница 32: ...32 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Futera XLF pressure sensor hose routing Figure 23...

Страница 33: ...33 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Exploded view Figure 24 Repair parts...

Страница 34: ...34 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Repair parts continued Figure 20 Electrical components Figure 25...

Страница 35: ...11 0412 1 1 NS Flange 2 11 0219 2 2 19 Low Gas Pressure Switch Manual Reset 11 0422 1 1 NS Firing Valve 3 4 11 0461 1 1 NS Ball Valve 11 0395 1 1 20 Gas Hose 53 4001 1 1 21 Firing Valve 2 11 0459 1 1...

Страница 36: ...252 1 1 46 Heat Exchanger Assembly Copper 70 3577 1 70 3579 1 Heat Exchanger Assembly cupronickel 70 3581 1 70 3583 1 47 O ring 06 0007 2 2 48 Frequency Drive 15 0230 1 1 49 Flame Safeguard RM7897C 16...

Страница 37: ...0 Collar Fan Transition 01 0201s 1 1 60a Gasket 06 0004 1 1 60b Fan Hold Down Plate 04 0596 1 1 61 Pump Contactor Relay 15 0118 2 2 62 Mini Fan 12 0021 1 1 63 Air Funnel 04 1016 1 1 64 Solenoid Valve...

Страница 38: ...h in the bottom right of the electrical panel on the main HeatNet board Also locate the manometer test manifold in the bottom of the electrical panel Disable any external call for heat and toggle the...

Страница 39: ...pbelow140 o F 60o C Operating atlowerreturntemperaturesislikelytocausecondensationintheprimaryheatexchanger resultingincorrosionandpossible failure of the heat exchanger COMMISSIONING THE BOILER WATER...

Страница 40: ...ead in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS INSPECTION The state or local gas inspector of the side g wall horizontally vented gas...

Отзывы: