RBI Futera XLF 4000 Скачать руководство пользователя страница 30

30

Finned copper tube gas boilers & water heaters – Boiler manual

FTXLF-IOM-HN-1-110308 Copyright 2008 Mestek, Inc.

mAintenAnce

  Disconnect electrical power and close the manual gas 

shut off valve before performing maintenance or severe 

personal injury may result!

  Servicing, inspection and adjustment must be done by 

a trained technician in accordance with all applicable 

local  and  national  codes.  Improper  servicing  or 

adjustment can damage the boiler/water heater!

The boiler/water heater must be cleaned and inspected at least once 

a year and before each heating season. Make sure that the burner and 

ignition components are free from dust, soot, dirt, corrosion or other 

deposits that would impair the boiler/water heater ‘s performance. 

Refer to Figure 20, page 28 for component identification.

  Improper burner servicing can result in premature 

burner failure voiding the warranty!

pilot and burner removal 

Close the manual shutoff valves in the gas supply line and turn 

1. 

off electrical power to the boiler/water heater. 

Remove the jacket top panel. 

2. 

Remove wires from the spark rods and remove the UV sensor 

3. 

from the transition piece. 

Remove the pilot assembly:

4. 

Disconnect the compression nut at the front of the pilot 

a. 

block.

Remove the pilot gas tubing.

b. 

Remove the (2) screws from the pilot block.

c. 

Remove the pilot assembly.

d. 

Disconnect the flexible gas line from the manifold.

5. 

Disconnect the wires to the fan and remove the (2) bolts and the 

6. 

fan hold-down plates that secure the fan to the transition piece.

Lift and remove the fan housing from the boiler/water heater, tak-

7. 

ing care not to damage the spark rods and or their alignment. 

Remove the four nuts holding the transition piece to the heat 

8. 

exchanger. 

Remove the transition piece, taking care not to damage the 

9. 

O-ring.
Remove the burner, taking care not to damage the gasket.

10. 

Replace all components after servicing.

11. 

Heat exchanger inspection

Close the manual shutoff valves in the gas supply lines and turn 

1. 

off electrical power to the boiler/water heater. 

Remove burner following the instructions in the Burner Removal 

2. 

section. 

Remove the front jacket panel and combustion chamber door. 

3. 

Inspect  the  inside  and  outside  of  the  heat  exchanger  

4. 

for signs of damage, sooting or corrosion. 

The outside surfaces of the copper tubes should be free of 

5. 

any  soot  deposits.  A  slight  black  smudge  is  normal  with  

some types of gases. Black soot indicates poor combustion. 

Green deposits indicate condensation due to low return water 

temperatures. In either case the heat exchanger must be cleaned 

thoroughly and the problem resolved before the boiler/water 

heater is returned to service. 

If there are no signs of damage, sooting or corrosion, reassemble 

6. 

the unit following the previous steps in reverse order. 

A  badly  corroded  or  damaged  heat  exchanger  must  

7. 

be replaced, see the Heat Exchanger Repair & Replacement sec-

tion.

Heat exchanger cleaning

Close the shut off valves in the inlet and outlet piping. On heating 

1. 

systems close the system fill valve and relieve the system pressure 

from the boiler by carefully lifting the relief valve or opening the 

drain valve. 

Disconnect the boiler/water heater from the system piping. 

2. 

Remove the eight bolts on the rear pipe enclosure panel. 

3. 

Remove the front jacket panel and combustion chamber door. 

4. 

Slide the heat exchanger out of the unit. 

5. 

Remove the “V” baffle straps and “V” baffles. 

6. 

Thoroughly  clean  the  heat  exchanger  with  water  from  

7. 

a high-pressure hose. Use a soft bristle brush if necessary. 

Replace the cleaned heat exchanger and other components in 

8. 

the reverse order of their removal.

Heat exchanger repair & replacement

A leaking or otherwise damaged tube(s) can be replaced as out-

1. 

lined in steps 2 through 8. 

Remove the heat exchanger from the boiler/water heater as out-

2. 

lined in the Heat Exchanger Cleaning section. 

Remove the pipe plugs from the inlet/outlet and return headers 

3. 

opposite from the ends of the tube(s) being replaced. 

Carefully cut the damaged tube(s) in half, taking care not to dam-

4. 

age the adjacent tubes and remove. 

Install and swage/expand in place the new tube(s). 

5. 

Содержание Futera XLF 4000

Страница 1: ...boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property...

Страница 2: ...DP switch blocked air 10 inlet DP switch blocked flue 11 DP switch blower prov 12 ing DP switch pilot air prov 13 ing Ignitor 14 Pilot gas valve and pilot gas 15 pressure regulator Flow switch 16 Low...

Страница 3: ...ommonwealth of Massachusetts you MUST FOLLOW the additional instructions contained in RBI s instruc tion sheet MACODE 3 located in the back of this manual The owner should maintain a record of all ser...

Страница 4: ...it abledrainpanthat sadequatelydrainedmustbeinstalledunder the unit DO NOT place this boiler water heater in a location that 5 would restrict the introduction of combustion air into the unit or subjec...

Страница 5: ...ating the free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh s...

Страница 6: ...nd win 3 dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appl...

Страница 7: ...be joined and sealed in accordance with the vent system manufacturer s instructions Whenhorizontalventrunsexceed5ft 1 5mtheymustbesupported at 3 ft 0 9 m intervals with overhead hangers The vent syst...

Страница 8: ...nning horizontal combustion air and venting for single or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences...

Страница 9: ...ot exceed 100 feet each See Table 3 or 4 for min pipe diameters Locate exhaust terminal downwind from air intake to reduce potential for flue gas recirculation Failure to complycouldresultinsevere per...

Страница 10: ...ed and sized Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems Table 5 lists the equivalent breeching and flue sizes required for the boiler...

Страница 11: ...alent lengths up to100 feet maximum In this configuration the boiler water heater blower is used to push the flue products horizontally to the outdoors see Figure 7 The air for combustion is taken fro...

Страница 12: ...s than 33 input Category II chimney inspection sizing Masonry chimneys when used must be lined with a metal liner certified for Category IV venting A thorough inspection of the masonry chimney must be...

Страница 13: ...vent system is designed using accepted engineering practices and the design calculations prove there is no need for barometric dampers the barometric dampers may be omitted When required by ap plicab...

Страница 14: ...proved method If the unit must be shut off for any reason the electric 3 gas and water supplies MUST be shut off and the unit and its pump completely drained Improper outdoor installation of this unit...

Страница 15: ...15 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Futera XLF Piping Figure 9...

Страница 16: ...rmal expansion must be installed in the heating system An expansion tank must be installed close to the boiler on the suction side of the pump An air scoop and automatic air vent must also be installe...

Страница 17: ...2 requirements All boilers furnished with factory mounted 3 outlet water temperature gauge Boiler pump purging required Use termi 4 nals supplied All primary secondary piping systems re 5 quire a rem...

Страница 18: ...intain Inlet Temperature Above Dew Point T1 Temp Min 140o F 60o C Sealed Combustion 1 Turn heater on and open valves A B 2 After steady state operation if T1 is less than Temp Min slowly close valve B...

Страница 19: ...ghaFuteraXLF water heater is 260 GPM 16 4 L when equipped with coppertubes Thecupronickelheatexchangerallowsfor 315 GPM 19 9 L s See Table 9 page 20 RBI water heaters are designed to run scale free Du...

Страница 20: ...ditional precautions must be observed due to unusual characteristics of the local water supply Call the nearest RBI representative for details To properly size the pump a grain hardness andpHtestmustb...

Страница 21: ...th 30 total 6 90 4 o elbows full pipe size CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 5 The pH and water hardness must be measured before selecting heat exchanger and pump Consult the Heat Exch...

Страница 22: ...y piping has the capacity to meet the demand Figure16depictstheproperwaytoconnecttheboiler waterheater to the gas supply piping The manual shut off valve MUST be in stalled in the supply piping It sho...

Страница 23: ...Gate valve Gas cock 2 5 2 10 3 1 2 3 0 2 6 2 12 3 1 4 3 5 3 7 7 15 3 1 8 4 5 4 10 1 20 2 2 4 6 0 5 12 6 25 2 2 9 7 3 6 15 2 30 4 3 5 13 4 Equivalent lengths above are for threaded fittings Multiply v...

Страница 24: ...the heating system piping Close the make upwatervalveandcheckandcleanthestrainersandmake upwater pressure reducing valve Openthemake upwatervalveandadjustthesystempressureifnec essary The system shou...

Страница 25: ...loweroperatesatminimumignitionsetting Seethecalibra 1 tionsectioninthe HeatNetControl IOM to enter the calibra tion menus The ignition transformer is energized The pilot solenoid valve 2 opens for the...

Страница 26: ...tch on HeatNet control 13 board to the LOW FIRE position The boiler will begin the start up sequence 14 Allow the boiler to pre purge and enter the pilot ignition cycle 15 Ifpilotlights indicatedbyago...

Страница 27: ...ARED STATE A few random speckles of red are acceptable but large concentrations of spots or large areas of red are not If large amounts of red concentrations are observed verify combustion readings Le...

Страница 28: ...orrectly When finished disable the low fire hold switch and replace test 8 portstonormalstate Removethemanometerconnectionsand close the control panel door The Futera XLF boiler allows for many modes...

Страница 29: ...could indicate undersized gas line or insufficient gas supply Staticandoperatinggaspressurerequiredatthegasvalveinletis 2 listed in the Table above If the gas pressure is above the limit above a lock...

Страница 30: ...he gas supply lines and turn 1 off electrical power to the boiler water heater RemoveburnerfollowingtheinstructionsintheBurnerRemoval 2 section Remove the front jacket panel and combustion chamber doo...

Страница 31: ...does contact a qualified service technician to have it inspected NEVERtrytocleanorrepairthereliefvalve Ifthevalve fails to operate properly have it replaced Theaquastathighlimitcontrolsthemaximumwater...

Страница 32: ...32 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Futera XLF pressure sensor hose routing Figure 23...

Страница 33: ...33 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Exploded view Figure 24 Repair parts...

Страница 34: ...34 Finned copper tube gas boilers water heaters Boiler manual FTXLF IOM HN 1 110308 Copyright 2008 Mestek Inc Repair parts continued Figure 20 Electrical components Figure 25...

Страница 35: ...11 0412 1 1 NS Flange 2 11 0219 2 2 19 Low Gas Pressure Switch Manual Reset 11 0422 1 1 NS Firing Valve 3 4 11 0461 1 1 NS Ball Valve 11 0395 1 1 20 Gas Hose 53 4001 1 1 21 Firing Valve 2 11 0459 1 1...

Страница 36: ...252 1 1 46 Heat Exchanger Assembly Copper 70 3577 1 70 3579 1 Heat Exchanger Assembly cupronickel 70 3581 1 70 3583 1 47 O ring 06 0007 2 2 48 Frequency Drive 15 0230 1 1 49 Flame Safeguard RM7897C 16...

Страница 37: ...0 Collar Fan Transition 01 0201s 1 1 60a Gasket 06 0004 1 1 60b Fan Hold Down Plate 04 0596 1 1 61 Pump Contactor Relay 15 0118 2 2 62 Mini Fan 12 0021 1 1 63 Air Funnel 04 1016 1 1 64 Solenoid Valve...

Страница 38: ...h in the bottom right of the electrical panel on the main HeatNet board Also locate the manometer test manifold in the bottom of the electrical panel Disable any external call for heat and toggle the...

Страница 39: ...pbelow140 o F 60o C Operating atlowerreturntemperaturesislikelytocausecondensationintheprimaryheatexchanger resultingincorrosionandpossible failure of the heat exchanger COMMISSIONING THE BOILER WATER...

Страница 40: ...ead in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS INSPECTION The state or local gas inspector of the side g wall horizontally vented gas...

Отзывы: