RBI Futera XLF 4000 Скачать руководство пользователя страница 5

5

Finned copper tube gas boilers & water heaters – Boiler manual

FTXLF-IOM-HN-1-110308 Copyright 2008 Mestek, Inc.

  Never operate the Futera XLF in an  environment 

subjected to a negative pressure unless it is Direct 

Vented. Failure to comply with this warning can result 

in excessive levels of carbon monoxide causing severe 

personal injury or death!

All air from inside the building 

If the Futera XLF is to be located in a confined space, the minimum 

clearances listed in Table 1, page 4 must be maintained between it 

and any combustible construction. When installed in a confined 

space without the intake air option (as in Figure 5, page 10 through 

Figure 8, page 13) two permanent openings communicating with 

an additional room(s) are required. The combined volume of 

these spaces must have sufficient volume to meet the criteria for 

an unconfined space. The total air requirements of all gas utiliza-

tion equipment, fireplaces, wood stoves or any type of exhaust 

fan must be considered when making this determination. Each 

opening must have a minimum free area of 1 in

2

/1000 Btu/hr, 

2200 mm

2

/kW based on the total input rating of ALL gas utilization 

equipment in the confined area. Each opening must be no less than  

100 in

2

, 64,516 mm

2

 in size. The upper opening must be within 

12 inches, 305 mm of, but not less than 3 inches, 76 mm from, the 

top of the enclosure. The bottom opening must be within 12 inches, 

305 mm of, but not less than 3 inches, 76 mm from, the bottom of 

the enclosure.

All air from outside the building 

When installed in a confined space without utilizing the intake air 

option two permanent openings communicating directly with, or 

by ducts to, the outdoors or spaces that freely communicate with 

the outdoors must be present. The upper opening must be within 

12 inches, 305 mm of, but not less than 3 inches, 76 mm from, the 

top of the enclosure. The bottom opening must be within 12 inches, 

305 mm of, but not less than 3 inches, 76 mm from, the bottom of 

the enclosure.

Where directly communicating with the outdoors or communicating 

with the outdoors through vertical ducts, each opening shall have a 

minimum free area of 1 in

2

/4000 Btu/hr, 550 mm

2

/kW of the total 

input rating of all of the equipment in the enclosure.

Where communicating with the outdoors through horizontal ducts, 

each opening shall have a minimum free area of 1 in

2

/2000 Btu/hr, 

1100 mm

2

/kW of the total input rating of all of the equipment in 

the enclosure. 

When ducts are used, they must have the same cross-sectional area 

as the free area of the opening to which they connect.

When calculating the free area necessary to meet the make-up air 

requirements of the enclosure, consideration must be given to the 

blockage effects of louvers, grills and screens. Screens must have a 

minimum mesh size of 1/4 inch, 6.4 mm. If the free area through a 

louver or grill is not known, ducts should be sized per Table 2.

Canadian installations must comply with CSA B149.1 when air sup-

ply is provided by natural air flow from the outdoors for natural draft, 

partial fan-assisted, fan-assisted, or power draft-assisted burners, there 

shall be a permanent air supply opening(s) having a cross-sectional 

area of not less than 1 in

2

 per 7,000 Btuh (310 mm

2

 per kW) up to 

and including 1 million Btuh, plus 1 in

2

 per 14,000 Btuh (155 mm

2

 

per kW) in excess of 1 million Btuh. 

Make-up Air Louver Sizing

table 2 

Input 

MBH

Required cross-sectional area

Wire screen

¼ inch (6.4 mm)

Metal louvers 

75% free area

Wooden louvers 

25% free area

in

2

cm

2

in

2

cm

2

in

2

cm

2

3000

750

4838

1000

6452

3000

19354

4000

1000

6452

1334

8592

4000

25808

intake air option — General guidelines 

This configuration provides combustion air directly to the boiler/

water heater’s air intake adapter using a dedicated pipe when using 

the direct vent option. Combustion air can be drawn in horizontally 

through the same outside wall which terminates the exhaust gases 

or vertically through the roof, see Figure 1, page 8 through Figure 4, 

page 9.

  Common intake air systems may be used provided the 

common duct is sized properly. An intake combustion 

air damper should be installed if the common vent 

option is used in the intake air pipe of each heater. 

Improper installation can result in excessive levels of 

carbon monoxide which can cause severe personal 

injury or death!

Intake air pipe sizing

table 3 

Input 

MBH

Vertical

Horizontal

in

mm

in

mm

3000

10

254

8

203

4000

12

305

10

254

All  joints  in  metal  intake  air  systems  must  be  secured  using 

corrosion  resistant  fasteners  and  sealed  using  a  suitable  Sili-

cone  caulk.  If  PVC  or  CPVC  is  used,  the  joints  must  be  

cleaned with a suitable solvent and connected using a solvent based 

PVC cement. 

  The combustion air system MUST be supported by the 

building structure not the boiler/water heater.

  A combustion air damper interlocked with the unit 

should be installed in the intake air pipe when the 

infiltration of subfreezing air could occur, otherwise 

the unit could freeze up voiding the warranty!

intake air option – Vertical guidelines 

The maximum equivalent length for the vertical intake air pipe is 

100 ft, 30.5 m. Each 90

o

 elbow and the intake air terminal are equal 

to 10 linear ft, 3.0 m of pipe, see Table 3.

An approved, nonrestrictive intake air terminal must be used. The 

intake air terminal must terminate as shown in Figure 3, page 9. The 

penetration point in the roof must be properly flashed and sealed.

Содержание Futera XLF 4000

Страница 1: ...boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property...

Страница 2: ...DP switch blocked air 10 inlet DP switch blocked flue 11 DP switch blower prov 12 ing DP switch pilot air prov 13 ing Ignitor 14 Pilot gas valve and pilot gas 15 pressure regulator Flow switch 16 Low...

Страница 3: ...ommonwealth of Massachusetts you MUST FOLLOW the additional instructions contained in RBI s instruc tion sheet MACODE 3 located in the back of this manual The owner should maintain a record of all ser...

Страница 4: ...it abledrainpanthat sadequatelydrainedmustbeinstalledunder the unit DO NOT place this boiler water heater in a location that 5 would restrict the introduction of combustion air into the unit or subjec...

Страница 5: ...ating the free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh s...

Страница 6: ...nd win 3 dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appl...

Страница 7: ...be joined and sealed in accordance with the vent system manufacturer s instructions Whenhorizontalventrunsexceed5ft 1 5mtheymustbesupported at 3 ft 0 9 m intervals with overhead hangers The vent syst...

Страница 8: ...nning horizontal combustion air and venting for single or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences...

Страница 9: ...ot exceed 100 feet each See Table 3 or 4 for min pipe diameters Locate exhaust terminal downwind from air intake to reduce potential for flue gas recirculation Failure to complycouldresultinsevere per...

Страница 10: ...ed and sized Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems Table 5 lists the equivalent breeching and flue sizes required for the boiler...

Страница 11: ...alent lengths up to100 feet maximum In this configuration the boiler water heater blower is used to push the flue products horizontally to the outdoors see Figure 7 The air for combustion is taken fro...

Страница 12: ...s than 33 input Category II chimney inspection sizing Masonry chimneys when used must be lined with a metal liner certified for Category IV venting A thorough inspection of the masonry chimney must be...

Страница 13: ...vent system is designed using accepted engineering practices and the design calculations prove there is no need for barometric dampers the barometric dampers may be omitted When required by ap plicab...

Страница 14: ...proved method If the unit must be shut off for any reason the electric 3 gas and water supplies MUST be shut off and the unit and its pump completely drained Improper outdoor installation of this unit...

Страница 15: ...15 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Futera XLF Piping Figure 9...

Страница 16: ...rmal expansion must be installed in the heating system An expansion tank must be installed close to the boiler on the suction side of the pump An air scoop and automatic air vent must also be installe...

Страница 17: ...2 requirements All boilers furnished with factory mounted 3 outlet water temperature gauge Boiler pump purging required Use termi 4 nals supplied All primary secondary piping systems re 5 quire a rem...

Страница 18: ...intain Inlet Temperature Above Dew Point T1 Temp Min 140o F 60o C Sealed Combustion 1 Turn heater on and open valves A B 2 After steady state operation if T1 is less than Temp Min slowly close valve B...

Страница 19: ...ghaFuteraXLF water heater is 260 GPM 16 4 L when equipped with coppertubes Thecupronickelheatexchangerallowsfor 315 GPM 19 9 L s See Table 9 page 20 RBI water heaters are designed to run scale free Du...

Страница 20: ...ditional precautions must be observed due to unusual characteristics of the local water supply Call the nearest RBI representative for details To properly size the pump a grain hardness andpHtestmustb...

Страница 21: ...th 30 total 6 90 4 o elbows full pipe size CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 5 The pH and water hardness must be measured before selecting heat exchanger and pump Consult the Heat Exch...

Страница 22: ...y piping has the capacity to meet the demand Figure16depictstheproperwaytoconnecttheboiler waterheater to the gas supply piping The manual shut off valve MUST be in stalled in the supply piping It sho...

Страница 23: ...Gate valve Gas cock 2 5 2 10 3 1 2 3 0 2 6 2 12 3 1 4 3 5 3 7 7 15 3 1 8 4 5 4 10 1 20 2 2 4 6 0 5 12 6 25 2 2 9 7 3 6 15 2 30 4 3 5 13 4 Equivalent lengths above are for threaded fittings Multiply v...

Страница 24: ...the heating system piping Close the make upwatervalveandcheckandcleanthestrainersandmake upwater pressure reducing valve Openthemake upwatervalveandadjustthesystempressureifnec essary The system shou...

Страница 25: ...loweroperatesatminimumignitionsetting Seethecalibra 1 tionsectioninthe HeatNetControl IOM to enter the calibra tion menus The ignition transformer is energized The pilot solenoid valve 2 opens for the...

Страница 26: ...tch on HeatNet control 13 board to the LOW FIRE position The boiler will begin the start up sequence 14 Allow the boiler to pre purge and enter the pilot ignition cycle 15 Ifpilotlights indicatedbyago...

Страница 27: ...ARED STATE A few random speckles of red are acceptable but large concentrations of spots or large areas of red are not If large amounts of red concentrations are observed verify combustion readings Le...

Страница 28: ...orrectly When finished disable the low fire hold switch and replace test 8 portstonormalstate Removethemanometerconnectionsand close the control panel door The Futera XLF boiler allows for many modes...

Страница 29: ...could indicate undersized gas line or insufficient gas supply Staticandoperatinggaspressurerequiredatthegasvalveinletis 2 listed in the Table above If the gas pressure is above the limit above a lock...

Страница 30: ...he gas supply lines and turn 1 off electrical power to the boiler water heater RemoveburnerfollowingtheinstructionsintheBurnerRemoval 2 section Remove the front jacket panel and combustion chamber doo...

Страница 31: ...does contact a qualified service technician to have it inspected NEVERtrytocleanorrepairthereliefvalve Ifthevalve fails to operate properly have it replaced Theaquastathighlimitcontrolsthemaximumwater...

Страница 32: ...32 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Futera XLF pressure sensor hose routing Figure 23...

Страница 33: ...33 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Exploded view Figure 24 Repair parts...

Страница 34: ...34 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Repair parts continued Figure 20 Electrical components Figure 25...

Страница 35: ...11 0412 1 1 NS Flange 2 11 0219 2 2 19 Low Gas Pressure Switch Manual Reset 11 0422 1 1 NS Firing Valve 3 4 11 0461 1 1 NS Ball Valve 11 0395 1 1 20 Gas Hose 53 4001 1 1 21 Firing Valve 2 11 0459 1 1...

Страница 36: ...252 1 1 46 Heat Exchanger Assembly Copper 70 3577 1 70 3579 1 Heat Exchanger Assembly cupronickel 70 3581 1 70 3583 1 47 O ring 06 0007 2 2 48 Frequency Drive 15 0230 1 1 49 Flame Safeguard RM7897C 16...

Страница 37: ...0 Collar Fan Transition 01 0201s 1 1 60a Gasket 06 0004 1 1 60b Fan Hold Down Plate 04 0596 1 1 61 Pump Contactor Relay 15 0118 2 2 62 Mini Fan 12 0021 1 1 63 Air Funnel 04 1016 1 1 64 Solenoid Valve...

Страница 38: ...h in the bottom right of the electrical panel on the main HeatNet board Also locate the manometer test manifold in the bottom of the electrical panel Disable any external call for heat and toggle the...

Страница 39: ...pbelow140 o F 60o C Operating atlowerreturntemperaturesislikelytocausecondensationintheprimaryheatexchanger resultingincorrosionandpossible failure of the heat exchanger COMMISSIONING THE BOILER WATER...

Страница 40: ...ead in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS INSPECTION The state or local gas inspector of the side g wall horizontally vented gas...

Отзывы: